—SELECTION GUIDE ReliaGear® Merchandised panelboardsA panelboard offer ready to go for projects with quick turnaround05/24

Page 2

— ReliaGear® Merchandised neXT SuperBox power panelboardsProduct overviewA fully assembled panelboard offer ready to go from inventory for projects with quick turnaround. The SuperBox offer is a preconfigured combination of enclosure, interior, ground, neutral, front and fillers available from inventory for immediate installation. One SKU includes everything needed for the power  circuit breakers and accessories required for the project, and you’re ready to go.11 Other ReliaGear neXT configurations are available as factory-assembled, made-to-order items. Contact your local ABB sales team for more information.RELIAGEAR® MERCHANDISED NEXT SUPERBOX POWER PANELBOARDSProjects with quick turnaround Emergency situations, data centers, commercial renovation or building expansionsNo lead timeQuickly and efficiently install these readily available panelboards from distributor inventoryFlexible Designchanges in the field, single-tool installation and plug-in breakers for quick location flexibility

Page 3

B1 copy starts hereB2 copy starts hereB3 copy starts here— ReliaGear® Merchandised neXT SuperBox power panelboardsGeneral characteristicsSystem voltages • • • • • • Short circuit rating  installed, except as noted in the series rating listed with an integral or remote main breaker or fusible switch installed ahead of the power panel.Enclosures • to personnel against access to hazardous parts and toprovide a degree of protection against ingress of solidforeign objects (falling dirt).• degree of protection to personnel against access tohazardous parts, falling dirt and harmful effects on theand that will be undamaged by the external formation of iceand snow with no damage to the external enclosure.BussingSilver-plated copper Certifications • • • Federal specification W-C-375, rev. B, amend. 1,and service• power distribution• • • UL 50, enclosures for electrical equipment• UL 67, panelboards• cUL listed, low-voltage modular power panels• RELIAGEAR® MERCHANDISED NEXT SUPERBOX POWER PANELBOARDSPart IdentifierDescription CodeR N S BEnclosure WidthDescription Code4 045Panel AmpacityDescription Code0 60 81 2Enclosure HeightDescription Code6 07 28 49 6Enclosure TypeDescription CodeARG 6 4 5 RB 21 9SNRMain typeDescription CodeMain LugsLMain BreakerBGround Fault Main BreakerG

Page 4

— ReliaGear® Merchandised neXT SuperBox power panelboardsSelectionSelect main and branch feeder circuit breakers1234Determine the X-space required to meet main and branch feeder circuit breaker selectionSelect the SuperBox required based on maximum ampacity, main type, enclosure type, and bus X-space requiredSelect the required accessoriesRELIAGEAR® MERCHANDISED NEXT SUPERBOX POWER PANELBOARDS

Page 5

B1 copy starts hereB2 copy starts hereB3 copy starts here— ReliaGear® Merchandised neXT SuperBox power panelboardsStep 1: Select main and branch feeder circuit breakers (XT1–XT2)1,2Frame Int. rating at 480 V AC Trip unit Poles AmpsLoad side lugs (AWG or kcmil) Ordering code TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF     TMF                                                                      1 Additional Tmax® XT plug-in circuit breakers and accessories are available. Contact your local ABB sales team for more information.2 All breakers are standard rated (standard circuit breakers design considers 80% of the rated load). In case a 100% rated breaker is needed, a factory assembled ReliaGear neXT configuration will be required.Separate mounting rail required. See details in accessories table.Breakers installed in panel must adhere to UL/NEC WBS requirements. RELIAGEAR® MERCHANDISED NEXT SUPERBOX POWER PANELBOARDS

Page 6

Frame Int. rating at 480 V Trip unit Poles AmpsLoad side lugs (AWG or kcmil) Ordering code  TMF      TMF      TMF      TMF      TMF      TMF      TMF      TMF      TMF      TMF      TMF      TMF      TMF      TMF      TMF      TMF                                                                                                                                                                                                          1 Additional Tmax® XT plug-in circuit breakers and accessories are available. Contact your local ABB sales team for more information.2 All breakers are standard rated (standard circuit breakers design considers 80% of the rated load). In case a 100% rated breaker is needed, a factory assembled ReliaGear neXT configuration will be required.3 Breakers installed in panel must adhere to UL/NEC WBS requirements— ReliaGear® Merchandised neXT SuperBox power panelboardsStep 1: Select main and branch feeder circuit breakers (XT4)1,2RELIAGEAR® MERCHANDISED NEXT SUPERBOX POWER PANELBOARDS

Page 7

B1 copy starts hereB2 copy starts hereB3 copy starts here— ReliaGear® Merchandised neXT SuperBox power panelboardsStep 1: Select main and branch feeder circuit breakers (XT5–XT7)1,2,3Frame Int. rating at 480 V Trip unit Poles AmpsLoad side lugs (AWG or kcmil) RELT compatible Ordering code      No       No       No       No       No       No       No       No       No       No       No       No       No       No       No       No       No       No       No       No       No       No       No       No       No       No       No       No       No       No       No       No   Ekip Touch LSI    Yes   Ekip Touch LSI    Yes   Ekip Touch LSI    Yes   Ekip Touch LSI    Yes   Ekip Touch LSI    Yes   Ekip Touch LSIG    Yes   Ekip Touch LSIG    Yes   Ekip Touch LSIG    Yes 1Additional Tmax® XT plug-in circuit breakers and accessories are available. Contact your local ABB sales team for more information.2 All breakers are standard rated (standard circuit breakers design considers 80% of the rated load). In case a 100% rated breaker is needed, a factory assembled ReliaGear neXT configuration will be required.3 If 750 kcmil lugs are needed, a factory assembled ReliaGear neXT configuration will be required.4 Breakers installed in panel must adhere to UL/NEC WBS requirements.RELIAGEAR® MERCHANDISED NEXT SUPERBOX POWER PANELBOARDS

Page 8

— ReliaGear® Merchandised neXT SuperBox power panelboardsStep 1: Select main and branch feeder circuit breakers (TEY–FB)1,2Frame Int. rating at 480 V Trip unit Poles Amps PhaseLoad side lugs (AWG or kcmil) Ordering codeTEY  TMF     TEY  TMF   B  TEY  TMF   C  TEY  TMF     TEY  TMF   B  TEY  TMF   C   TEY  TMF     TEY  TMF   B  TEY  TMF   C  TEY  TMF     TEY  TMF     TEY  TMF   BC  TEY  TMF   BC  TEY  TMF     TEY  TMF     FB TMF     FB TMF   B  FB TMF   C  FB TMF     FB TMF     FB TMF   B  FB TMF   B  FB TMF   C  FB TMF   C  FB  TMF      FB  TMF   BC  FB  TMF     FB  TMF     FB  TMF     FB  TMF     FB  TMF     FB  TMF     FB  TMF     FB  TMF   BC  FB  TMF   BC  FB  TMF   BC  FB  TMF   BC  FB  TMF   BC  FB  TMF   BC  FB  TMF     FB  TMF     FB  TMF     FB  TMF     FB  TMF     FB  TMF     1Additional TEY and FB plug-in circuit breakers and accessories are available. Contact your local ABB sales team for more information.2 All breakers are standard rated (standard circuit breakers design considers 80% of the rated load). In case a 100% rated breaker is needed, a factory assembled ReliaGear neXT configuration will be required.3Interrupt rating at 240 V AC.4 Breakers installed in panel must adhere to UL/NEC WBS requirements.—1-pole FB —2-pole FB—1-pole TEY—2-pole TEYRELIAGEAR® MERCHANDISED NEXT SUPERBOX POWER PANELBOARDS

Page 9

B1 copy starts hereB2 copy starts hereB3 copy starts here— ReliaGear® Merchandised neXT SuperBox power panelboardsStep 1: Select main and branch feeder circuit breakers (Formula A2)1,2,3FrameInt. rating at 240 V Trip unit Poles Amps PhaseCu load side lugs (AWG or kcmil)Al load side lugs (AWG or kcmil) Ordering code  TMF        TMF        TMF        TMF        TMF        TMF        TMF        TMF        TMF        TMF        TMF        TMF        TMF     — 1 Additional Formula A2 plug-in circuit breakers are available. Contact your local ABB sales team for more information.2 All breakers are standard rated (standard circuit breakers design considers 80% of the rated load). In case a 100% rated breaker is needed, a factory-assembled ReliaGear neXT configuration will be required.3 250 A Formula A2 plug-in breakers with 350 kcmil Al load side lugs available. Contact your local ABB sales team for more information.4 Breakers installed in panel must adhere to UL/NEC WBS requirements.—RELIAGEAR® MERCHANDISED NEXT SUPERBOX POWER PANELBOARDS

Page 10

— ReliaGear® Merchandised neXT SuperBox power panelboardsStep 2: Select the required accessories3Group Type Volts AC XT1 XT2 XT4 XT52XT6 XT7 TEY FB A2contactsQ = Indication of the status of the circuit breakerSY = Bell alarm     – – – –     – – – –     – – – –  –  – – – –  –  – – –  –  – – –  –  – – –  –  – – –Shunt trip      ZEZSZ – – –     – – –    – – –Undervoltage release      – – –      – – –      – – –Fixed padlockOpen position –      – – – –     –    –Removable padlock – – – – – – – – RELT RELT kit – – – – –  – – –RELT kit – – – – –  – – –RELT kit – – – – –  – – –RELT wire connector – – – – – – – – –RELT wire connector – – – – – – – – –Mounting rail  –  – – – – – – – – –  – – – – – – – – –  – – – – – – – –Blank and fillers – – – – – – – – –  – – – – – – – – –  – – – – – – – – –  – – – – – – – – –  – – – – – – – – –  – – – – – – – – –  –  – – – – – – – –Service entrance barriers –       – – –1 Padlocks are not included in the kit.2 Tmax XT5 electrical accessories require 1 (one) extra X-space for installation.3 Additional Tmax XT accessories are available. Contact your local ABB sales team for more information.4 Requires XT7 equipped with Ekip Touch or above trip unit, 3 X-space factor required. 5 CN003 includes Ekip 2K-1 signaling and Ekip supply. CN004 includes Ekip 2K-3 signaling and Ekip supply. CN004 is ONLY compatible with firmware version 3.10.00 or higher. Refer to 9AKK107991A2520 to validate firmware version.6 SBX2WT2P3 for XT2 thermo mag, SBX2WE2P3 for XT2 Ekip 7 SBX4W30P3 for 300 kcmil, SBX4W35P3 for 350 kcmil——Shunt trip—Fixed padlock —RELT—Mounting railRELIAGEAR® MERCHANDISED NEXT SUPERBOX POWER PANELBOARDS

Page 11

B1 copy starts hereB2 copy starts hereB3 copy starts here———— ReliaGear® Merchandised neXT SuperBox power panelboardsStep 3: Determine the X-space requiredEach circuit breaker frame has specific requirements for the number of mounting positions (X-spaces). Thanks to required are lower when two or five breakers are mounted close to one another. RELTs also require X-space, since they are plug-in modules. Refer to the table below and add up the number of X-spaces required for each breaker frame.Frame Max. ampacity (A) Poles X-spaces   3   5   11   3   3  4   6   6FB   1FB   2TEY   1TEY   2   2RELT – – 3 – – 101 Tmax® XT5 with electrical accessories requires 1 (one) additional X-space.of this feature, unique mounting brackets are required when mounting brackets required. These additional rails are not included with SuperBox configurations and must be ordered as accessories.Order codes for XT1 mounting rails • • • ———RELIAGEAR® MERCHANDISED NEXT SUPERBOX POWER PANELBOARDS

Page 12

— ReliaGear® Merchandised neXT SuperBox power panelboardsStep 4: Select the SuperBox required—40" offset enclosure—45" offset enclosuredouble sided. Wire bending space requirements interior. —Wire bend spaceBreakerLeft mount space (in)Right mount space (in)40" offset enclosure  –                45" offset enclosure  –  –  –                Description AmpsEnclosure type MainGround fault on main compatibleDimensions(H x W x D inches)X-space leftX-space right Ordering code    No       Main breakerNo        No      Main breakerNo       No       Main breakerNo        No      Main breakerNo       No       Main breakerNo       Main breakerYes       No      Main breakerNo      Main breakerYes  1 X-space required for main breaker must be accounted for based on specific breaker selected. 2 Depth includes 0.9" of hanger bracket.3 Breakers installed in panel must adhere to UL/NEC wire bending space requirements.4 Compatible with XT7 Ekip Touch LSIG or higher.600 A1200 A 250 A250 A111455410"5.2"5.2"15.2"111765445.2"5.2"12.2 "15"20.2 "104"FBTEY2TEY1".5".3"FB14"14.5"14.3"216.4"115.2"26.4"4.3"FB4.5""4.2120.2"21.4"26.4"4.3"FBTEY2TEY14.5"4.600 A1200 A 250 A250 A111455410"5.2"5.2"15.2"111765445.2"5.2"12.2 "15"20.2 "10FBTEY2TEY1".5".3"FB14"14.5"14.3"216.4"115.2"26.4"4.3"FB4.5""4.2120.2"21.4"26.4"4.3"FBTEY2TEY14.5"4.13 .4" RELIAGEAR® MERCHANDISED NEXT SUPERBOX POWER PANELBOARDSAvailable configurations and wire bending space