TECHNICAL BROCHUREReliaGear™ neXTUL 67 low-voltage distribution power panelboards
B1 copy starts hereB2 copy starts hereB3 copy starts hereInteriorsReliaGear neXT panelboard interiors feature plug-in and bolt-on (when vertical main circuit breakers are selected) technology, IP 20 “finger-safe” features (on clean bus only) and center or offset mounting positions within the enclosure. Main lug, feed-through lug and clean bus options exist. X-height or X-space refers to the space occupied by individual (plug-in) components on the interior bus. One X-space for ReliaGear neXT equals 1.385 inches.2 RELIAGEAR NEXT30" wide circuit breaker panelCenter-mounted interior40" wide circuit breaker panelOffset-mounted interior45" wide circuit breaker panelOffset-mounted interior45" wide circuit breaker panelCenter-mounted interior—01 Typical standard, hinged gutter covers—02 Typical sheet metal fillers cover the space between gutter covers and circuit breakers/blanks—03 Typical sheet metal blanks cover the future space for adding circuit breakers to the interior Standard interior heights• 16X05• 24X05• 32X05• 40X05Interior materials• Tin- and silver-plated aluminum (heat rated)• Tin- and silver-plated copper (heat rated or 1000 A per sq. in. density rated)XT4XT4XT4 XT4XT4XT4XT1XT1XT1XT1XT1XT1FB/TEY FB/TEY225 A04225 A045.5" 5.5"30"XT4XT4XT4XT4XT4XT4XT5XT5XT1XT1XT1FB/TEY FB/TEY8" 5.5"40"600 A04225 A04XT4XT4XT4XT4XT4XT5XT6/XT7XT1XT1XT1FBFB/TEY13" 5.5"45"0302011200 A04225 A04XT4XT4XT4XT4FB/TEY600 A04XT5600 A04XT5XT5 XT1XT4XT4FB/TEY5.5" 5.5"45"Clean bus Main lug Feed-through lug—04Maximum ampacity circuit breaker allowed per this side of interior—05Interiors are double sided; double standard interior heights for available mounting space (Ex. 16X bus has 32X max. of circuit breaker mounting space)
X-space requirements for plug-in devices3INTERIORS AND X-SPACE REQUIREMENTS—X-space requirements for plug-in devices See table below for the X-space requirements of plug-in components. Frame Max. ampacity (A) Poles X-spaceSingle XT1 125 3 3Two XT1 125 3 5Five XT1 125 3 11XT4 250 3 3XT5 600 3 4XT6 800 3 6XT7 1200 3 6FB/TEY 100/70 1 1FB/TEY 100/125 2 2SPD – – 10RELT – – 3AMP1 main meter – – 4 3 X-spaces5 X-spaces11 X-spaces—Single XT1—Two XT1 = 16% space saving—Five XT1 = 26% space saving—XT1 circuit breaker assemblies — panelboard densitiy and mounting hardwareThe small footprint of XT1 allows this panel to offer multiple options to improve circuit breaker density. As you configure and order ReliaGear neXT panelboards, you'll notice that XT1 are grouped in quantities of one, two or five. As part of this feature, unique mounting brackets are required when adding XT1 breaker assemblies to existing installations. See below for X-space and mounting brackets required. Frame X-space % X-space savings (compared to single XT1 kits) Mounting hardwareSingle XT1 3 – SR1XBFTwo XT1 5 16% SR2XBFFive XT1 11 26% SR5XBFXT1 group mounting brackets are included in panelboard orders from the factory, but are sold separately when adding an XT1 to an existing installation.
B1 copy starts hereB2 copy starts hereB3 copy starts hereEnclosuresReliaGear neXT panelboards come in three widths (30", 40" and 45") and four heights (60", 72", 84" and 96"). Enclosure sizing is determined by three criteria: 1) wire-bending space required for main device; 2) interior height; and 3) the largest main or branch devices selected. For additional detail, please refer to document 1SQC900008M0201 for NEMA 1, 2, 3R, 4, 4X and 12 enclosure dimensions.4 RELIAGEAR NEXT—Enclosure depths TypeDepthBox Box and front/doorNEMA 1 11" 11"NEMA 1 + DID 11" 14.5"NEMA 2 (with drip hood) 11" 16.3"NEMA 2 + DID (with drip hood) 11" 16.3"NEMA 3R 14.5" * 14.5" *NEMA 4 / 4X / 12 14.5" * 14.8" **Does not include additional depth needed for hanging brackets / handle.—NEMA 1 and NEMA 2 mounting hole locationsHeight Holes A (in) B (in) C (in)60" 4 5 – 872" 4 5 – 884" 6 5 42 896" 6 5 48 8—NEMA 3R, 4, 4X, 12 mounting hole locations Enclosure exterior size (in) Dimension D (in) Dimension E (in)30 (33.5) W x 60 (61.0) H 65.97 24.4730 (33.5) W x 72 (73.0) H 77.97 24.4730 (33.5) W x 84 (85.0) H 89.97 24.4730 (33.5) W x 96 (97.0) H 101.97 24.4740 (43.5) W x 60 (61.0) H 65.97 34.4740 (43.5) W x 72 (73.0) H 77.97 34.4740 (43.5) W x 84 (85.0) H 89.97 34.4740 (43.5) W x 96 (97.0) H 101.97 34.4745 (48.5) W x 60 (61.0) H 65.97 39.4745 (48.5) W x 72 (73.0) H 77.97 39.4745 (48.5) W x 84 (85.0) H 89.97 39.4745 (48.5) W x 96 (97.0) H 101.97 39.47Note: Values in parentheses are overall enclosure dimensions.BAAC CED
Connections and terminations5—Panelboard connection types This table lists X-space required for interior bus connection types. One X-space for ReliaGear neXT equals 1.385 inches. ReliaGear neXT offers main lug, vertical main breaker and horizontal main breakers. This panelboard also offers feed-through lugs and clean bus, if no feed-through is required. ReliaGear neXT interiors can be reversed in the field for feed direction.Maximum ampacity Box widths Connection to interior X-space250, 400, 600, 800, 1000, 1200 30, 40, 45 Bolted main, single or dual mechanical lug 4 per sideBolted main, single or dual compression lugVertical main breaker padsBolted main with feed-through lug pads 8 per sideClean bus (horizontal main breaker) See circuit breaker X-height table —Main breaker ReliaGear neXT offers vertical and horizontal main connection types. This table list the X-space required and minimum enclosure widths per main breaker type. Vertical main breakers connect to main lug pads, which use 4X of circuit breaker mounting space along the interior bus. Vertical main circuit breakers also require a vertical main mounting kit. See catalog numbering in document 1SQC900001C0201.Maximum ampacity Main breaker type Orientation X-spaceMinimum enclosure width (interior orientation)225 XT4 Horizontal 3 30" (center)600 XT5 Horizontal 4 40" (offset)800 XT6 Horizontal 6 45" (offset)1200 XT7 Horizontal 6 45" (offset)600 XT5 Vertical 4 30" (center)1200 XT7 Vertical 4 30" (center)—Standard main lug terminations (Cu/Al mechanical) Standard mechanical lugs shown. Oversized (500–750 kcmil) mechanical lugs and compression lugs are also available. Please refer to document 1SQC900001C0201 for complete offering.Main amps Lug Wires per lug Qty. of lugs per phase Wire range (AWG/kcmil)250 LGML260* 2 1 #2–600 400 LGML260* 2 1 #2–600 600 LGML260* 2 1 #2–600 800 LGML260* 2 2 #2–600 1000 LGML260* 2 2 #2–600 1200 LGML260* 2 2 #2–600 * A (aluminum) or C (copper) suffix lugs available.Lug catalog number contains 1 lug. Lug quantity to be ordered to be based on number of wires and number of phases in panel. For example, in an 800 A panel, incoming Cu wires are qty. 3, 300 kcmil wires per phase. Customer to order qty. 6 LGML260C. —Standard dual main lug terminations (Cu/Al mechanical) Standard mechanical lugs shown. Oversized (500–750 kcmil) mechanical lugs and compression lugs are also available. Please refer to document 1SQC900001C0201 for complete offering. Main amps Lug Wires per lug Qty. of lugs per phase Wire range (AWG/kcmil)250 LGML260* 2 2 #2–600 400 LGML260* 2 2 #2–600 600 LGML260* 2 2 #2–600 800 LGMD460* 2 4 #2–600 1000 LGMD460* 2 4 #2–600 1200 LGMD460* 2 4 #2–600 * A (aluminum) or C (copper) suffix lugs available.Lug quantity to be ordered to be based on number of wires and number of phases in panel. For example in an 800 A dual main lug panel, incoming Cu wires are qty. 3, 300 kcmil wires per phase. Customer to order qty. 3 LGMD460C. ENCLOSURES AND CONNECTIONS AND TERMINATIONS
B1 copy starts hereB2 copy starts hereB3 copy starts hereConnections and terminations6 RELIAGEAR NEXT—Standard neutral lug terminationsStandard extrusions shown. Additional lugs may be added to these base extrusions when required (ground fault, vertical main, dual main, etc.) Lug amp rating No. of wires Wire size (AWG/kcmil) Recommended tightening torque250/400 2 (main) #2–600 (Cu/Al)3⁄8" Internal hex, 375 lb-in5 #6–250 (Cu) #6–300 (Al)5⁄16 Internal hex, 275 lb-in16 #14–2/0 (Cu) #12–2/0 (Al)7⁄16 Straight slot, 50 lb-in24 #8–#4 (Cu-Al)1⁄4 Straight slot, 45 lb-in#12–#10 (Al) #14–#10 (Cu)1⁄4 Straight slot, 25 lb-in600/800/1200 8 (main) #2–600 (Cu/Al)3⁄8" Internal hex, 375 lb-in10 #6–250 (Cu) #6–300 (Al)5⁄16 Internal hex, 275 lb-in9 #14–2/0 (Cu) #12–2/0 (Al)7⁄16 Straight slot, 50 lb-in10 #8–#4 (Cu-Al)1⁄4 Straight slot, 45 lb-in#12–#10 (Al) #14–#10 (Cu)1⁄4 Straight slot, 25 lb-in—Standard ground lug terminations Grounds available in bonded or isolated, 10 or 47 wire, Al or Cu forms. Wire count No. of wires Wire size (AWG/kcmil)47 2 (main) #2–600 (Cu/Al)16 #14–2/0 (Cu) #12–2/0 (Al)5 #6–250 (Cu) #6–300 (Al)24 #8–#4 (Cu-Al)#12–#10 (Al) #14–#10 (Cu)10 10 6–2/0 AWG —Standard circuit breaker terminations (Cu/Al) Standard terminations shown. ReliaGear neXT plug-in breaker assemblies are preassembled with line-side connector and load-side lugs, and main breakers are suitable for reverse-feed applications. Circuit breaker frame Terminal lugs (Cu-Al)Frame Ampacity Installation Poles Catalog number Cables per lug Range (AWG/kcmil) Cu or AlxT1 125 Horizontal 3 KXT2CUAL2-3PC 1 #10-2/0XT4 25–70 Horizontal 3 KXT4CUAL1-3PC 1 #14-1/0XT4 80-225 Horizontal 3 KXT4CUAL2-3PC 1 #4-300XT4 250 Horizontal 3 K XT4CUAL3-3PC 1 3/0-350XT5 600 Horizontal/vertical 3 KXT5CUAL2X500K-3PC 2 2/0-500XT6 800 Horizontal 3 KXT6CUAL3X400K-3PC 3 2/0-400XT7 1200 Horizontal/vertical 3 KXT7CUAL4X500K-3PC 4 4/0-500XT7 1200 Horizontal/vertical 3 KXT7CUAL3X750KC-3PC 2*/3 500-750FB/TEY 15–20 Horizontal 1, 2 FCAL12/** 1 #14-#10FB/TEY 25–60 Horizontal 1, 2 FCAL13/** 1 #10-#4FB/TEY 70 Horizontal 1, 2 FCAL14/** 1 #1-1/0TEY – Horizontal 1, 2 ** 1 #4-2/0*) Max. two 750 kcmil cables allowed up to 800 A in horizontal installation due to wire-bending space limitation **) TEY lugs are captive, please replace complete breaker
Tmax® XT molded case circuit breakers7CONNECTIONS AND TERMINATIONS, MOLDED CASE CIRCUIT BREAKERS—XT1—XT4—XT5—XT6—XT7—Tmax XT ModelFrame size (amps)No. of polesRated voltage 50–60 Hz AC Interrupt ratings (kA)Dimensions – fixed, 3 poles W x H x D(3) mm (in.)Trip units for power distributionXT1 125 3 480Δ(1)At 240 V AC: N = 50, S = 65, H = 100 At 480 V AC: N = 25, S = 35, H = 65 At 600Y/347 V AC: N = 18, S = 22, H = 2576.2 x 185.16 x 264.67 (3 x 7.29 x 10.42)TMFXT4 250 3 600 At 240 V AC: N = 65, S =100, H = 150, L = 200, V = 200 At 480 V AC: N = 25, S = 35, H(2) = 65, L(2) = 100, V(2) = 100 At 600 V AC: N = 18, S = 22, H(2) = 25, L(2) = 50, V(2) = 65104.9 x 198.12 x 248.67 (4.13 x 7.8 x 9.79)TMF, Ekip DIP, Ekip TouchXT5 400–600 3 600 At 240 V AC: N = 65, S =100, H = 150, L = 200 At 480 V AC: N = 35, S = 50, H(2) = 65, L(2) = 100 At 600 V AC: N = 18, S = 25, H(2) = 35, L(2) = 65139.45 x 206.25 x 387.6 (5.49 x 8.12 x 15.26) TMA, Ekip DIP, Ekip TouchXT6 800 3 600 At 240 V AC: N = 65, S =100, H = 200 At 480 V AC: N = 35, S = 50, H = 65 At 600 V AC: N = 20, S = 25, H =35209.04 x 211.33 x 487.93 (8.23 x 8.32 x 19.21)TMA, Ekip DIPXT7 800–1000–1200 3 600 At 240 V AC: S =65, H = 100, L = 200 At 480 V AC: S = 50, H = 65, L = 100 At 600 V AC: S = 25, H = 50, L = 65210.06 x 276.61 x 487.93 (8.27 x 10.89 x 19.21)Ekip DIP, Ekip Touch(1) Current-limiting circuit breaker in 480 V AC and 600 V AC(2) 600 Y/347 V AC (3) Dimensions include line-side connector and mounting bracket
B1 copy starts hereB2 copy starts hereB3 copy starts here—Record Plus FBPoles 1, 2Amperes 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100Trip unit Fixed thermal-magnetic—Interrupting ratingsAmpere rating Maximum voltage Type PolesUL listed interrupting rating rms symmetrical kA AC voltage240 V 277 V 347 V 480 V 600 V15–100 600Y/347 V AC FBV 1 35 35 22 – –2 65 – – 35 22FBN 1 65 65 25 – –2 150 – – 65 25FBH 1 100 100 35 – –2 200 – – 100 35—TEYPoles 1, 2Amperes 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125Trip unit Fixed thermal-magnetic—Interrupting ratingsAmpere rating Maximum voltage Type PolesUL listed interrupting rating rms symmetrical kA AC voltage120/240 V 480/277 V15–70 (1-pole) 277 V AC (1-pole) TEYD 1–2 65 2515–125 (2-pole) 480Y/277 V AC (2-pole) TEYH 1–2 65 35TEYL 1–2 100 65Record Plus® FB and TEY molded case circuit breakers—1-pole FB—2-pole FB—1-pole TEY—2-pole TEY8 RELIAGEAR NEXT
Wire bending and conduit space9MOLDED CASE CIRCUIT BREAKERS, WIRE BENDING AND CONDUIT SPACE—30" center box—40" offset box—45" offset box—45" center boxXT1XT1XT1XT4FB2PFB1PSTEY2PSTEY1PXT1XT1XT1XT4FB2PFB1PSTEY2PSTEY1P5.2"5.2"4.9"4.5"4.3"4.5"4.3"4.9"5.2"5.2"XT1XT1XT1XT4FB2PFB1PSTEY2PSTEY1PXT5XT5XT4FB2PFB1PSTEY2PSTEY1P10.9"4.5"4.3"4.9"5.2"5.2"15.2"14.9"14.5"14.3"XT1XT1XT1XT4FB2PFB1PSTEY2PSTEY1PXT7XT6XT5XT4FB2PFB1PSTEY2PSTEY1P4.5"4.3"4.9"5.2"5.2"12.2"15.9"20.2"19.9"10.94"19.5"19.3"XT5XT4XT4FB2PFB1PSTEY2PSTEY1PXT5XT5XT4FB2PFB1PSTEY2PSTEY1P8.4"8.4"12.7"12.4"12"11.8"12.7"12.4"12"11.8"Typical available conduit spaceConduit hubs should comply with the requirements in the Standard for Conduit, Tubing, and Cable Fittings, UL 514B. Conduit hubs should comply with the requirements of the UL 50E NEMA rating of the ReliaGear neXT enclosure on which they are installed to maintain the enclosure’s rating. Consider your specific neutral and ground configuration when planning conduit space. For additional dimensional detail, reference document 1SQC900008M0201. —Top and bottom NEMA 1—Top and bottom NEMA 2—Top and bottom NEMA 3R—Top and bottom NEMA 4/4X/12Conduit space (top and bottom) Enclosure typeDimensionEnclosure width NEMA 1NEMA 2*NEMA 3RNEMA 4/4X/12A (in.) 45 44 4640 39 4130 29 31B (in.) 30/40/45 40C (in.) 30/4 0/45 2 2.9 3.3D (in.) 30/4 0/45 2.2E (in.) 30/40/45 6.7Y (in.) (distance off backwall) 30/4 0/45 0.35 0.45 0.45 0.38X (in.) (distance off right sidewall) 30/4 0/45 0.25 0.4 0.5 0.1*NEMA 2 has double top wall due to drip hood. All other enclosure conduit space is a single thickness of sheet metal.Circuit breaker wire bending space
General • Panelboards are listed and labeled by Underwriters Laboratories, Inc. in accordance with UL Standards 50 and 67, and shall conform to the latest requirements of the National Electrical Code (NEC) and NEMA Standard PB.1. • The panelboard will meet service entrance requirements when specified.• Boxes are furnished without knockouts. Panel boxes and fronts are cold-rolled steel and furnished with ANS1 light gray polyester textured powder coat. • A four-piece front and hinged gutter covers are provided by default to provide ease of wiring access. All screw fasteners are 1⁄4–20 thread and zinc coated to retard corrosion. • Main and branch circuit breakers shall be quick-make, quick-break and trip-indicating. Interrupting rating of the circuit breaker shall not be less than the maximum short-circuit currents available at the incoming line terminals as shown on the plans. • ReliaGear neXT circuit breakers are compatible with ReliaGear SB switchboards. ReliaGear nexT components are not compatible with any other panelboard type. —Publications Title Document NumberGuideform specification 1SQC900001D0201Assembly Instructions — Factory assembled 1SQC900004M0201Assembly Instructions — Bulk pack 1SQC900003M0201Door-in-door instructions 1SQC900002M0201Dual main lugs 1SQC900009M0201Grounds and neutrals 1SQC900007M0201NEMA 3R, 4, 4X and 12 enclosures 1SQC900008M0201RELT unit 1SQC900005M0201SPD unit 1SQC900006M0201AMP1 main circuit breaker meter 1SQC900001M0201Service entrance barrier 1SQC900010M0201General information1SXU900300G0201, 6.2021—We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB Inc. does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB Inc. © 2021 ABB All rights reserved—ABB Inc. Electrification business 305 Gregson Dr.Cary, NC 27511 United Statessolutions.abb/reliagearnext