ABB Quick Selector Guide for Small Projects

Page 1

Contact your Viking Electric sales representative for more information or assistance.—Small ProjectsQuick Selector Guide

Page 2

—Table of contentContactsPro-stock unassembled panelboards R-Series panelboardsReliaGear neXT power panelboardsRetrofit kits for Spectra panelboardsMolded case circuit breakersCircuit breaker enclosures Disconnect and safety switchesDry type transformersLighting contactorsSPDs/TVSSLoad centers and circuit breakers

Page 3

ABB Distributor customer service Stock, price and availability Order status Expedite requests Order changes Order cancellationE-mail: us-el.distributorsales@abb.comPhone: 1-800-431-7867, prompt 1ABB new order entryUse empower or E-mail us-elgmusorders@abb.comABB component supportTechnical support product/application inquiriesE-mail: epis.component.support@abb.comPhone: 1-800-431-7867, prompt 4ABB post sales and warrantyDefective product warranty issues and inquiriesUse empower or phone 1-800-431-7867, prompt 5ABB empower help deskempower technical issuesE-mail: empoweru@abb.comABB trainingempower training: https://empoweru.lessonly.com/signinProduct training: https://mylearning.abb.comBuylog and Control CatalogPlease refer to the Buylog and/or Control Catalog for further product informationand details. Reach out to your local ABB account manager with any questionsBuylog: https://electrification.us.abb.com/buylogControl Catalog: https://electrification.us.abb.com/control-catalogElectrical distribution contacts

Page 4

—Breaker quoting guideAdding breaker to circuit breaker enclosure1. Select CB enclosure from CB enclosure tab2. Select breaker from CCB tab3. Select lugs from MCCB tabAdding breaker to Spectra bolt-on panel1. Select mounting hardware from Retrofit kit for Spectra panelboards tab2. Select breaker from MCCB tab3. Select lugs from MCCB tabAdding main breaker or subfeed breaker to a ReliaGear pro-stock panel. Select breaker from Pro-stock tabAdding breaker to ReliaGear neXT panelboard or ReliaGear switchboard group mounted section. Select breaker from ReliaGear neXT tab

Page 5

—Pro-Stock Panelboards

Page 6

—ReliaGear lighting panelboardsPro-Stock, unassembled lighting panelsCopper busVoltageRating(Amps)No. ofcircuitsFeed-thru Non feed-thruProduct NumberBox/FrontHeightProduct NumberBox/FrontHeightTGL2 GroundBars1,2                  – –         – –      Vac,                   – –         – –      Vac,                   – –         – –      Note: Main bus rated 250A main breaker and 225A main lugAluminum busVoltageRating(Amps)No. ofcircuitsFeed-thru Product NumberBox/FrontHeightTGL2 GroundBars1,2                           Note: Main bus rated 250A main breaker and 225A main lugTGL20 ground lug quantitiesInterior TypeNo. of TGL20s Requiredby Panel Rating100-250A 400A 600AMain Lug Only   Main Lug and Feed-thru   Main Circuit breaker Only   Main Circuit breaker and Sub-feed   Main Circuit breaker and Feed-thru   1 For TGL20 ground lug quantities, see TGL20 Ground Lug Quantities table above.2 For isolated ground, use EGS12. When using the EGS12, 3, 5 and 7 ground lugs (TGL20s) are required for 18, 30 and 42 circuits respectively.100-600A (600A main circuit breaker not available)240 Vac 1 or 3 phase or 480y/277 vac 3 phaseOrder by product number from the customer service center1. Select interiorSelect the interior by bus type, panel rating and number of circuits. Identify the box/front height for use in Steps 2 and 3.

Page 7

—ReliaGear lighting panelboardsPro-Stock, unassembled lighting panels2. Select boxSelect a box of the correct height (see Step 1). Boxes come with blank endwalls. If endwalls with knockouts are required, also order knockout endwall kit AKEW2. BoxHeightNEMA 1 NEMA 3RNEMA 4, 4X & 12 Painted GalvanealNEMA 4, 4X & 12 Stainless Steel20" 20" 20" 20" – – –                         3. Select frontSelect a front of the correct height (see Step 1).Front HeightStandard (20") Door Within Door (20") Front Hinged To Box (20")Flush Surface Flush Surface Flush Surface                                    (T) Fronts with quarter turn lock for applications with XT5 circuit breakers. Applicable for NEMA 1 enclosures only.NEMA 1 Front options sold separatelyNEMA 3RNEMA 4/4X/12 painted galvanealNEMA 4/4X/12 stainless steelStandard Door within door Front hinged to BoxStandard with quarter turn lock

Page 8

—ReliaGear lighting panelboardsPro-Stock, unassembled lighting panels4. Select main and/or sub-feed circuit breaker kitSelect main circuit breaker kit appropriate for your interior type (see Step 1), amp rating and kAIC rating. If a sub-feed circuit breaker is required, repeat the selection process.Note: 400A circuit breaker kits cannot be used for sub-feed applications in Pro-Stock panelboards.For additional details, see Section 6 of the BuyLog.Interior Type Cat. No.¹Rating (Amps)No. of PolesCircuit breaker Short Circuit Rating (kAIC)10 14 22 25 35 50 65 100 150 200     THQB – THHQB – – – – – – –    –  – – – – – – –    –  – – – – – – –   – – – – – –       – – – – – –  – – –    THQB – THHQB – – – – – – –    –  – – – – – – –    –  – – – – – – –    –  – – – – – – –   – – – – – –         – – – – – –        – – – – – –  – – –   – – – – – –       – – – – – –  – – –   – – – – – –       – – – – – –  – – –   – – – – – –  – – –     – TEY – – – – – – – –   –  – – – – – – – –   – – –   –  – – –   – – – – – –  – – –   – – –   –       – – –   –          – – – – – –  – – –   – – –   –  – – –   – – – – – –  – – –   – – – –    – – –   – – – – – –  – – –,   – – – – – –  – – –¹ Circuit breaker not included except for “WB” kits (where product number ends in “WB”). “WB” kits include a circuit breaker, mounting kit and load-side lugs.² Actual Circuit breaker Short Circuit Rating is 25kAIC         

Page 9

—ReliaGear lighting panelboardsPro-Stock, unassembled lighting panels5. Typical main circuit breakers - Skip Step 5 if you selected a main circuit breaker kit ending in “WB” —no circuit breaker is required. - To correlate circuit breaker types with the kAIC rating in specific panelboards, see the table for Step 4. For more rating details, see ReliaGear Lighting Panels Rating Series Labels (1TQC173100E0001). - Use 2 outer poles for 3 pole applications - For TEY and THQB main circuit breakers, see branch circuit breakers tables in Step 7.Tmax XT Circuit breakers (3-pole) For use with appropriate main circuit breaker kit (see Step 4).240V KAIC 480V KAIC Breaker Description Product Number Wire Range (Cu/Al) Cables per Lug                                                                                                    Main or subfeed circuit breakers for use with RQ panels (208/120 Vac 3-phase or 240 Vac single phase). See Step 4.AmpRating2-pole 3-pole10kAIC 22kAIC 10kAIC 22kAICProduct3 Number Product Number Product Number Product Number                    

Page 10

—ReliaGear lighting panelboardsPro-Stock, unassembled lighting panels6. Select main lug kit and accessoriesSelect lug kit(s) for main lug and/or feed-thru applications, if required. (All lugs are suitable for interiors with either copper or aluminum bus.) Also select any accessories required.Main lug kitsLug TypeAmpRatingStandard Oversized 200% NeutralProductNumberWire RangeProductNumberWire RangeProductNumberPressure     NKA          –Copper     NKR        – – –Compression     NKT      Dual    – – –Main    – – –¹ 500 MCM Cu, 750 MCM Al.² For 200% neutral feed-thru, order NKA4FT, (GO-101P). Wire range (2) 2/0 – 600 MCM or (4) 4-250 MCM.AccessoriesService Entrance³Amp Rating Product Number BNDKT   entrance label.ProCare Kit⁷Description Product NumberProCare Kit for Pro-Stockpanelboard installationand maintenancePROCAREplates, (2) 225A phase barriers, (2) feed-thru barriers, (1) 400/600A phase barrier, (50) directory cards/rating books, (50) circuit number strips (1-48), (50) circuit number strips (43-84), (5) standard locks and keys, (50) deadfront screws, (10) RQ/RE front hardware kits, (10) AD front hardware kits, (50) service disconnect labels, (50) main labels.Main breaker service entrance lug cover kitBreaker Type Poles Product Number          Spare lugsFrame PolesProduct NumberWire-Cu-Al (Unless otherwise specified)Per LugRange                          

Page 11

—ReliaGear lighting panelboardsPro-Stock, unassembled lighting panels7. Typical bolt-on branch circuit breakersThese tables show typical branch circuit breakers, but do not include all branch circuit breakers that can be used with Pro-Stock panelboards.Branch circuit circuit breakers for use with RQ panels (208/120 Vac 3-phase or 240 Vac single phase)AmpRating10kAIC 22kAIC1-pole 2-pole 3-pole 1-pole 2-pole 3-poleProduct Number Product Number Product Number Product Number Product Number Product Number                                                             –   –   –   –   –   –  Branch circuit circuit breakers for use with RE panels (480/277 Vac 3-phase)AmpRating14kAIC1-pole 2-pole 3-poleProduct Number Product Number Product Number                              

Page 12

—ReliaGear lighting panelboardsPro-Stock, unassembled lighting panelsPro-Stock interiors product number structure218 RCXAX B4T11AEUInterior Type AQU = 240 Vac AEU = 480Y/277 VacBus B4 = Copper Blank = AluminumT1 Feed-thru Blank Non Feed-thru* (requires copper bus [B4]) * For retrofit applicationsPhase 1 = 1-Phase 3 = 3-PhaseNo. of Circuits 18 = 18 Circuits 30 = 30 Circuits 42 = 42 CircuitsMax. Amp Rating 2 = 225A 4 = 400A 6 = 600A

Page 13

—ReliaGear lighting panelboardsProduct optionsEquipment grounds—factory supplied with panelboardDescription Product NumberField installed kitspositionspositionsbranch positionsbranch positionsMain lug for above terminal kits Optional equipment groundsDescription Product NumberAluminum Extruded Bonded AEBGCopper Extruded Bonded AEBGCAluminum Extruded Isolated AEIGCopper Extruded Isolated AEIGCCopper Isolated/Bonded ASPGIBCCircuit breaker mounting¹ hardware kitsDescription Product Number  ¹ Use to mount circuit breaker in existing space.² Includes screws, washers and ReliaGear panelboard connectors.THQB/THHQB/THQL/THHQL/TEY filler platesProduct NumberTED4/SE/FB filler platesProduct NumberEnclosure optionsBox extensions—For additional end gutter space or conduitskirt applications–see page 11-21.AEBGAEBGCAEIGAEIGCASPGIBC

Page 14

Corbin LockHandle locking THL103T-Handle Quarter Turn KitFixed padlock in the open position – PLL—ReliaGear lighting panelboardsAccessoriesField installed kits/replacement partsOrder by product number from factoryEndwall kitsProduct Number Description Qty. Blank  Knockout Panelboard locksDescription Product NumberT-Handle Quarter Turn Kit¹ ASPQTRTFlush Quarter Turn Kit¹ ASPQTRKReplacement Lock with Std. Key Additional Keys for Above Lock Yale Lock Kit Corbin Lock Kit  ¹ The quarter turn kits are only compatible with factory-built quarter turn fronts. They cannot be used to convert other locks (standard, Corbin, etc.) to quarter turn. Keys are interchangeable with standard, Corbin, etc.Replacement Lock with ABB75 Key – Red Replacement Lock with Standard Key – BlackPadlock in the open position – PLCLocking devicesFrame Style Description Product NumberPadlocking Device (single padlock)QTHQB, THHQB, THQL, THHQLE TEY Formula  Formula  Tmax XT  KXTBPLLOPCL Tmax XT  KXTCPLLOPCL Tmax XT  Tmax XT  Handle Locking (nonpadlocking)QTHQB, THHQB, THL, THHQLE TEY Q/EFiller plate for Q and TEY breakersSafety catch for trough coversACHKGasketing Kit AGSK

Page 15

—ReliaGear lighting panelboardsAccessoriesField installed kits/replacement partsOrder by product number from factoryPermanent circuit number kitsProduct NumberDescriptionRQ, RL, RE AD      Panelboards partsDescription Product NumberDirectory Card     Metal Directory Card Holder Directory Card Holder Delta Hi-leg Conversion Kit, to Add B-Phase Plug on RL PanelsAPHBLBolt on RE/RQ Panels APHBQ NEMATRX Service Entrance Kit ASPSERENT RQ/RL/RE Rail Bracket ASPAQLEBKTFront Flush Adjust Kit RE Front Mounting Kit RQ/RL Front Mounting Kit AD Front Mounting Kit Front Hinge to Box Mounting Kit Front Extension Mounting Kit Can of Touch-up Paint ² Included in factory assembled panels—AD panels with Spectra branch circuit breakers.Box extensionsBolts to ReliaGear box with or without box endwall in place.Extensions can be combined to obtain lengths greater than 18 and 24 inches.Box Extensions Covers Only 10 covers per kit.Description Product Number      Box Widthand DepthBox MountingBox ExtensionLength (Inches)Box ExtensionProduct NumberFlush   Surface          Flush  Surface  Flush  Surface  

Page 16

—R-Series Panelboards

Page 17

—ReliaGear lighting panelboardsTypesType RLService information:1P, 3W-120/240 Vac3P, 3W-240 Vac3P, 4W-240/120 Vac, 208/120 VacFully rated: 65kAIC at 240VSeries rated: 200kAIC at 240VMain circuit breakers:100A-THQB, THHQB, TEY125A-XT1225A-A2250A-XT4400A-XT5600A-XT5800A-XT6¹Main lug:125-800ABranch circuit breakers (plug-in):Amperage-15-100APoles-1, 2, 3Types-THQL, THHQL, TXQLSubfeeds: Amperage-15-600APoles-2, 3Types- A2, XT1, XT4, XT5EnclosuresLength-25.5, 31.5, 37.5, 43.5, 49.5, 55.5, 64.5, 76.5, 82.5, 88.5Width-20”Depth-5.81”Type RQService information:1P, 3W-120/240 Vac3P, 3W-240 Vac3P, 4W-240/120 Vac, 208/120 VacFully rated: 65kAIC at 240VSeries rated: 200kAIC at 240VMain circuit breakers:100A-THQB, THHQB, TEY125A-XT1225A-A2250A-XT4400A-XT5600A-XT5800A-XT6¹Main lug:125-800ABranch circuit breakers (bolt-on):Amperage-15-100APoles-1, 2, 3Types-THQB, THHQB, TXQBSubfeeds: Amperage-15-600APoles-2, 3Types- A2, XT1, XT4, XT5EnclosuresLength-25.5, 31.5, 37.5, 43.5, 49.5, 55.5, 64.5, 76.5, 82.5, 88.5Width-20” Depth-5.81”Type RLType RQ

Page 18

—ReliaGear lighting panelboardsTypesType REService information:1P, 3W-120/240 Vac, 125/250 Vdc3P, 3W-240 Vac3P, 4W-480/277 Vac, 208/120 Vac, 240/120 VacFully rated: 18kAIC at 480Y/277V, 65kAIC at 240VSeries rated: Reference panel configuration in empower or DET-008Main circuit breakers:100A-TEY, TEYF125A-XT1250A-XT4400A-XT5600A-XT5800A-XT6¹Main lug:125-800ABranch circuit breakers (bolt-on):Amperage-15-100APoles-1, 2, 3Types-TEY, TEYFSubfeeds:Amperage-15-600APoles: 3*Types: XT1, XT4, XT5*3 poles can be used as 2 polesEnclosuresLength-25.5, 31.5, 37.5, 43.5, 49.5, 55.5, 64.5, 76.5, 82.5, 88.5Width-20”Depth-5.81”Type RSService information:1P, 3W-120/240 Vac, 125/250 Vdc3P, 3W-240 Vac3P, 4W-480/277 Vac, 208/120 Vac, 240/120 VacFully rated: 65kAIC at 480Y/277V, 100kAIC at 240VSeries rated: Reference panel configuration in empower or DET-008Main circuit breakers:100A-TEYD, TEYH, TEYL125A-XT1250A-XT4400A-XT5600A-XT5800A-XT6¹Main lug:125-800ABranch circuit breakers (bolt-on):Amperage-15-125APoles- 1, 2, 3Types- TEYD, TEYH, TEYLSubfeeds:Amperage-15-600APoles: 3*Types: XT1, XT4, XT5*3 poles can be used as 2 polesEnclosuresLength-25.5, 31.5, 37.5, 43.5, 49.5, 55.5, 64.5, 76.5, 82.5, 88.5Width-20”Depth-5.81”Type RDService information:3P, 3W-480 Vac, 600 Vac3P, 4W-208/120 Vac, 480/277 Vac, 600/347 VacFully rated: 42kAIC at 240V, 42 kAIC at 600Y/347V, 42kAIC at 480VSeries rated: Reference panel configuration in empower or DET-008Main circuit breakers:150A-XT4225A-XT4400A-XT5600A-XT5Main lug:150-800ABranch circuit breakers (bolt-on):Amperage- 5-100A (FB 1P, 2P) 15-125A (XT2 eKIP DIP Hi-Touch 3P)220A Max. double branchTypes: FB, XT2 eKIP DIP Hi-TouchEnclosuresLength-31.5, 37.5, 43.5, 49.5, 55.5, 64.5, 76.5, 82.5, 88.5Width-20”Depth-5.81”Type RE Type RS Type RD

Page 19

—ReliGear neXT Power Panelboards

Page 20

B1 copy starts hereB2 copy starts hereB3 copy starts hereInteriorsReliaGear neXT panelboard interiors feature plug-in and bolt-on (when vertical main circuit breakers are selected) technology, IP 20 “finger-safe” features (on clean bus only) and center or offset mounting positions within the enclosure. Main lug, feed-through lug and clean bus options exist. X-height or X-space refers to the space occupied by individual (plug-in) components on the interior bus. One X-space for ReliaGear neXT equals 1.385 inches.30" wide circuit breaker panelCenter-mounted interior40" wide circuit breaker panelOffset-mounted interior45" wide circuit breaker panelOffset-mounted interior45" wide circuit breaker panelCenter-mounted interior—01 Typical standard, hinged gutter covers—02 Typical sheet metal fillers cover the space between gutter covers and circuit breakers/blanks—03 Typical sheet metal blanks cover the future space for adding circuit breakers to the interior Standard interior heights• 16X05• 24X05• 32X05• 40X05Interior materials• Tin- and silver-plated aluminum (heat rated)• Tin- and silver-plated copper (heat rated or 1000 A per sq. in. density rated)XT4XT4XT4 XT4XT4XT4XT1XT1XT1XT1XT1XT1FB/TEY FB/TEY225 A04225 A045.5" 5.5"30"XT4XT4XT4XT4XT4XT4XT5XT5XT1XT1XT1FB/TEY FB/TEY8" 5.5"40"600 A04225 A04XT4XT4XT4XT4XT4XT5XT6/XT7XT1XT1XT1FBFB/TEY13" 5.5"45"0302011200 A04225 A04XT4XT4XT4XT4FB/TEY600 A04XT5600 A04XT5XT5 XT1XT4XT4FB/TEY5.5" 5.5"45"Clean bus Main lug Feed-through lug—04Maximum ampacity circuit breaker allowed per this side of interior—05Interiors are double sided; double standard interior heights for available mounting space (Ex. 16X bus has 32X max. of circuit breaker mounting space)

Page 21

X-space requirements for plug-in devices—X-space requirements for plug-in devices See table below for the X-space requirements of plug-in components. Frame Max. ampacity (A) Poles X-spaceSingle XT1 125 3 3Two XT1 125 3 5Five XT1 125 3 11XT4 250 3 3XT5 600 3 4XT6 800 3 6XT7 1200 3 6FB/TEY 100/70 1 1FB/TEY 100/125 2 2SPD – – 10RELT – – 3AMP1 main meter – – 4 3 X-spaces5 X-spaces11 X-spaces—Single XT1—Two XT1 = 16% space saving—Five XT1 = 26% space saving—XT1 circuit breaker assemblies — panelboard densitiy and mounting hardwareThe small footprint of XT1 allows this panel to offer multiple options to improve circuit breaker density. As you configure and order ReliaGear neXT panelboards, you'll notice that XT1 are grouped in quantities of one, two or five. As part of this feature, unique mounting brackets are required when adding XT1 breaker assemblies to existing installations. See below for X-space and mounting brackets required. Frame X-space % X-space savings (compared to single XT1 kits) Mounting hardwareSingle XT1 3 – SR1XBFTwo XT1 5 16% SR2XBFFive XT1 11 26% SR5XBFXT1 group mounting brackets are included in panelboard orders from the factory, but are sold separately when adding an XT1 to an existing installation.

Page 22

—Stocked Breakers Select horizontal main and feeder circuit breakers (80% rated only)US PN Global ABB PN Frame Br Cap @480V X Space Poles Amps Trip Unit PhaseXT1HU3015AYD000XXX (1)1SDX051540R1 (1)XT1 H (65kA) 3 3 15 TMF --XT1HU3020AYD000XXX (1)1SDX051541R1 (1)XT1 H (65kA) 3 3 20 TMF --XT1HU3030AYD000XXX (1)1SDX051543R1 (1)XT1 H (65kA) 3 3 30 TMF --XT1HU3040AYD000XXX (1)1SDX051545R1 (1)XT1 H (65kA) 3 3 40 TMF --XT1HU3050AYD000XXX (1)1SDX051547R1 (1)XT1 H (65kA) 3 3 50 TMF --XT1HU3060AYD000XXX (1)1SDX051548R1 (1)XT1 H (65kA) 3 3 60 TMF --XT1HU3070AYD000XXX (1)1SDX051549R1 (1)XT1 H (65kA) 3 3 70 TMF --XT1HU3100AYD000XXX (1)1SDX051552R1 (1)XT1 H (65kA) 3 3 100 TMF --XT1HU3125AYD000XXX (1)1SDX051554R1 (1)XT1 H (65kA) 3 3 125 TMF --XT4HU3060EYG000XXX 1SDX051596R1 XT4 H (65kA) 3 3 60 Ekip LS/I --XT4HU3100EYJ000XXX 1SDX051607R1 XT4 H (65kA) 3 3 100 Ekip LS/I --XT4HU3150EYJ000XXX 1SDX051617R1 X T4 H (65kA) 3 3 150 Ekip LS/I --XT4HU3225EYJ000XXX 1SDX051627R1 XT4 H (65kA) 3 3 225 Ekip LS/I --XT4HU3250EYL000XXX 1SDX051633R1 XT4 H (65kA) 3 3 250 Ekip LS/I --XT5HU330ABYN000XXX 1SDX052064R1 XT5 H (65kA) 4 3 300 TMA --XT5HU340ABYN000XXX 1SDX052069R1 XT5 H (65kA) 4 3 400 TMA --XT5HU350BBYN000XXX 1SDX052074R1 XT5 H (65kA) 4 3 500 TMA --XT5HU360BBYN000XXX 1SDX052075R1 XT5 H (65kA) 4 3 600 TMAXT7HU380CFYW000XXX 1SDX052323R1 XT7 H (65kA) 6 3 800 Ekip Dip LSI --XT7HU310DFYW000XXX 1SDX052353R1 XT7 H (65kA) 6 3 1000 Ekip Dip LSI --XT7HU312EFYW000XXX 1SDX052383R1 XT7 H (65kA) 6 3 1200 Ekip Dip LSI --NEFBN16TE020R2A 1SQA001023R0001 FB 1p N (65kA) 1 1 20 TMF ANEFBN16TE030R2A 1SQA001035R0001 FB 1p N (65kA) 1 1 30 TMF ANEFBN16TE020R2B 1SQA001098R0001 FB 1p N (65kA) 1 1 20 TMF BNEFBN16TE030R2B 1SQA001104R0001 FB 1p N (65kA) 1 1 30 TMF BNEFBN16TE020R2C 1SQA001137R0001 FB 1p N (65kA) 1 1 20 TMF CNEFBN16TE030R2C 1SQA001143R0001 FB 1p N (65kA) 1 1 30 TMF CNEFBN26TE020R2AB 1SQA001026R0001 FB 2p N (65kA) 2 2 20 TMF ABNEFBN26TE030R2AB 1SQA001038R0001 FB 2p N (65kA) 2 2 30 TMF ABNEFBN26TE040R2AB 1SQA001050R0001 FB 2p N (65kA) 2 2 40 TMF ABNEFBN26TE050R2AB 1SQA001062R0001 FB 2p N (65kA) 2 2 50 TMF ABNEFBN26TE060R2AB 1SQA001068R0001 FB 2p N (65kA) 2 2 60 TMF ABNEFBN26TE100R2AB 1SQA001092R0001 FB 2p N (65kA) 2 2 100 TMF ABNEFBN26TE020R2BC 1SQA001176R0001 FB 2p N (65kA) 2 2 20 TMF BCNEFBN26TE030R2BC 1SQA001182R0001 FB 2p N (65kA) 2 2 30 TMF BCNEFBN26TE040R2BC 1SQA001188R0001 FB 2p N (65kA) 2 2 40 TMF BCNEFBN26TE050R2BC 1SQA001194R0001 FB 2p N (65kA) 2 2 50 TMF BCNEFBN26TE060R2BC 1SQA001197R0001 FB 2p N (65kA) 2 2 60 TMF BCNEFBN26TE100R2BC 1SQA001209R0001 FB 2p N (65kA) 2 2 100 TMF BCNEFBN26TE020R2AC 1SQA001215R0001 FB 2p N (65kA) 2 2 20 TMF ACNEFBN26TE030R2AC 1SQA001221R0001 FB 2p N (65kA) 2 2 30 TMF ACNEFBN26TE040R2AC 1SQA001227R0001 FB 2p N (65kA) 22 40 TMF ACNEFBN26TE050R2AC 1SQA001233R0001 FB 2p N (65kA) 2 2 50 TMF ACNEFBN26TE060R2AC 1SQA001236R0001 FB 2p N (65kA) 2 2 60 TMF ACNEFBN26TE100R2AC 1SQA001248R0001 FB 2p N (65kA) 2 2 100 TMF AC(1) SR1XBF mounting bracket required for each XT1 ordered

Page 23

—ReliaGear neXT renewal parts catalog numbersXT circuit breakersPart identifierXT = Circuit breaker familyFrame1 = XT14 = XT45 = XT56 = XT67 = XT7Frame amps015 = 15 A 080 = 80 A 25A = 250A (XT5)020 = 20 A 090 = 90 A 30A = 300 A025 = 25 A 100 = 100 A 40A = 400 A030 = 30 A 110 = 110 A 50B = 500 A035 = 35 A 125 = 125 A 60B = 600 A (XT5)040 = 40 A 150 = 150 A 600 = 600 A (XT6)045 = 45 A 175 = 175 A 80C = 800 A (XT7)050 = 50 A 200 = 200 A 800 = 800 A (XT6)060 = 60 A 225 = 225 A 10E = 1000 A070 = 70 A 250 = 250A (XT4) 12E = 1200 ATrip unitA = TMFB = TMAD = Molded Case SwitchE = Ekip DIP LS/IF = Ekip DIP LSIG = Ekip DIP LSIGP = Ekip Touch LSIQ = Ekip Touch LSIGR = Ekip Touch Measuring LSIS = Ekip Touch Measuring LSIGT = Ekip Hi-Touch LSIU = Ekip Hi-Touch LSIGInterrupting ratingN = NS = SH = HL = LV = VkAIC rating depending on voltage level; refer to performance table.StandardU = UL 80% ratedQ = UL 100% ratedPoles3 = 3 polesXT Y1DN 00UX3X015 XA X

Page 24

—ReliaGear neXT renewal parts catalog numbersXT circuit breakers (continued)Additional certificationsX = NoneLine-side terminals (top)Y = Line-side connectorsAdvanced functionalitiesX = NoneLoad-side terminal (bottom)D = XT1 10–2/0 AWG N = XT5 2x2/0 AWG-500kcmilG = XT4 14–1/0 AWG, 100 A U = XT6 3x2/0 AWG-400kcmilJ = XT4 4 AWG– 300 kcmil, 225 A W = XT7 4x4/0 AWG-500kcmilL = XT4 3/0 AWG–350 kcmil, 250 A X = XT7 3x500-750kcmilKey locksX = NoneA = Ronis key lock – A type keyE = Ronis key lock – Different keysG = Kirk key lock XT5-XT7K = Castell key lock XT5-XT7Accessories combination00 = NoneAux.Bell alarmShunt opening releaseUndervoltage releaseCommunication modulesFront accessories0 = NoneG = PadlockPlease refer to Tmax XT technical catalog for more information.XTY1DN00U03X015 XA X

Page 25

—ReliaGear neXT renewal parts catalog numbersFB circuit breakersTEY circuit breakersPart identifierNEFB = neXT FB circuit breakersPart identifierTEYA = neXT TEY circuit breakersInterrupting ratingV = VN = NH = HkAIC rating depending on voltage level; refer to performance table.Interrupting ratingD = DH = HL = LkAIC rating depending on voltage level; refer to performance table.Rated current015 = 15 A 050 = 50 A020 = 20 A 060 = 60 A025 = 25 A 070 = 70 A030 = 30 A 080 = 80 A035 = 35 A 090 = 90 A040 = 40 A 100 = 100 A045 = 45 APhaseR2A = A phase (1p)R2B = B phase (1p)R2C = C phase (1p)2AB = AB phases (2p)2AC = AC phases (2p)2BC = BC phases (2p)Phase0A = A phase (1p) AB = AB phases (2p)0B = B phase (1p) AC = AC phases (2p)0C = C phase (1p) BC = BC phases (2p)Load lugA = (1) #14-10. 15-20AB = (1) #10-4. 25-60AC = #4-2/0. 70-125AShunt tripX = None M = 120VK = 24V N = 240VAuxX = None D = 277VBell alarmX = None A = Bell alarmOtherX = NoneOtherX = NonePDLX = None C = PadlockPoles1 = 1 pole2 = 2 polesPolesE = 1 poleF = 2 polesVoltage rating6 = 600/347 VRated CurrentC = 015 L = 060D = 020 M = 070E = 025 N = 080F = 030 P = 090G = 035 Q = 100H = 040 R = 110J = 045 S = 125K = 050Trip unitTE = Fixed thermal magneticNEFBV16TE015 R2ATEYADE C A X XX X X X0AKey locksX = NoneA = Ronis key lock – A type keyE = Ronis key lock – Different keysG = Kirk key lock XT5-XT7K = Castell key lock XT5-XT7

Page 26

—ReliaGear neXT renewal parts catalog numbersSpacersPart identifierSR = SpacerX height01 = 1" 10 = 10"02 = 2" 1X = Single XT1 spacer03 = 3" 2X = Double XT1 spacer04 = 4" T1 = XT106 = 6"FillerBF = Blank and fillerBB = Blank onlyEF = Filler onlyRF = RELT fillerSF = SPD fillerSR01BF

Page 27

—POWER PANELBOARDS AND SWITCHBOARDSTmax® XT Retrofit Kits for Spectra™ PanelboardsExtending the life of your installation

Page 28

—Choosing the right retrofit has never been so easyYou consider what you need. We will show you what's possibleStep 1. Select breaker and trip unitStep 2. Select retrofit kitStep 3. Enter separate breaker and retrofit kit orders through empower.abb.com using desktop, laptop or mobile devices. ABB empowerStep 4. Receive breaker and retrofit kit shipments— 01 Maximum of two Tmax® XT4, XT5 or XT7 retrofit kits can be installed, side by side, in an existing Spectra™ panelboard installation— 02 For instantaneous selectivity, see DET-760. For series ratings, see DET-008.— 02 XT7 breaker handle extension included in this kit— 01 Maximum of two Tmax® XT4, XT5 or XT7 retrofit kits can be installed, side by side, in an existing Spectra™ panelboard installation Possible combinations within the rangeLegacy Spectra™ breakerSpectra™ E Frame Spectra™ F Frame Spectra™ G Frame Spectra™ K FrameTmax® XT BreakerTmax® XT1 Tmax® XT4 Tmax® XT5 Tmax® XT7Industrial applicationsCommercial and industrial applicationsThermal-magnetic trip unitsElectronic trip units125 A 250 A 250 A 600 A 600 A 1200 ALegacy Spectra™based Kit AMCB6EBFP AMCB6FJFP AMCB3FJFP AMCB6GBFP AMCB3GMFP AMCB3KMFPTmax® XT Kit01SRFB6XT1FPX SRFB6XT4FPX SRFB3XT4FPX SRFB6XT5BFPX SRFB3XT5MFPX SRFB3XT7MFPX02Tmax® XT Kit with Kirk lock provisions01SRFB6XT1FPK SRFB6XT4FPK SRFB3XT4FPK SRFB6XT5BFPK SRFB3XT5MFPK SRFB3XT7MFPK02SRFN400GF XT5 UL 400 A Neutral current transformer kitSRFN600GF XT5 UL 600 A Neutral current transformer kitSRFN800GF XT7 UL 800 A Neutral current transformer kitSRFN100GF XT7 UL 1000 A Neutral current transformer kitSRFN120GF XT7 UL 1200 A Neutral current transformer kitThe world of electrical distribution is a complex one, yet choosing the right device for your individual needs has never been simpler thanks to this Tmax® XT retrofit01 offering for Spectra™ Panelboards and Switchboards. Maybe you are looking for a basic protection device for a standard distribution system. Or perhaps you need something more complex, such as a locking mechanisms or devices that integrate protection, automation, measuring and communication into a cloud-based supervision system. Follow the flowchart when placing an order. All mount-ing kits, filler plates and hardware required are included under a single part number. Circuit breakers are ordered separately.02Bolt-on Strap Kits - Type SRFBNeutral CT Kits - Type SRFNExample: Example: SRFBSRFN6400PolesAmpere Rating3 XT1 = Tmax® XT XT1XT4 = Tmax® XT XT4XT5 = Tmax® XT XT5XT7 = Tmax® XT XT7GF = Tmax® XT Spectra™ Panel Neutral CT kitBlank = Main or BranchB = Branch OnlyM = Main OnlyFPX = FPK = With Filler Plate Kit (full width plates with cutouts for handles, etc.) With Filler Plate Kit and Kirk Lock Provision 6C/B FrameModification CodeMounting Accessory CodeXT1GFB FPX400 = 400A Tmax® XT XT5 600 = 600A Tmax® XT XT5 800 = 800A Tmax® XT XT7 100 = 1000A Tmax® XT XT7 120 = 1200A Tmax® XT XT7

Page 29

—Choosing the right retrofit has never been so easyYou consider what you need. We will show you what's possibleStep 1. Select breaker and trip unitStep 2. Select retrofit kitStep 3. Enter separate breaker and retrofit kit orders through empower.abb.com using desktop, laptop or mobile devices. ABB empowerStep 4. Receive breaker and retrofit kit shipments— 01 Maximum of two Tmax® XT4, XT5 or XT7 retrofit kits can be installed, side by side, in an existing Spectra™ panelboard installation— 02 For instantaneous selectivity, see DET-760. For series ratings, see DET-008.— 02 XT7 breaker handle extension included in this kit— 01 Maximum of two Tmax® XT4, XT5 or XT7 retrofit kits can be installed, side by side, in an existing Spectra™ panelboard installation Possible combinations within the rangeLegacy Spectra™ breakerSpectra™ E Frame Spectra™ F Frame Spectra™ G Frame Spectra™ K FrameTmax® XT BreakerTmax® XT1 Tmax® XT4 Tmax® XT5 Tmax® XT7Industrial applicationsCommercial and industrial applicationsThermal-magnetic trip unitsElectronic trip units125 A 250 A 250 A 600 A 600 A 1200 ALegacy Spectra™based Kit AMCB6EBFP AMCB6FJFP AMCB3FJFP AMCB6GBFP AMCB3GMFP AMCB3KMFPTmax® XT Kit01SRFB6XT1FPX SRFB6XT4FPX SRFB3XT4FPX SRFB6XT5BFPX SRFB3XT5MFPX SRFB3XT7MFPX02Tmax® XT Kit with Kirk lock provisions01SRFB6XT1FPK SRFB6XT4FPK SRFB3XT4FPK SRFB6XT5BFPK SRFB3XT5MFPK SRFB3XT7MFPK02SRFN400GF XT5 UL 400 A Neutral current transformer kitSRFN600GF XT5 UL 600 A Neutral current transformer kitSRFN800GF XT7 UL 800 A Neutral current transformer kitSRFN100GF XT7 UL 1000 A Neutral current transformer kitSRFN120GF XT7 UL 1200 A Neutral current transformer kitThe world of electrical distribution is a complex one, yet choosing the right device for your individual needs has never been simpler thanks to this Tmax® XT retrofit01 offering for Spectra™ Panelboards and Switchboards. Maybe you are looking for a basic protection device for a standard distribution system. Or perhaps you need something more complex, such as a locking mechanisms or devices that integrate protection, automation, measuring and communication into a cloud-based supervision system. Follow the flowchart when placing an order. All mount-ing kits, filler plates and hardware required are included under a single part number. Circuit breakers are ordered separately.02Bolt-on Strap Kits - Type SRFBNeutral CT Kits - Type SRFNExample: Example: SRFBSRFN6400PolesAmpere Rating3 XT1 = Tmax® XT XT1XT4 = Tmax® XT XT4XT5 = Tmax® XT XT5XT7 = Tmax® XT XT7GF = Tmax® XT Spectra™ Panel Neutral CT kitBlank = Main or BranchB = Branch OnlyM = Main OnlyFPX = FPK = With Filler Plate Kit (full width plates with cutouts for handles, etc.) With Filler Plate Kit and Kirk Lock Provision 6C/B FrameModification CodeMounting Accessory CodeXT1GFB FPX400 = 400A Tmax® XT XT5 600 = 600A Tmax® XT XT5 800 = 800A Tmax® XT XT7 100 = 1000A Tmax® XT XT7 120 = 1200A Tmax® XT XT7

Page 30

—Accessories for Retrofit KitsThe parts you might need for your installationNeutral Current Transformers for XT5 and XT7XT1 Kirk LockXT7 folding handle reduces handle operation effort and are included in XT7 retrofit kitsXT4 Kirk LockXT5 Kirk LockXT7 Kirk Lock

Page 31

—Lighting distribution panelboardsRenewal partsMounting hardwareOrder from the customer service centerMounting hardware with filler plate, straps and brackets bolt-on Spectra™- Mounting kit with filler plate includes hardware straps, brackets and filler plate.- Filler plate kit includes filler plate and associated hardware only.Mounting Arrangement Breaker Frame Number of Poles Box Width Range X Height Product NumberDual Mounted TEB, TED    Dual Mounted TEY    Dual Mounted FBV, FBN, FBH, or FBL    Dual Mounted FCS, FCV, FCN, FCH or FCL    Dual Mounted FES, FEV, FEN, FEH or FEL    Dual Mounted TQD, THQD    Dual Mounted THED, SED, SEH, SEL, SEP    Dual Mounted TEB, TED, THED, SED, SEH, SEL, SEP    Dual Mounted     Dual Mounted     Dual Mounted TEY    Dual Mounted FBV, FBN, FBH, or FBL    Dual Mounted FCS, FCV, FCN, FCH or FCL    Dual Mounted FES, FEV, FEN, FEH or FEL    Dual Mounted TQD, THQD    Dual Mounted SFH, SFL, SFP    Dual Mounted SFH, SFL, SFP    Dual Mounted     Dual Mounted     Dual Mounted     Dual Mounted     Dual Mounted FGV, FGN, FGH or FGP    Dual Mounted SGH, SGL, SGP    Dual Mounted FGV, FGN, FGH or FGP    Dual Mounted SGH, SGL, SGP    Dual Mounted     Dual Mounted     Single Mounted SFH, SFL, SFP    Single Mounted     Single Mounted FGV, FGN, FGH or FGP    Single Mounted FES, FEV, FEN, FEH or FEL    Single Mounted SGH, SGL, SGP    Single Mounted SFH, SFL, SFP    Single Mounted     Single Mounted     Single Mounted     Single Mounted FGV, FGN, FGH or FGP    Single Mounted FES, FEV, FEN, FEH or FEL    Single Mounted SGH, SGL, SGP    Single Mounted     Single Mounted     Single Mounted SKP    Single Mounted SKH, SKL, SKP, TKM, THKM    Single Mounted SKH, SKL, SKP, TKM, THKM    Single Mounted     Single Mounted     1Maximum of two XT4, XT5, XT7 kits may be stacked beside each other.Please note that Spectra, TED, FE, and FG breakers are obsolete

Page 32

—Lighting distribution panelboardsRenewal partsMounting hardwareOrder from the customer service centerFiller plates plug-in or bolt-on Spectra™ Use to cover unused spaces.Includes filler plate support brackets and hardware.SpaceX Height1Box Width RangeSwitchboardSection WidthsProductNumber                                                      1Filler plates bolt-on Spectra™- Filler plate kit includes filler plate and associated hardware only.Mounting Arrangement Breaker Frame Number of Poles Box Width Range X Height Product NumberDual Mounted TQD, THQD    Dual Mounted TEB, TED    Dual Mounted TEY    Dual Mounted FBV, FBN, FBH, or FBL    Dual Mounted FBV, FBN, FBH, or FBL    Dual Mounted TQD, THQD    Dual Mounted TEB, TED, THED,SED, SEH, SEL, SEP    Dual Mounted SFH, SFL, SFP    Dual Mounted     Dual Mounted FGV, FGN, FGH or FGP    Dual Mounted SGH, SGL, SGP    Single Mounted SFH, SFL, SFP    Single Mounted     Single Mounted FGV, FGN, FGH or FGP    Single Mounted SGH, SGL, SGP    Single Mounted SKP    Single Mounted SKP, SKH, SKL, TKM, THKM    Please note that Spectra, TED, FE, and FG breakers are obsolete

Page 33

—Molded Case Circuit Breakers

Page 34

—Q-Line Circuit BreakersBolt-on Circuit Breakers240V ClassTQB, THQB 120/240 Vac# of Poles Ampere Rating Wire Range1120/240 Vac Interrupting Rating Product Number1 10 14-8 Cu/12-8 Al 5kA TQB111031 15 14-8 Cu/12-8 Al 10kA THQB111521 20 14-8 Cu/12-8 Al 10kA THQB112021 25 14-8 Cu/12-8 Al 10kA THQB11251 30 14-8 Cu/12-8 Al 10kA THQB11301 35 8-3 Cu/8-3 Al 10kA THQB11351 40 8-3 Cu/8-3 Al 10kA THQB11401 45 8-3 Cu/8-3 Al 10kA THQB11451 50 8-3 Cu/8-3 Al 10kA THQB11501 60 8-3 Cu/8-3 Al 10kA THQB11601 70 6-1/0 Cu/4-1/0 Al 10kA THQB1170TQB, THQB 120/240 Vac, Internal Common Trip# of Poles Ampere Rating Wire Range1120/240 Vac Interrupting Rating Product Number2 10 14-8 Cu/12-8 Al 5kA TQB211032 15 14-8 Cu/12-8 Al 10kA THQB21152 20 14-8 Cu/12-8 Al 10kA THQB21202 25 14-8 Cu/12-8 Al 10kA THQB21252 30 14-8 Cu/12-8 Al 10kA THQB21302 35 8-3 Cu/8-3 Al 10kA THQB21352 40 8-3 Cu/8-3 Al 10kA THQB21402 45 8-3 Cu/8-3 Al 10kA THQB21452 50 8-3 Cu/8-3 Al 10kA THQB21502 60 8-3 Cu/8-3 Al 10kA THQB21602 70 6-1/0 Cu/4-1/0 Al 10kA THQB21702 80 6-1/0 Cu/4-1/0 Al 10kA THQB21802 90 6-1/0 Cu/4-1/0 Al 10kA THQB21902 100 6-1/0 Cu/4-1/0 Al 10kA THQB21100TQB, THQB 240 Vac, Internal Common Trip# of Poles Ampere Rating Wire Range1240 Vac Interrupting Rating Product Number2 10 14-8 Cu/12-8 Al 5kA TQB2201032 15 14-8 Cu/12-8 Al 10kA THQB220152 20 14-8 Cu/12-8 Al 10kA THQB220202 25 14-8 Cu/12-8 Al 10kA THQB220252 30 14-8 Cu/12-8 Al 10kA THQB220302 35 8-3 Cu/8-3 Al 10kA THQB220352 40 8-3 Cu/8-3 Al 10kA THQB220402 45 8-3 Cu/8-3 Al 10kA THQB220452 50 8-3 Cu/8-3 Al 10kA THQB220502 60 8-3 Cu/8-3 Al 10kA THQB220602 70 6-1/0 Cu/4-1/0 Al 10kA THQB220702 80 6-1/0 Cu/4-1/0 Al 10kA THQB220802 90 6-1/0 Cu/4-1/0 Al 10kA THQB220902 100 6-1/0 Cu/4-1/0 Al 10kA THQB221003 10 14-8 Cu/12-8 Al 5kA TQB3201033 15 14-8 Cu/12-8 Al 10kA THQB320153 20 14-8 Cu/12-8 Al 10kA THQB320203 25 14-8 Cu/12-8 Al 10kA THQB320253 30 14-8 Cu/12-8 Al 10kA THQB320303 35 8-3 Cu/8-3 Al 10kA THQB320353 40 8-3 Cu/8-3 Al 10kA THQB320403 45 8-3 Cu/8-3 Al 10kA THQB320453 50 8-3 Cu/8-3 Al 10kA THQB320503 60 8-3 Cu/8-3 Al 10kA THQB320603 70 6-1/0 Cu/4-1/0 Al 10kA THQB320703 80 6-1/0 Cu/4-1/0 Al 10kA THQB320803 90 6-1/0 Cu/4-1/0 Al 10kA THQB320903 100 6-1/0 Cu/4-1/0 Al 10kA THQB321001Solid or stranded for 14-10 AWG.2UL listed as SWD (Switching Duty) rated. Suitable for switching 120 Vac fluorescent lighting loads.3Not UL listed.UL listed HACR (heating, air conditioning and refrigeration).THQB2115

Page 35

—Q-Line Circuit BreakersBolt-on Circuit Breakers240V ClassTHQB and THHQB 120/240 Vac Arc Fault (Single pole)# of Poles Ampere Rating Wire Range1120/240 Vac Interrupting Rating Product Number1 15 14-10 Cu/14-10 Al 10kA THQB1115AF221 20 14-10 Cu/14-10 Al 10kA THQB1120AF221 15 14-10 Cu/14-10 Al 22kA THHQB1115AF221 20 14-10 Cu/14-10 Al 22kA THHQB1120AF22THQB 120 Vac, Ground Fault Circuit Interrupters (30 ma); cULus# of Poles Ampere Rating Wire Range1120 Vac Interrupting Rating Product Number1 15 14-8 Cu/12-8 Al 10kA THQB1115GFEP1 20 14-8 Cu/12-8 Al 10kA THQB1120GFEP1 30 14-8 Cu/12-8 Al 10kA THQB1130GFEPTHHQB 120 Vac, Ground Fault Circuit Interrupters, Internal Common Trip# of Poles Ampere Rating Wire Range1120 Vac Interrupting Rating Product Number2 15 14-8 Cu/12-8 Al 22kA THHQB2115GFEP2 20 14-8 Cu/12-8 Al 22kA THHQB2120GFEP2 30 14-8 Cu/12-8 Al 22kA THHQB2130GFEPTHQB 120/240 or 208Y/120 Vac, Ground Fault Circuit Interrupters (30 ma); cULusInternal Common Trip# of Poles Ampere Rating Wire Range1120 Vac Interrupting Rating Product Number2 15 14-8 Cu/12-8 Al 10kA THQB2115GFEP2 20 14-8 Cu/12-8 Al 10kA THQB2120GFEP2 30 14-8 Cu/12-8 Al 10kA THQB2130GFEP2 40 14-8 Cu/12-8 Al 10kA THQB2140GFEP1Solid or stranded for 14-10 AWG.2Combination AFCI compliant with NEC 2008 and later.THQB, THHQB 120/240 Vac, Ground Fault Circuit Interrupters, Self Testing, cULus# of Poles Ampere Rating Wire Range1120/240 Vac Interrupting Rating Product Number1 15 14-8Cu/12-8 Al 10kA THQB1115GFT1 20 14-8Cu/12-8 Al 10kA THQB1120GFT1 25 14-8 Cu/12-8 Al 10kA THQB1125GFT1 30 14-8Cu/12-8 Al 10kA THQB1130GFT1 15 14-8Cu/12-8 Al 22kA THHQB1115GFT1 20 14-8Cu/12-8 Al 22kA THHQB1120GFT1 25 14-8 Cu/12-8 Al 22kA THHQB1125GFT1 30 14-8Cu/12-8 Al 22kA THHQB1130GFT2 15 14-8Cu/12-8 Al 10kA THQB2115GFT2 20 14-8Cu/12-8 Al 10kA THQB2120GFT2 25 14-8 Cu/12-8 Al 10kA THQB2125GFT2 30 14-8Cu/12-8 Al 10kA THQB2130GFT2 15 14-8Cu/12-8 Al 22kA THHQB2115GFT2 20 14-8Cu/12-8 Al 22kA THHQB2120GFT2 25 14-8Cu/12-8 Al 22kA THHQB2125GFT2 30 14-8Cu/12-8 Al 22kA THHQB2130GFTTHQB1120AF2THQB2120GFTTHQB1115GFEPTHQB2140GFEP

Page 36

—Q-Line Circuit BreakersBolt-on Circuit Breakers240V ClassTHQB, THHQB 120/240 Vac, High Intensity Discharge Lighting Loads1# of Poles Ampere Rating Wire Range2120/240 Vac Interrupting Rating Product Number1 15 14-8 Cu/12-8 Al 10kA THQB1115HID31 20 14-8 Cu/12-8 Al 10kA THQB1120HID31 25 14-8 Cu/12-8 Al 10kA THQB1125HID1 30 14-8 Cu/12-8 Al 10kA THQB1130HID1 15 14-8 Cu/12-8 Al 22kA THHQB1115HID31 20 14-8 Cu/12-8 Al 22kA THHQB1120HID31 25 14-8 Cu/12-8 Al 22kA THHQB1125HID1 30 14-8 Cu/12-8 Al 22kA THHQB1130HID2 15 14-8 Cu/12-8 Al 10kA THQB2115HID2 20 14-8 Cu/12-8 Al 10kA THQB2120HID2 25 14-8 Cu/12-8 Al 10kA THQB2125HID2 30 14-8 Cu/12-8 Al 10kA THQB2130HIDTHQB 120 Vac, Internal Common Trip with Factory Installed 120 Vac Shunt Trip4# of Poles Ampere Rating Wire Range2120 Vac Interrupting Rating Product Number2 20 14-8 Cu/12-8 Al 10kA THQB2120ST12 30 14-8 Cu/12-8 Al 10kA THQB2130ST12 100 6-1/0 Cu/4-1/0 Al 10kA THQB21100ST13 20 14-8 Cu/12-8 Al 10kA THQB32020ST13 30 14-8 Cu/12-8 Al 10kA THQB32030ST13 35 8-3 Cu/8-3 Al 10kA THQB32035ST13 40 8-3 Cu/8-3 Al 10kA THQB32040ST13 50 8-3 Cu/8-3 Al 10kA THQB32050ST13 60 8-3 Cu/8-3 Al 10kA THQB32060ST13 70 6-1/0 Cu/4-1/0 Al 10kA THQB32070ST13 80 6-1/0 Cu/4-1/0 Al 10kA THQB32080ST13 90 6-1/0 Cu/4-1/0 Al 10kA THQB32090ST13 100 6-1/0 Cu/4-1/0 Al 10kA THQB32100ST1THHQB 120/240 Vac, Internal Common Trip, High Intensity Discharge Lighting Loads1# of Poles Ampere Rating Wire Range2120/240 Vac Interrupting Rating Product Number2 15 14-8 Cu/12-8 Al 22kA THHQB2115HID2 20 14-8 Cu/12-8 Al 22kA THHQB2120HID2 25 14-8 Cu/12-8 Al 22kA THHQB2125HID2 30 14-8 Cu/12-8 Al 22kA THHQB2130HIDTHQB 120 Vac with Switching Neutral Single Thermal Magnetic Pole;Single Nonautomatic Pole# of Poles Ampere Rating Wire Range2120 Vac Interrupting Rating Product Number2 15 14-8 Cu/12-8 Al 10kA THQB21WY152 20 14-8 Cu/12-8 Al 10kA THQB21WY202 25 14-8 Cu/12-8 Al 10kA THQB21WY252 30 14-8 Cu/12-8 Al 10kA THQB21WY30THQB 120 Vac with Switching Neutral Two Thermal Magnetic Pole;Single Nonautomatic Pole# of Poles Ampere Rating Wire Range2120 Vac Interrupting Rating Product Number3 15 14-8 Cu/12-8 Al 10kA THQB31W Y153 20 14-8 Cu/12-8 Al 10kA THQB31WY203 25 14-8 Cu/12-8 Al 10kA THQB31WY253 30 14-8 Cu/12-8 Al 10kA THQB31WY301UL listed as HID (high intensity discharge).2Solid or stranded for 14-10 AWG.3UL listed as SWD (switching duty). Suitable for switching 120 Vac fluorescent lighting loads.420-60 ampere are UL listed as HACR (heating, air conditioning and refrigeration).THQB 120 Vac with Factory Installed 120 Vac Shunt Trip4# of Poles Ampere Rating Wire Range2120 Vac Interrupting Rating Product Number1 20 14-8 Cu/12-8 Al 10kA THQB1120ST1THQB32020ST1

Page 37

—Q-Line Circuit BreakersBolt-on Circuit Breakers240V ClassTHHQB 120/240 Vac# of Poles Ampere Rating Wire Range1120/240 Vac Interrupting Rating Product Number1 15 14-8 Cu/12-8 Al 22kA THHQB111521 20 14-8 Cu/12-8 Al 22kA THHQB112021 25 14-8 Cu/12-8 Al 22kA THHQB11251 30 14-8 Cu/12-8 Al 22kA THHQB11301 35 8-3 Cu/8-3 Al 22kA THHQB11351 40 8-3 Cu/8-3 Al 22kA THHQB11401 45 8-3 Cu/8-3 Al 22kA THHQB11451 50 8-3 Cu/8-3 Al 22kA THHQB11501 60 8-3 Cu/8-3 Al 22kA THHQB11601 70 6-1/0 Cu/4-1/0 Al 22kA THHQB1170THQB/THHQB 120/240 Vac, Low Magnetic Pickup# of Poles Ampere Rating Wire Range1120/240 Vac Interrupting Rating Product Number1 15 14-8 Cu/12-8 Al 10 kA THQB1115LM21 20 14-8 Cu/12-8 Al 10 kA THQB1120LM21 15 14-8 Cu/12-8 Al 22 kA THHQB1115LM1 20 14-8 Cu/12-8 Al 22 kA THHQB1120LM2 15 14-8 Cu/12-8 Al 10 kA THQB2115LM2 20 14-8 Cu/12-8 Al 10 kA THQB2120LM2 15 14-8 Cu/12-8 Al 22 kA THHQB2115LM2 20 14-8 Cu/12-8 Al 22 kA THHQB2120LMTHHQB 120/240 Vac, Internal Common Trip# of Poles Ampere Rating Wire Range1120/240 Vac Interrupting Rating Product Number2 15 14-8 Cu/12-8 Al 22kA THHQB21152 20 14-8 Cu/12-8 Al 22kA THHQB21202 25 14-8 Cu/12-8 Al 22kA THHQB21252 30 14-8 Cu/12-8 Al 22kA THHQB21302 35 8-3 Cu/8-3 Al 22kA THHQB21352 40 8-3 Cu/8-3 Al 22kA THHQB21402 45 8-3 Cu/8-3 Al 22kA THHQB21452 50 8-3 Cu/8-3 Al 22kA THHQB21502 60 8-3 Cu/8-3 Al 22kA THHQB21602 70 6-1/0 Cu/4-1/0 Al 22kA THHQB21702 80 6-1/0 Cu/4-1/0 Al 22kA THHQB21802 90 6-1/0 Cu/4-1/0 Al 22kA THHQB21902 100 6-1/0 Cu/4-1/0 Al 22kA THHQB21100THHQB 120/240 Vac, Internal Common Trip# of Poles Ampere Rating Wire Range1240 Vac Interrupting Rating Product Number2 15 14-8 Cu/12-8 Al 22kA THHQB220152 20 14-8 Cu/12-8 Al 22kA THHQB220202 25 14-8 Cu/12-8 Al 22kA THHQB220252 30 14-8 Cu/12-8 Al 22kA THHQB220302 35 8-3 Cu/8-3 Al 22kA THHQB220352 40 8-3 Cu/8-3 Al 22kA THHQB220402 45 8-3 Cu/8-3 Al 22kA THHQB220452 50 8-3 Cu/8-3 Al 22kA THHQB220502 60 8-3 Cu/8-3 Al 22kA THHQB220602 70 6-1/0 Cu/4-1/0 Al 22kA THHQB220702 80 6-1/0 Cu/4-1/0 Al 22kA THHQB220802 90 6-1/0 Cu/4-1/0 Al 22kA THHQB220902 100 6-1/0 Cu/4-1/0 Al 22kA THHQB221003 15 14-8 Cu/12-8 Al 22kA THHQB320153 20 14-8 Cu/12-8 Al 22kA THHQB320203 25 14-8 Cu/12-8 Al 22kA THHQB320253 30 14-8 Cu/12-8 Al 22kA THHQB320303 35 8-3 Cu/8-3 Al 22kA THHQB320353 40 8-3 Cu/8-3 Al 22kA THHQB320403 45 8-3 Cu/8-3 Al 22kA THHQB320453 50 8-3 Cu/8-3 Al 22kA THHQB320503 60 8-3 Cu/8-3 Al 22kA THHQB320603 70 6-1/0 Cu/4-1/0 Al 22kA THHQB320703 80 6-1/0 Cu/4-1/0 Al 22kA THHQB320803 90 6-1/0 Cu/4-1/0 Al 22kA THHQB320903 100 6-1/0 Cu/4-1/0 Al 22kA THHQB321001Solid or stranded for 14-10 AWG.2UL listed as SWD (switching duty) rated. Suitable for switching 120 Vac fluorescent lighting loads.UL listed HACR (heating, air conditioning and refrigeration).THHQB2115

Page 38

—Industrial Circuit Breakers15-100AThermal Magnetic TripType TEY/TEYFNoninterchangeable TripBolt-on480Y/277V ClassTEY/TEYF (UL/cUL File E-11592)AmpereRatingWire Range1Product Number Product NumberSingle Pole - Includes Integral Cu/Al Load LugsType TEY3, 414kA @ 277 VacType TEYF3, 418kA @ 277 Vac15 #14-#10 TEY1152TEYF115220 #14-#10 TEY1202TEYF120225 #14-#10 TEY125 TEYF12530 #14-#10 TEY130 TEYF13035 #10-#4 TEY135 TEYF13540 #10-#4 TEY140 TEYF14045 #10-#4 TEY145 TEYF14550 #10-#4 TEY150 TEYF15060 #10-#4 TEY160 TEYF16070 #4 -1/0 TE Y170 –80 #4-1/0 TEY180 –90 #4-1/0 TEY190 –100 #4-1/0 TEY1100 –Two-Pole - Includes Integral Cu/Al Load LugsType TEY3, 414kA @ 480 / 277 VacType TEYF3, 418kA @ 480 / 277 Vac15 #14-#10 TEY215 TEYF21520 #14-#10 TEY220 TEYF22025 #14-#10 TEY225 TEYF22530 #14-#10 TEY230 TEYF23035 #10-#4 TEY235 TEYF23540 #10-#4 TEY240 TEYF24045 #10-#4 TEY245 TEYF24550 #10-#4 TEY250 TEYF25060 #10-#4 TEY260 TEYF26070 #4 -1/0 TEY270 TEYF27080 #4-1/0 TEY280 TEYF28090 #4-1/0 TEY290 TEYF290100 #4-1/0 TEY2100 TEYF2100110 #4-2/0 – TEYF2110B125 #4-2/0 – TEYF2125BThree-Pole - Includes Integral Cu/Al Load LugsType TEY3, 414kA @ 480 / 277 VacType TEYF3, 418kA @ 480 / 277 Vac15 #14-#10 TEY315 TEYF31520 #14-#10 TEY320 TEYF32025 #14-#10 TEY325 TEYF32530 #14-#10 TEY330 TEYF33035 #10-#4 TEY335 TEYF33540 #10-#4 TEY340 TEYF34045 #10-#4 TEY345 TEYF34550 #10-#4 TEY350 TEYF35060 #10-#4 TEY360 TEYF36070 #4 -1/0 TEY370 TEYF37080 #4-1/0 TEY380 TEYF38090 #4-1/0 TEY390 TEYF390100 #4-1/0 TEY3100 TEYF3100110 #4-2/0 – TEYF3110B125 #4-2/0 – TEYF3125B1Solid or stranded for 14-10 AWG.2 Single-pole, 15 and 20 ampere breakers are also UL listed as switching duty breakers, suitable for switching 120, 240, or 277 Vac.3UL listed HACR (Heating, Air Conditioning, Refrigeration).4UL listed for HID (high intensity discharge), all 50A or less.1- 2- and 3-pole TEY/TEYF breakersTEY and TEYF breakers are one-inch wide per pole, compact, bolt-on circuit breakersfor use on grounded 480Y/277 Vac systems. Short circuit ratings at that voltage for TEYand TEYF are 14 and 18kA, respectively. TEYF also offers higher selectivity ratings withupstream devices (See DET-537 for details). The bolt-on mounting base (TEY3B) shownon page 6-217 makes TEY and TEYF suitable for various lug-lug applications.

Page 39

—Industrial Circuit Breakers15-125AThermal Magnetic TripType TEYD/TEYH/TEYLNoninterchangeable TripBolt-on480Y/277V ClassTEYD/TEYH/TEYL (UL/cUL File E-11592)AmpereRatingWire Range1Product Number Product Number Product NumberSingle Pole Includes Load LugsType TEYD25kA @ 480 / 277 VacType TEYH35kA @ 480 / 277 VacType TEYL65kA @ 480 / 277 Vac15 #14-#10 TEYD1015B TEYH1015B TEYL1015B20 #14-#10 TEYD1020B TEYH1020B TEYL1020B25 #10-#4 TEYD1025B TEYH1025B TEYL1025B30 #10-#4 TEYD1030B TEYH1030B TEYL1030B35 #10-#4 TEYD1035B TEYH1035B TEYL1035B40 #10-#4 TEYD1040B TEYH1040B TEYL1040B45 #10-#4 TEYD1045B TEYH1045B TEYL1045B50 #10-#4 TEYD1050B TEYH1050B TEYL1050B60 #10-#4 TEYD1060B TEYH1060B TEYL1060B70 #4-2/0 TEYD1070B TEYH1070B TEYL1070BTwo-PoleIncludes Load LugsType TEYD25kA @ 480 / 277 VacType TEYH35kA @ 480 / 277 VacType TEYL65kA @ 480 / 277 Vac15 #14-10 TEYD2015B TEYH2015B TEYL2015B20 #14 -10 TEYD2020B TEYH2020B TEYL2020B25 #10-#4 TEYD2025B TEYH2025B TEYL2025B30 #10-#4 TEYD2030B TEYH2030B TEYL2030B35 #10-#4 TEYD2035B TEYH2035B TEYL2035B40 #10-#4 TEYD2040B TEYH2040B TEYL2040B45 #10-#4 TEYD2045B TEYH2045B TEYL2045B50 #10-#4 TEYD2050B TEYH2050B TEYL2050B60 #10-#4 TEYD2060B TEYH2060B TEYL2060B70 #4-2/0 TEYD2070B TEYH2070B TEYL2070B80 #4-2/0 TEYD2080B TEYH2080B TEYL2080B90 #4-2/0 TEYD2090B TEYH2090B TEYL2090B100 #4-2/0 TEYD2100B TEYH2100B TEYL2100B110 #4-2/0 TEYD2110B TEYH2110B TEYL2110B125 #4-2/0 TEYD2125B TEYH2125B TEYL2125BThree-PoleIncludes Load LugsType TEYD25kA @ 480 / 277 VacType TEYH35kA @ 480 / 277 VacType TEYL65kA @ 480 / 277 Vac15 #14-#10 TEYD3015B TEYH3015B TEYL3015B20 #14-#10 TEYD3020B TEYH3020B TEYL3020B25 #10-#4 TEYD3025B TEYH3025B TEYL3025B30 #10-#4 TEYD3030B TEYH3030B TEYL3030B35 #10-#4 TEYD3035B TEYH3035B TEYL3035B40 #10-#4 TEYD3040B TEYH3040B TEYL3040B45 #10-#4 TEYD3045B TEYH3045B TEYL3045B50 #10-#4 TEYD3050B TEYH3050B TEYL3050B60 #10-#4 TEYD3060B TEYH3060B TEYL3060B70 #4-2/0 TEYD3070B TEYH3070B TEYL3070B80 #4-2/0 TEYD3080B TEYH3080B TEYL3080B90 #4-2/0 TEYD3090B TEYH3090B TEYL3090B100 #4-2/0 TEYD3100B TEYH3100B TEYL3100B110 #4-2/0 TEYD3110B TEYH3110B TEYL3110B125 #4-2/0 TEYD3125B TEYH3125B TEYL3125B1Solid or stranded for 14-10 AWG.2 Single-pole, 15 and 20 ampere breakers are also UL listed as switching duty breakers, suitable for switching 120, 240, or 277 Vac.3UL listed HACR (Heating, Air Conditioning, Refrigeration).4UL listed for HID (high intensity discharge), all 50A or less. ;The TEY family of circuit breakers (TEY, TEYF, TEYD, TEYH, and TEYL) are one-inch wide perpole, compact, bolt-on circuit breakers for use on grounded 480Y/277 Vac systems, andare typically installed within Lighting Panelboards, including ABB A-Series. Short circuitratings at 480/277 Vac are shown in the tables that follow. Ratings at other voltages areshown in the Quick Reference Guide at the beginning of this section. Bolt-On mountingbases TEY3B (page 6-66) and TEY3B125 (page 6-66) make these frames suitable forunit mount / lug-lug connected applications. Handle tie kits, suitable for use with multiplesingle pole breakers used on shared neutral circuits (page 6-66) are available forTEYD/H/L circuit breakers.1- 2- and 3-poleTEYD/TEYH/TEYL breakers

Page 40

—Formula A Circuit breakers for power distributionA2 ordering informationA2 250 A — Fixed (F) 2-pole — Front terminals (F), thermal-magnetic trip unit — TMF Icu (240 V)In I3 A (10 kA) N (25 kA)125 1250 A2A125TW-2 A2N125TW-2150 1500 A2A150TW-2 A2N150TW-2175 1750 A2A175T W-2 A2N175TW-2200 2000 A2A200TW-2 A2N200TW-2225 2250 A2A225TW-2 A2N225TW-2250 2500 A2A250TW-2 A2N250TW-2A2 250 A — Fixed (F) 3-pole — Front terminals (F), thermal-magnetic trip unit — TMF Icu (240 V)In I3 A (10 kA) N (25 kA)125 1250 A2A125TW A2N125TW150 1500 A2A150TW A2N150TW175 1750 A 2A175TW A2N175TW200 2000 A2A200TW A2N200TW225 2250 A2A225TW A2N225TW250 2500 A2A250TW A2N250TW

Page 41

—Tmax XT molded case circuit breakersXT1 stocked base breakersN S HInterrupt rating @ 480v 25kA 35kA 65kAIn I3Ordering Code Ordering Code Ordering CodeFixed thermal magnetic trip unit (TMF)15 500 XT1NU3015AFF000XXX XT1SU3015AFF000XXX XT1HU3015AFF000XXX20 500 XT1NU3020AFF000XXX XT1SU3020AFF000XXX XT1HU3020AFF000XXX25 500 XT1NU3025AFF000XXX XT1SU3025AFF000XXX XT1HU3025AFF000XXX30 500 XT1NU3030AFF000XXX XT1SU3030AFF000XXX XT1HU3030AFF000XXX35 500 XT1NU3035AFF000XXX XT1SU3035AFF000XXX XT1HU3035AFF000XXX40 500 XT1NU3040AFF000XXX XT1SU3040AFF000XXX XT1HU3040AFF000XXX45 500 XT1NU3045AFF000XXX --- XT1HU3045AFF000XXX50 500 XT1NU3050AFF000XXX XT1SU3050AFF000XXX XT1HU3050AFF000XXX60 600 XT1NU3060AFF000XXX XT1SU3060AFF000XXX XT1HU3060AFF000XXX70 700 XT1NU3070AFF000XXX XT1SU3070AFF000XXX XT1HU3070AFF000XXX80 800 XT1NU3080AFF000XXX XT1SU3080AFF000XXX XT1HU3080AFF000XXX90 900 XT1NU3090AFF000XXX XT1SU3090AFF000XXX XT1HU3090AFF000XXX100 1000 XT1NU3100AFF000XXX XT1SU3100AFF000XXX XT1HU3100AFF000XXX110 1100 XT1NU3110AFF000XXX XT1SU3110AFF000XXX XT1HU3110AFF000XXX125 1250 XT1NU3125AFF000XXX XT1SU3125AFF000XXX XT1HU3125AFF000XXXMagnetic trip unit (MCP)3 9-33 --- --- XT1HU3003MFF000XXX7 21-77 --- --- XT1HU3007MFF000XXX15 45-165 --- --- XT1HU3015MFF000XXX30 90-330 --- --- XT1HU3030MFF000XXX50 150-550 --- --- XT1HU3050MFF000XXX70 210-770 --- --- XT1HU3070MFF000XXX80 240-880 --- --- XT1HU3080MFF000XXX100 300-1100 --- --- XT1HU3100MFF000XXX125 375-1375 --- --- XT1HU3125MFF000XXXMolded case switchesInMag. override125 1000 XT1NU3125DFF000XXX XT1SU3125DFF000XXX XT1HU3125DFF000XXXXT1 125A Fixed (F) - 3 poles - Front terminals (F) - UL/CSA* Lugs not included. Please refer to page 31-32 for lug information.

Page 42

N S H LInterrupt rating @ 480v 25kA 35kA 65kA 100kAIn Ordering code Ordering code Ordering code Ordering codeThermal magnetic fixed (TMF)15 XT2NU3015AFF000XXX XT2SU3015AFF000XXX XT2HU3015AFF000XXX XT2LU3015AFF000XXX20 XT2NU3020AFF000XXX XT2SU3020AFF000XXX XT2HU3020AFF000XXX XT2LU3020AFF000XXX25 XT2NU3025AFF000XXX XT2SU3025AFF000XXX XT2HU3025AFF000XXX ---30 XT2NU3030AFF000XXX XT2SU3030AFF000XXX XT2HU3030AFF000XXX XT2LU3030AFF000XXX35 XT2NU3035AFF000XXX XT2SU3035AFF000XXX XT2HU3035AFF000XXX XT2LU3035AFF000XXX40 XT2NU3040AFF000XXX XT2SU3040AFF000XXX XT2HU3040AFF000XXX XT2LU3040AFF000XXX50 XT2NU3050AFF000XXX XT2SU3050AFF000XXX XT2HU3050AFF000XXX XT2LU3050AFF000XXX60 XT2NU3060AFF000XXX XT2SU3060AFF000XXX XT2HU3060AFF000XXX XT2LU3060AFF000XXX70 XT2NU3070AFF000XXX XT2SU3070AFF000XXX XT2HU3070AFF000XXX XT2LU3070AFF000XXXThermal magnetic adjustable (TMA)80 XT2NU3080BFF000XXX XT2SU3080BFF000XXX XT2HU3080BFF000XXX XT2LU3080BFF000XXX90 XT2NU3090BFF000XXX XT2SU3090BFF000XXX XT2HU3090BFF000XXX XT2LU3090BFF000XXX100 XT2NU3100BFF000XXX --- XT2HU3100BFF000XXX XT2LU3100BFF000XXX125 XT2NU3125BFF000XXX XT2SU3125BFF000XXX XT2HU3125BFF000XXX XT2LU3125BFF000XXXMagnetic trip unit (MCP)7 --- --- XT2HU3007MFF000XXX ---15 --- --- XT2HU3015MFF000XXX ---30 --- --- XT2HU3030MFF000XXX ---50 --- --- XT2HU3050MFF000XXX ---70 --- --- XT2HU3070MFF000XXX ---100 --- --- XT2HU3100MFF000XXX ---125 --- --- XT2HU3125MFF000XXX ---Ekip LS/I trip unit60 XT2NU3060EFF000XXX --- XT2HU3060EFF000XXX ---100 XT2NU3100EFF000XXX XT2SU3100EFF000XXX XT2HU3100EFF000XXX XT2LU3100EFF000XXX125 XT2NU3125EFF000XXX XT2SU3125EFF000XXX XT2HU3125EFF000XXX ---125 (100% rated) XT2NQ3125EFF000XXX XT2SQ3125EFF000XXX XT2HQ3125EFF000XXX ---Ekip LSIG trip unit60 --- --- XT2HU3060GFF000XXX ---100 --- XT2SU3100GFF000XXX XT2HU3100GFF000XXX ---125 XT2NU3125GFF000XXX --- XT2HU3125GFF000XXX ---No trip unit (MCS)In125 --- --- XT2HU3125DFF000XXX ---—Tmax XT molded case circuit breakersXT2 stocked base breakersXT2 125A - Fixed (F) - 3 poles - Front terminals (F) - UL/CSA* Lugs not included. Please refer to page 31-32 for lug information.

Page 43

N SInterrupt rating @ 480v 25kA 35kAIn I3Ordering Code Ordering CodeFixed thermal magnetic trip unit (TMF)80 800 XT3NU3080AFF000XXX ---90 900 XT3NU3090AFF000XXX ---100 1000 XT3NU3100AFF000XXX ---110 1100 XT3NU3110AFF000XXX XT3SU3110AFF000XXX125 1250 XT3NU3125AFF000XXX XT3SU3125AFF000XXX150 1500 XT3NU3150AFF000XXX XT3SU3150AFF000XXX175 1750 XT3NU3175AFF000XXX XT3SU3175AFF000XXX200 2000 XT3NU3200AFF000XXX XT3SU3200AFF000XXX225 2250 XT3NU3225AFF000XXX XT3SU3225AFF000XXXMagnetic trip unit (MCP)125 750-1500 --- XT3SU3125MFF000XXX150 900-1800 --- XT3SU3150MFF000XXX200 1200-2400 --- XT3SU3200MFF000XXXMolded case switchIn225 2250 XT3NU3225DFF000XXX XT3SU3225DFF000XXX—Tmax XT molded case circuit breakersXT3 stocked base breakersXT3 225A - Fixed (F) - 3 poles - Front terminals (F) - UL/CSA* Lugs not included. Please refer to page 31-32 for lug information.

Page 44

—Tmax XT molded case circuit breakersXT4 stocked base breakers N S H LInterrupt rating @480v 25kA 35kA 65kA 100kAIn I3Ordering code Ordering code Ordering code Ordering codeThermal magnetic fixed (TMF)150 1500 XT4NU3150AFF000XXX XT4SU3150AFF000XXX XT4HU3150AFF000XXX XT4LU3150AFF000XXX175 1750 XT4NU3175AFF000XXX XT4SU3175AFF000XXX XT4HU3175AFF000XXX XT4LU3175AFF000XXX200 2000 XT4NU3200AFF000XXX XT4SU3200AFF000XXX XT4HU3200AFF000XXX XT4LU3200AFF000XXX225 2250 XT4NU3225AFF000XXX XT4SU3225AFF000XXX XT4HU3225AFF000XXX ---250 2500 XT4NU3250AFF000XXX XT4SU3250AFF000XXX XT4HU3250AFF000XXX XT4LU3250AFF000XXX250 (100% rated) 2500 XT4NQ3250AFF000XXX --- XT4HQ3250AFF000XXX ---Thermal magnetic adjustable (TMA)105-150 750-1500 XT4NU3150BFF000XXX XT4SU3150BFF000XXX XT4HU3150BFF000XXX 1122.5 -175 875-1750 XT4NU3175BFF000XXX XT4SU3175BFF000XXX XT4HU3175BFF000XXX XT4LU3175BFF000XXX140-200 1000-2000 XT4NU3200BFF000XXX XT4SU3200BFF000XXX XT4HU3200BFF000XXX XT4LU3200BFF000XXX157.5 -225 1125-2250 --- XT4SU3225BFF000XXX XT4HU3225BFF000XXX XT4LU3225BFF000XXX175-250 1250-2500 XT4NU3250BFF000XXX XT4SU3250BFF000XXX XT4HU3250BFF000XXX XT4LU3250BFF000XXX175-250 1250-2500 XT4NQ3250BFF000XXX XT4SQ3250BFF000XXX XT4HQ3250BFF000XXX ---Magnetic trip unit (MCP)25 75-275 --- --- XT4HU3025MFF000XXX ---50 150-550 --- --- XT4HU3050MFF000XXX ---100 500-7000 --- --- XT4HU3100MFF000XXX ---150 750-1500 --- --- XT4HU3150MFF000XXX ---175 875-1750 --- --- XT4HU3175MFF000XXX ---200 1000-2000 --- --- XT4HU3200MFF000XXX ---250 1250-2500 --- --- XT4HU3250MFF000XXX ---Ekip LS/I trip unit150 --- XT4NU3150EFF000XXX XT4SU3150EFF000XXX XT4HU3150EFF000XXX ---225 --- XT4NU3225EFF000XXX XT4SU3225EFF000XXX XT4HU3225EFF000XXX ---250 --- XT4NU3250EFF000XXX XT4SU3250EFF000XXX XT4HU3250EFF000XXX XT4LU3250EFF000XXX250 (100% rated) --- XT4NQ3250EFF000XXX XT4SQ3250EFF000XXX XT4HQ3250EFF000XXX ---Ekip LSIG trip unit150 --- XT4NU3150GFF000XXX --- XT4HU3150GFF000XXX ---225 --- XT4NU3225GFF000XXX --- --- ---250 --- XT4NU3250GFF000XXX XT4SU3250GFF000XXX XT4HU3250GFF000XXX ---Molded case switchInMag. Override 250 2500 XT4NU3250DFF000XXX XT4SU3250DFF000XXX XT4HU3250DFF000XXX ---XT4 250A - Fixed (F) - 3 poles - Front terminals (F) - UL/CSA* Lugs not included. Please refer to page 31-32 for lug information.

Page 45

Distribution circuit breakersTmax XT, XT4, 250A Frame, Ekip DIP LS/I, LSI, LSIG, and LIG protection trip units with Front TerminalsAmpsN (25kA) S (35kA) H (65kA)U.S. Ordering Code U.S. Ordering Code U.S. Ordering CodeEkip DIP LS/I40XT4N040EFF000XXX X T4S040EFF000XXX XT4H040EFF000XXX60XT4N060EFF000XXX XT4S060EFF000XXX XT4H060EFF000XXX100XT4N100EFF000XXX XT4S100EFF000XXX X T4H100EFF000XXX150XT4N150EFF000XXX XT4S150EFF000XXX XT4H150EFF000XXX225XT4N225EFF000XXX X T4S225EFF000XXX X T4H225EFF000XXX250XT4N250EFF000XXX XT4S250EFF000XXX XT4H250EFF000XXXEkip DIP LSI40XT4N040FFF000XXX XT4S040FFF000XXX XT4H040FFF000XXX60XT4N060FFF000XXX XT4S060FFF000XXX XT4H060FFF000XXX100XT4N100FFF000XXX XT4S100FFF000XXX XT4H100FFF000XXX150XT4N150FFF000XXX XT4S150FFF000XXX XT4H150FFF000XXX225XT4N225FFF000XXX XT4S225FFF000XXX XT4H225FFF000XXX250XT4N250FFF000XXX XT4S250FFF000XXX XT4H250FFF000XXXEkip DIP LSIG40XT4N040GFF000XXX XT4S040GFF000XXX XT4H040GFF000XXX60XT4N060GFF000XXX XT4S060GFF000XXX XT4H060GFF000XXX100XT4N100GFF000XXX X T4S100GFF000XXX XT4H100GFF000XXX150XT4N150GFF000XXX X T4S150GFF000XXX XT4H150GFF000XXX225XT4N225GFF000XXX XT4S225GFF000XXX X T4H225GFF000XXX250XT4N250GFF000XXX XT4S250GFF000XXX XT4H250GFF000XXXEkip DIP LIG40XT4N040CFF000XXX XT4S040CFF000XXX XT4H040CFF000XXX60XT4N060CFF000XXX XT4S060CFF000XXX XT4H060CFF000XXX100XT4N100CFF000XXX X T4S100CFF000XXX XT4H100CFF000XXX150XT4N150CFF000XXX XT4S150CFF000XXX XT4H150CFF000XXX225XT4N225CFF000XXX XT4S225CFF000XXX XT4H225CFF000XXX250XT4N250CFF000XXX XT4S250CFF000XXX XT4H250CFF000XXX U for UL 80% rated or Q for 100% rated  3 for 3-pole or 4 for 4-poleTmax XT, XT4, 250A Frame, Ekip DIP LS/I, LSI, LSIG, and LIG protection trip units with Front TerminalsAmpsL (100kA) V (150kA) X (200kA)U.S. Ordering Code U.S. Ordering Code U.S. Ordering CodeEkip DIP LS/I40XT4L040EFF000XXX XT4V040EFF000XXX XT4X040EFF000XXX60XT4L060EFF000XXX XT4V060EFF000XXX XT4X060EFF000XXX100XT4L100EFF000XXX XT4V100EFF000XXX XT4X100EFF000XXX150XT4L150EFF000XXX XT4V150EFF000XXX XT4X150EFF000XXX225XT4L225EFF000XXX XT4V225EFF000XXX XT4X225EFF000XXX250XT4L250EFF000XXX XT4V250EFF000XXX X T4X250EFF000XXXEkip DIP LSI40XT4L040FFF000XXX XT4V040FFF000XXX XT4X040FFF000XXX60XT4L060FFF000XXX XT4V060FFF000XXX XT4X060FFF000XXX100XT4L100FFF000XXX XT4V100FFF000XXX XT4X100FFF000XXX150XT4L150FFF000XXX XT4V150FFF000XXX XT4X150FFF000XXX225XT4L225FFF000XXX XT4V225FFF000XXX XT4X225FFF000XXX250XT4L250FFF000XXX XT4V250FFF000XXX XT4X250FFF000XXXEkip DIP LSIG40XT4L040GFF000XXX XT4V040GFF000XXX X T4X040GFF000XXX60XT4L060GFF000XXX XT4V060GFF000XXX XT4X060GFF000XXX100XT4L100GFF000XXX XT4V100GFF000XXX XT4X100GFF000XXX150XT4L150GFF000XXX XT4V150GFF000XXX XT4X150GFF000XXX225XT4L225GFF000XXX XT4V225GFF000XXX XT4X225GFF000XXX250XT4L250GFF000XXX XT4V250GFF000XXX XT4X250GFF000XXXEkip DIP LIG40XT4L100CFF000XXX XT4V040CFF000XXX XT4X040CFF000XXX60XT4L150CFF000XXX XT4V060CFF000XXX XT4X060CFF000XXX100XT4L225CFF000XXX XT4V4100CFF000XXX X T4X4100CFF000XXX150XT4L250CFF000XXX XT4V150CFF000XXX XT4X150CFF000XXX225XT4L040CFF000XXX X T4V225CFF000XXX XT4X225CFF000XXX250XT4L060CFF000XXX XT4V250CFF000XXX XT4X250CFF000XXX U for UL 80% rated or Q for 100% rated  3 for 3-pole or 4 for 4-pol—Ordering codes for Tmax XT4Circuit breakers—Tmax XT4 – circuit breaker

Page 46

Distribution circuit breakersTmax XT, XT5 Ekip DIP LS/I, LSI, LSIG, and LIG protection trip units with Front TerminalsFrame Size AmpsN (35kA) S (50kA) H (65kA)U.S. Ordering Code U.S. Ordering Code U.S. Ordering CodeEkip DIP LS/I400250XT5N25AEFF000XXX XT5S25AEFF000XXX XT5H25AEFF000XXX300XT5N30AEFF000XXX XT5S30AEFF000XXX XT5H30AEFF000XXX400XT5N40AEFF000XXX XT5S40AEFF000XXX XT5H40AEFF000XXX600 600XT5N60BEFF000XXX XT5S60BEFF000XXX XT5H60BEFF000XXXEkip DIP LSI400250XT5N25AFFF000XXX XT5S25AFFF000XXX XT5H25AFFF000XXX300XT5N30AFFF000XXX XT5S30AFFF000XXX XT5H30AFFF000XXX400XT5N40AFFF000XXX XT5S40AFFF000XXX XT5H40AFFF000XXX600 600XT5N60BFFF000XXX XT5S60BFFF000XXX XT5H60BFFF000XXXEkip DIP LSIG400250XT5N25AGFF000XXX XT5S25AGFF000XXX XT5H25AGFF000XXX300XT5N30AGFF000XXX XT5S30AGFF000XXX XT5H30AGFF000XXX400XT5N40AGFF000XXX XT5S40AGFF000XXX XT5H40AGFF000XXX600 600XT5N60BGFF000XXX XT5S60BGFF000XXX XT5H60BGFF000XXXEkip DIP LIG400250XT5N25ACFF000XXX XT5S25ACFF000XXX XT5H25ACFF000XXX300XT5N30ACFF000XXX XT5S30ACFF000XXX XT5H30ACFF000XXX400XT5N40ACFF000XXX XT5S40ACFF000XXX XT5H40ACFF000XXX600 600XT5N60BCFF000XXX XT5S60BCFF000XXX XT5H60BCFF000XXX U for UL 80% rated or Q for 100% rated  3 for 3-pole or 4 for 4-poleTmax XT, XT5 Ekip DIP LS/I, LSI, LSIG, and LIG protection trip units with Front TerminalsFrame Size AmpsL (100kA) V (150kA) X (200kA)U.S. Ordering Code U.S. Ordering Code U.S. Ordering CodeEkip DIP LS/I400250XT5L25AEFF000XXX XT5V25AEFF000XXX XT5X25AEFF000XXX300XT5L30AEFF000XXX XT5V30AEFF000XXX XT5X30AEFF000XXX400XT5L40AEFF000XXX XT5V40AEFF000XXX XT5X40AEFF000XXX600 600XT5L60BEFF000XXX XT5V60BEFF000XXX XT5X60BEFF000XXXEkip DIP LSI400250XT5L25AFFF000XXX XT5V25AFFF000XXX XT5X25AFFF000XXX300XT5L30AFFF000XXX XT5V30AFFF000XXX XT5X30AFFF000XXX400XT5L40AFFF000XXX XT5V40AFFF000XXX XT5X40AFFF000XXX600 600XT5L60BFFF000XXX XT5V60BFFF000XXX XT5X60BFFF000XXXEkip DIP LSIG400250XT5L25AGFF000XXX XT5V25AGFF000XXX XT5X25AGFF000XXX300XT5L30AGFF000XXX XT5V30AGFF000XXX XT5X30AGFF000XXX400XT5L40AGFF000XXX XT5V40AGFF000XXX XT5X40AGFF000XXX600 600XT5L60BGFF000XXX XT5V60BGFF000XXX XT5X60BGFF000XXXEkip DIP LIG400250XT5L25ACFF000XXX XT5V25ACFF000XXX XT5X25ACFF000XXX300XT5L30ACFF000XXX XT5V30ACFF000XXX XT5X30ACFF000XXX400XT5L40ACFF000XXX XT5V40ACFF000XXX XT5X40ACFF000XXX600 600XT5L60BCFF000XXX XT5V60BCFF000XXX XT5X60BCFF000XXX U for UL 80% rated or Q for 100% rated  3 for 3-pole or 4 for 4-pole—Ordering codes for Tmax XT5Circuit breakers—Tmax XT5 – circuit breaker

Page 47

—Tmax XT molded case circuit breakersXT5 stocked base breakers N S H LInterupt rating @ 480Vac 35kA 50kA 65kA 100kAIn Ordering code Ordering code Ordering code Ordering codeThermal magnetic adjustable (TMA)300A TMA XT5NU330ABFF000XXX XT5SU330ABFF000XXX XT5HU330ABFF000XXX ---400A TMA XT5NU340ABFF000XXX XT5SU340ABFF000XXX XT5HU340ABFF000XXX ---400A TMA 100% rated XT5NQ340ABFF000XXX --- --- ---600A TMA XT5NU360BBFF000XXX XT5SU360BBFF000XXX XT5HU360BBFF000XXX ---Ekip LS/I trip unit300A LS/I XT5NU330AEFF000XXX --- --- ---400A LS/I XT5NU340AEFF000XXX --- XT5HU340AEFF000XXX ---400A LS/I 100% rated XT5NQ340AEFF000XXX --- XT5HQ340AEFF000XXX ---600A LS/I XT5NU360BEFF000XXX --- XT5HU360BEFF000XXX ---Ekip LSI trip unit400A LSI --- XT5SU340AFFF000XXX XT5HU340AFFF000XXX ---600A LSI --- --- XT5HU360BFFF000XXX ---Molded case switch (MCS)400A MCS --- --- XT5HU340ADFF000XXX ---600A MCS --- --- XT5HU360BDFF000XXX ---Ekip I trip unit400A I XT5NU340AKFF000XXX --- --- XT5LU340AKFF000XXX500A I --- --- --- XT5LU350BKFF000XXX N HInterrupt rating @ 480Vac 35kA 65kAIn Ordering code Ordering codeThermal magnetic adjustable (TMA)800A TMA XT6NU3800BFF000XXX --- --- ---Ekip LS/I trip unit600A LS/I 100%rated XT6NQ3600EFF000XXX --- --- ---800A LS/I XT6NU3800EFF000XXX --- --- ---800A LS/I 100% rated XT6NQ3800EFF000XXX --- XT6HQ3800EFF000XXX ---Molded case switch (MCS)800A MCS --- --- XT6HU3800DFF000XXX ---XT5 400/600A - Fixed (F) - 3poles - ULXT6 800A - Fixed (F) - 3poles - UL* Lugs not included. Please refer to page 31-32 for lug information.

Page 48

—Tmax XT molded case circuit breakersXT5 stocked base breakers S H LInterrupt rating @ 480Vac 35kA 65kA 100KAIn Ordering code Ordering code Ordering codeEkip LSI trip unit800A LSI XT7SU380CFFF000XXX --- XT7HU380CFFF000XXX ---1000A LSI XT7SU310DFFF000XXX --- --- ---1200A LSI XT7SU312EFFF000XXX --- XT7HU312EFFF000XXX ---Ekip I trip unit800A I --- --- --- XT7LU380CKFF000XXX1200A MCS --- --- --- XT7LU312EDFF000XXXXT7 1200A - Fixed (F) - 3poles - UL* Lugs not included. Please refer to page 31-32 for lug information.

Page 49

Distribution circuit breakersTmax XT, XT7 Ekip DIP LS/I, LSI, LSIG, and LIG protection trip units with Front TerminalsFrame Size AmpsS (50kA) H (65kA) L (100kA)U.S. Ordering Code U.S. Ordering Code U.S. Ordering CodeEkip DIP LS/I800 800XT7S80CEFF000XXX XT7H80CEFF000XXX XT7L80CEFF000XXX1000 1000XT7S10DEFF000XXX XT7H10DEFF000XXX XT7L10DEFF000XXX1200 1200XT7S12EEFF000XXX XT7H12EEFF000XXX XT7L12EEFF000XXXEkip DIP LSI800 800XT7S80CFFF000XXX XT7H80CFFF000XXX XT7L80CFFF000XXX1000 1000XT7S10DFFF000XXX XT7H10DFFF000XXX XT7L10DFFF000XXX1200 1200XT7S12EFFF000XXX XT7H12EFFF000XXX XT7L12EFFF000XXXEkip DIP LSIG800 800XT7S80CGFF000XXX XT7H80CGFF000XXX XT7L80CGFF000XXX1000 1000XT7S10DGFF000XXX XT7H10DGFF000XXX XT7L10DGFF000XXX1200 1200XT7S12EGFF000XXX XT7H12EGFF000XXX XT7L12EGFF000XXXEkip DIP LIG800 800XT7S80CCFF000XXX XT7H80CCFF000XXX XT7L80CCFF000XXX1000 1000XT7S10DCFF000XXX XT7H10DCFF000XXX XT7L10DCFF000XXX1200 1200XT7S12ECFF000XXX XT7H12ECFF000XXX XT7L12ECFF000XXX U for UL 80% rated or Q for 100% rated  3 for 3-pole or 4 for 4-poleDistribution circuit breakersTmax XT, XT7 Ekip TOUCH LSI and LSIG, protection trip units with Front TerminalsFrame Size AmpsS (50kA) H (65kA) L (100kA)U.S. Ordering Code U.S. Ordering Code U.S. Ordering CodeEkip TOUCH LSI800 800XT7S80CPFF000XXX XT7H80CPFF000XXX XT7L80CPFF000XXX1000 1000XT7S10DPFF000XXX XT7H10DPFF000XXX XT7L10DPFF000XXX1200 1200XT7S12EPFF000XXX XT7H12EPFF000XXX XT7L12EPFF000XXXEkip TOUCH LSIG800 800XT7S80CQFF000XXX XT7H80CQFF000XXX XT7L80CQFF000XXX1000 1000XT7S10DQFF000XXX XT7H10DQFF000XXX XT7L10DQFF000XXX1200 1200XT7S12EQFF000XXX XT7H12EQFF000XXX XT7L12EQFF000XXX U for UL 80% rated or Q for 100% rated  3 for 3-pole or 4 for 4-pole—Ordering codes for Tmax XT7Circuit breakers—Tmax XT7 – circuit breaker

Page 50

—Tmax XT accessoriesTerminal kits, insulating kits and phase barriersTerminal kits XT1 XT2 XT3 XT4Front terminals KXT1F-3PC KXT2F-3PC KXT3F-3PC K XT4F-3PCFront terminals for MCP KXT1F3PCMCP --- --- ---Extended front terminals KXT1EF-3PC KXT2EF-3PC --- K XT4EF-3PCExtended spread terminals KXT1ES-3PC KXT2ES-3PC KXT3ES-3PC KX T4ES-3PCMulti cable for Cu cables, 6x14-2 AWG KXT1MC-3PC KXT2MC-3PC KXT3MC-3PC KXT4MC-3PCCu cables, 14-1/0 AWG KXT1CU-3PC KXT2CU-3PC --- ---Cu cables MCP, 14-1/0 AWG KXT1CUMCP-3PC --- --- ---CuAl cables, 14-1/0 AWG --- KXT2CUAL1-3PC KXT3CUAL1-3PC K XT4CUAL1-3PCCuAl cables w/Control Tap, 14-1/0 AWG --- --- KXT3CUAL1C-3PC K XT4CUAL1C-3PCFC CuAl terminals for CuAl cables 10-2/0 AWG K XT1CUAL1-3PC KXT2CUAL2-3PC --- ---FC CuAl terminals AuxV for CuAl cables 10-2/0 AWG KXT1CUAL1C-3PC KXT2CUAL2C-3PC --- ---Cu cables, 10-250 kcmil --- --- KXT3CU-3PC K XT4CU-3PCCuAl cables, 4 AWG -300 kcmil --- --- KXT3CUAL2-3PC ---CuAl cables w/Control Tap, 4 AWG-300 kcmil --- --- KXT3CUAL2C-3PC ---CuAl cables, 4 AWG -300 kcmil --- --- --- KXT4CUAL2-3PCCuAl cables w/Control Tap, 4 AWG -300 kcmil --- --- --- K XT4CUAL2C-3PCCuAl cables, 250-350 kcmil --- --- --- KX T4CUAL3-3PCFC CuAl terminals AuxV for CuAl cables 3/0 AWG-350 Kcmil --- --- --- KX T4CUAL3C-3PCInsulating terminal covers XT1 XT2 XT3 XT4LTC low terminal covers KXT1LTC-3 K XT2LTC-3 KX T3LTC-3 K XT4LTC-3HTC high terminal covers KXT1HTC-3 KXT2HTC-3 KXT3HTC-3 KXT4HTC-3Phase barriers XT1 XT2 XT3 XT4PB height 25mm/0.98in KXTBPB25-3 KXTCPB25-3 KXTBPB25-3 KXTCPB25-3PB height 100mm/3.94in KXTBPB100-3 KXTCPB100-3 KXTBPB100-3 KXTCPB100-3PB height 200mm/7.87in KXTBPB200-3 KXTCPB200-3 KXTBPB200-3 KXTCPB200-3Din Rails KXT1EDIN-3

Page 51

Terminal kits XT5 XT6 XT7Front terminals KXT5F-3PC KXT6F-3PC ---Front terminals for MCP --- --- ---Extended front terminals KXT5EF-3PC KXT6EF-3PC ---FC CuAl 1x6AWG-350kcmi KXT5CUAL350K-3PC --- ---FC CuAl 1x250-500kcmil KXT5CUAL500K-3PC --- ---FC CuAl 1x500kcmil AuxV K KXT5CUAL500KC-3PC --- ---FC CuAl 2x250-500kcmil KXT5CUAL2X500K-3PC KXT6CUAL2X500K-3PC ---FC CuAl 2x500kcmil AuxV KXT5CUAL2X500KC-3 KXT6CUAL2X500KC-3 ---FC CuAl 3x2/0AWG-400kcmil --- KXT6CUAL3X400K-3PC ---FC CuAl 3x400kcmil AuxV --- KXT6CUAL3X400KC-3 ---FC CuAl 4x4/0 AWG – 500 kcmil --- --- KXT7CUAL4X500K-3PCFC CuAl 3x500-750kcmil --- --- KXT7CUAL3X750KC-3Insulating terminal covers XT5 XT6 XT7LTC low terminal covers K XT5LTC-3 K XT6LTC-3 ---HTC high terminal covers KXT5HTC-3 KXT6HTC-3 KXT7HTC2pcs-3HTC_BS High terminal covers with back shield KXT5HTCBS-3 --- ---Phase barriers XT5 XT6PB height 25mm/0.98in KXT5PB25UL-3 ---PB height 100mm/3.94in KXT5PB100UL-3 KXT6PB100UL-3PB height 200mm/7.87in KXT5PB200UL-3 KXT6PB200UL-3PS – Rear phase separators for FP KXT5PBFP-3 ---Cable Rack KXTFACCRCK KXTFACCRCK—Tmax XT accessoriesTerminal kits, insulating kits and phase barriersKXT5CUAL2X750KC-32X500-750MCM

Page 52

—Circuit Breaker Enclosures

Page 53

Type 1, Indoor Surface or Flush MountingProduct Features - Suitable for use as service equipment (SE) as noted. - 60°C/75°C conductor ratings - Short circuit ratings are equal to the rating of the installed breaker. To order enclosed or accessorized circuit breakers, a configurator is available at: empower.abb.comNEMA Type 1Certifications Product NumberFor 3P4W EnclosuresFor Enclosures with Ground Fault ProtectionMax. Ampere RatingFrame TypeNo. ofPolesULSEcULcULSE¹Flush SurfaceSurface,Blank End Wall²Neutral Product NumberNeutral Product Number³Neutral Sensor for Ground FaultTHQL, TXQL, THQL-GF • • - 44- Included - -THQL, TXQL, THQL-GF • • - 44- Included - - THQL  • • -   - Included - -THQC, THHQC, TXQC • • - 44- Included - -   • • •   - Included - -THED, TED, TEB • • -    Included - - THED, TED • • -  - -Included - -• • • -     • • •   - Included - -   • • •   - 5   • • •   - Included - -—Circuit Breaker EnclosuresNEMA Type 11 cUL Listed - Suitable for use as service equipment.2 Enclosures with blank end walls (no Knockouts) and a feature to adjust the instantaneous setting on Spectra Circuit breakers.3 Neutral for ground fault required to mount neutral sensor in enclosure.45 For 250A rating, use copper cable only.(Table continued on next page.)

Page 54

—Circuit Breaker EnclosuresNEMA Type 1NEMA Type 1Certifications Product NumberFor 3P4W EnclosuresFor Enclosures with Ground Fault ProtectionMax. Ampere RatingFrame TypeNo. ofPolesULSEcULcULSE¹Flush SurfaceSurface,Blank End Wall²Neutral Product NumberNeutral Product Number³Neutral Sensor for Ground Fault   • • •   - (Touch)   • • •   -(Touch)    • • •   -     • • •   -   1 cUL Listed - Suitable for use as service equipment.2 Enclosures with blank end walls (no Knockouts) and a feature to adjust the instantaneous setting on Spectra Circuit breakers. 3 Neutral for ground fault required to mount neutral sensor in enclosure.4 For 250A rating, use copper cable only.* 1200A Circuit Breaker enclosure code requirements may require Relt. Consult with an ABB representative before quoting.(continued)

Page 55

Type 3R, Outdoor, RaintightProduct Features - Suitable for use as service equipment (SE) as noted. - 60°C/75°C conductor ratings - Short circuit ratings are equal to the rating of the installed breaker. To order enclosed or accessorized circuit breakers, a configurator is available at: empower.abb.comNEMA Type 3R CertificationsFor 3P4W EnclosuresFor Enclosures with Ground Fault ProtectionMax. Ampere RatingFrame TypeNo. ofPolesULSEcULcULSE1Product Number5Neutral Product NumberNeutral Product Number2Neutral Sensor for Ground Fault THQL, TXQL, THQL-GF  • - - Included - - THQL, TXQL, THQL-GF  • - - Included - - THQL  • - -  Included - - THQC, THHQC, TXQC  • - - Included - -   • • •  Included - -   • • •  Included - - THED, TED, TEB  • • •  Included - -   • • •  Included - -   • • •   THED, TED  • • •  Included - -   • • •  Included - -   • • •      • • •    • • •      • • •    —Circuit Breaker EnclosuresNEMA Type 3R 1 cUL Listed - Suitable for use as service equipment.2 Neutral for ground fault required to mount neutral sensor in enclosure.34 For 250A rating, use copper cable only.5 100-250A devices have removable closing cap. Larger ampere devices require field cut openings. Order hubs separately. See page 7-10.* 1200A Circuit Breaker enclosure code requirements may require Relt. Consult with an ABB representative before quoting.

Page 56

—Circuit Breaker EnclosuresNEMA Type 3R NEMA Type 3R (continued)CertificationsFor 3P4W EnclosuresMax. Ampere RatingFrame TypeNo. ofPolesULSEcULcULSE1Product Number2Neutral Product NumberNotes THQL, TXQL, THQL-GF  • • - Included    • • •  Included    • • •  Included    • • • Included    • • • Included 1 cUL Listed - Suitable for use as service equipment.2 100-250A devices have removable closing cap. Larger ampere devices require field cut openings. Order hubs separately. See page 7-10. 34 Service rated equipment only.

Page 57

Product Features - Suitable for use as service equipment (SE) as noted. - 60°C/75°C conductor ratings - Short circuit ratings are equal to the rating of the installed breaker. To order enclosed or accessorized circuit breakers, a configurator is available at: empower.abb.comNEMA Type 12Certifications Product NumberFor 3P4W EnclosuresFor Enclosures with Ground Fault ProtectionMax. Ampere RatingFrame TypeNo. ofPolesULSEcULcULSE1With Knock OutsWithout Knock OutsNeutral Product NumberNeutral Product Number2Neutral Sensor for Ground Fault THED, TED, TEB  • • •   Included - -   • • • -  Included - -   • • • -     • • • -  Included - -   • • • -      • • • -      • • • -      • • • -    1 cUL Listed - Suitable for use as service equipment.2 Neutral for ground fault required to mount neutral sensor in enclosure. 3 For 250A rating, use copper cable only.* 1200A Circuit Breaker enclosure code requirements may require Relt. Consult with an ABB representative before quoting.Type 12,Rotary Handle Integral with Breaker—Circuit Breaker EnclosuresNEMA Type 12

Page 58

Product Features - Suitable for use as service equipment (SE) as noted. - 60°C/75°C conductor ratings - Short circuit ratings are equal to the rating of the installed breaker. To order enclosed or accessorized circuit breakers, a configurator is available at: empower.abb.comNEMA Type 4/4X CertificationsFor 3P4W EnclosuresFor Enclosures with Ground Fault ProtectionMax. Ampere RatingFrame TypeNo. ofPolesULSEcULcULSE1Product NumberNeutral Product NumberNeutral Product Number2Neutral Sensor for Ground Fault THED, TED, TEB  • • •   - -   • • •  Included - -   • • •     • • •  Included - -   • • •     • • •      • • •      • • •    1 cUL Listed - Suitable for use as service equipment.2 Neutral for ground fault required to mount neutral sensor in enclosure. 3 For 250A rating, use copper cable only.* 1200A Circuit Breaker enclosure code requirements may require Relt. Consult with an ABB representative before quoting.Type 4/4X,—Circuit Breaker EnclosuresNEMA Type 4/4X

Page 59

—Disconnects and Safety Switches

Page 60

TG4322TH3361SSTC10323RTDT3362—Spec-Setter™ safety switchesQuick selection guideGeneral duty safety switch short circuit ratingsMaximum System VoltageAmpere RatingUL Listed FusingEnclosure TypeClass Withstand Ratings (rms Sym Amps)FusibleK H RNon-Fusible: Fuse withstand ratings apply to non-fused switches when protected by an upstream fuse as listed or with upstream circuit Any other protective device K upstream H upstream R upstream Heavy duty safety switch short circuit ratingsMaximum System VoltageAmpere RatingUL Listed FusingEnclosure TypeClass Withstand Ratings (rms Sym Amps)FusibleH R J LNon-Fusible: Fuse withstand ratings apply to non-fused switches when protected by an upstream fuse as listed or with upstream circuit Any other protective deviceH upstream R upstream J upstream L upstream Double throw safety switch short circuit ratingsMaximum System VoltageAmpere RatingUL Listed FusingEnclosure TypeClass Withstand Ratings (rms Sym Amps)Fusible  R J T L Non-Fusible: Fuse withstand ratings apply to non-fused switches when protected by an upstream fuse as listed   When protected with fuses 123 Unless otherwise noted on the enclosure4 For 800A and 1200A only when protected with upstream fuses

Page 61

Heavy Duty Safety Switches240V Fusible - Heavy Duty - 3 Pole600V Fusible - Heavy Duty - 3 Pole

Page 62

Heavy Duty Safety Switches240V Fusible - Heavy Duty - 3 Pole

Page 63

1 800A and 1200A non-double throw safety switches also use the C Duty Level nomenclature—Spec-Setter™ safety switchesQuick selection guideT N3 61R DCH 3GE IdentificationFusing N= Non-Fusible T= Fusible Double Throw Blank= FusedNumber of Wires 2, 3, 4, 6 Ampere Rating 1= 30A 2= 60A 3= 100A 4= 200A 5= 400A 6= 600A 7= 800A 8= 1200ADuty Level H= Heavy Duty G= General Duty C= Non-Fusible Double Throw1 D= Fusible Double ThrowMaximum Voltage 2= 240V, 6= 600VEnclosure Type Blank= NEMA 1 R= NEMA 3R SS= NEMA 4/4X Stainless Steel Type 304 SS316= NEMA 4/4X Stainless Steel Type 316 J= NEMA 5/12Number of Poles 2, 3, 6 Other Features B= Bottom Feed (240V, TH, Type 1, 200-600A) CL= Copper Lug DC= 600V DC Max F= Farm Switch VW= Viewing Window Option VRED= Red PaintAll ABB Spec-Setter safety switches carry the following certifications: - UL Listed and cUL Listed  - Federal Specification WS-865C - NEMA Enclosed Safety Switch Standard KS1-2013 - Seismic Certified -  Horsepower ratedAll Spec-Setter safety switches are horsepower rated with the following exceptions: - 800A single throw type TC switches - 1200A single and double throw type TC and TDT switchesProduct referencesLug wire sizes Safety switch dimensions, weights, knock out locations, drawings and HP ratings Series rating information Seismic information *1200A Switch code require-ments may require relt. Consultwith an ABB representative be-fore quoting.

Page 64

DutyVoltage Fusing Poles AmperageEnclosure TypeHeavy Duty240VACFusible2 30A, 60A, 100A, 200ANEMA 1 - IndoorNEMA 3R - OutdoorNEMA 5/12 - Dust TightNEMA 3R/5/12 - Dust & Drip TightNEMA 4X - 304 Stainless SteelNEMA 4X - 316 Stainless Steel3 30A, 60A, 100A, 200ANon-fused 3 30A, 60A, 100A, 200A600VACFusible 3 30A, 60A, 100A, 200ANon-fused 3 30A, 60A, 100A, 200A600VDCFusible 2 30A, 60A, 100ANon-fused 2 30A, 60A, 100A —Explore the Range —Catalog Numbering SystemIdentificationT H N 3 3 6 1 R VW1800 A and 1200 A non-double throw safety switches also use the C nomenclatureNote: This information is provided for interpreting numbers. It should not be used to build product numbers.FusingN Non-fusibleT Fusible double throwBlank FusedNumber of-wires2, 3, 4, 6Ampere rating1 30 A2 60 A3 100 A4 200 ADuty levelH Heavy dutyG General dutyC Non-fusible double throw1D Fusible double throwMaximum voltage2 240 V6 600 VEnclosure typeBlank NEMA 1R NEMA 3RSS NEMA 4/4X stainless steel type 304SS316 NEMA 4/4X stainless steel type 316J NEMA 5/12Number of-poles2, 3, 6Other featuresB Bottom feed (240 V, TH, type 1, 200–600 A)DC 600 V DC max.F Farm switchVW Viewing window optionVRED Painted redThe viewing window is a polished surface, UV stabilized, polycarbonate product. A flame-retardant grade that meets UL 94, high-temperature resistance, and high clarity properties. It has been impact and strength tested. It has not been approved for use with infrared thermography.—Viewing Window

Page 65

—AC disconnect, NEMA type 3R30-60 amperes240 volts AC 50/60 HzUL/CUL listedSteel disconnects N3R outdoor enclosureAmperage RatingProduct Number HP RatingStandard Fuse Class15A GFCI Outlet Height Width DepthStandard PackageReplacement PullerFusibleNEUT.BONDED    –         –     Non-FusibleGROUNDEQUIP   –FactoryInstalled       –     Non-Automatic   –FactoryInstalled    - –     -Plastic disconnects N3R outdoor enclosureAmperage RatingProduct Number HP RatingStandard Fuse ClassRemovableClosing cap Height Width DepthStandard PackageReplacement PullerFusibleNEUT.BONDED    Yes        H Yes     Non-FusibleGROUNDEQUIP   – Yes        – No     Non-Automatic – No     –TF30R TF60R TFN60RGFR TPN60R

Page 66

—Dry Type Transformers

Page 67

—General purposeSingle-phase DOE 2016 and NRCan efficiencyCommon transformersGE by ABB's general purpose single-phase dry type transformers are step-down transformers designed for installations that require a 3-wire secondary voltage for 120/240 V systems. These units can also be used in 2-wire, 120x240 V applications. Their primary voltages are 240x480. Optional wall mount brackets are available for most models. lug kit and copper ground bar are included. Aluminum windings 150 °C Rise NEMA 2Primary VoltageSecondary VoltagekVATaps (FCBN,FCAN; %)Wiring Diagram1Product Net Weight (lbs.)FrameSizeCatalogNumber                                  Copper windings 150 °C Rise NEMA 2Primary VoltageSecondary VoltagekVATaps (FCBN,FCAN; %)Wiring Diagram1Product Net Weight (lbs.)FrameSizeCatalogNumber                             ¹ See page 10A-45 and 10A-46 for wiring diagrams.Technical characteristics • Connection: 3-wire or 2-wire secondaries• Voltages: (P) 240x480 (S) 120/240•  IEC 60085 Class R• Frequency: 60 Hz• • Standard single-phase tap arrangement• Painted, ANSI #61 gray NEMA 2 enclosure• Type QL• Audible sound level: NEMA ST-20 Standard• Seismic qualifications – CBC 2019 and IBC 2018; ASCE 7.05-2016• UL 1561• UL & cUL listed (XQNX, XQNX7:E323777)• Energy efficiency: DOE 2016 (10 CFR Part 431)• Energy efficiency: NRCan (CSA 802.2)• UL energy verification – for US and Canada (ZXPC:EV519886) (ZZED:EV23760)Type QL Transformer

Page 68

3-Phase Common VoltagesSeries Primary Voltage Secondary Voltage                                                                                                                          3-Phase Common VoltagesSeries Primary Voltage Secondary Voltage                                                                                                                                  3-Phase Common VoltagesSeries Primary Voltage Secondary Voltage                                                                                                   —General purposeThree-phaseDOE 2016 catalog number nomenclatureABB Standard1 = QL DOE 2016 DesignTransformer TypeOptionsA = Aluminum CoilB = Aluminum C&C (no enclosure)C = Copper CoilS = AL Stainless Steel EnclosureV = Copper C&C (no enclosure)Z = CU Stainless Steel EnclosureY = AccessorieskVA RatingCatalog No. Suffix CodesCore & Coil Temp Rise150 C 115 C 80 CCore & Coil CharacteristicsTemp Rise Rating Only   -3 dB noise reduction   Electrostatic Shield*   -3 dB noise reduction + Electrostatic Shield  -5 dB noise reduction   -5 dB noise reduction + Electrostatic Shield  * An Electrostatic Shield (a Guard I transformer) is bonded to the ground terminal and is a copper Voltage SeriesSee Voltage Chart below9T 1 0 A 1 G311001These options are UL recognized components.Please Note: This catalog number nomenclature is for illustrative purposes only. Not all catalog number combinations are available for production. Please reference the ordering tables beginning on page 10A-12 for Three-phase DOE 2016 Efficiency transformers currently available for ordering. For additional assistance, please contact your ABB Account Manager.* Standard factory lug kits are included with150KVA transformers and below

Page 69

—General purposeAluminum coilThree-phase DOE 2016 efficiencyK = 1 150°C Rise NEMA 2InputVoltageOutputVoltagekVA TapsWiringDiagram No.¹Approx. NetWeight (Lbs)FrameSizeCatalogNumber                                              K = 1 115°C Rise NEMA 2InputVoltageOutputVoltagekVA TapsWiringDiagram No.¹Approx. NetWeight (Lbs)FrameSizeCatalogNumber                                              K = 1 80°C Rise NEMA 2InputVoltageOutputVoltagekVA TapsWiringDiagram No.¹Approx. NetWeight (Lbs)FrameSizeCatalogNumber                                            -  K = 1 150°C Rise NEMA 2InputVoltageOutputVoltagekVA TapsWiringDiagram No.¹Approx. NetWeight (Lbs)FrameSizeCatalogNumber                                         ¹ See page 10A-45 and 10A-46 for wiring diagrams.Type QL Transformer

Page 70

—General purposeAluminum coilThree-phase DOE 2016 efficiencyK = 1 150°C Rise NEMA 2InputVoltageOutputVoltagekVA TapsWiringDiagram No.¹Approx. NetWeight (Lbs)FrameSizeCatalogNumber                                         K = 1 150°C Rise NEMA 2InputVoltageOutputVoltagekVA TapsWiringDiagram No.¹Approx. NetWeight (Lbs)FrameSizeCatalogNumber                                              K = 1 150°C Rise NEMA 2InputVoltageOutputVoltagekVA TapsWiringDiagram No.¹Approx. NetWeight (Lbs)FrameSizeCatalogNumber                                              K = 1 150°C Rise NEMA 2InputVoltageOutputVoltagekVA TapsWiringDiagram No.¹Approx. NetWeight (Lbs)FrameSizeCatalogNumber                                              K = 1 150°C Rise NEMA 2InputVoltageOutputVoltagekVA TapsWiringDiagram No.¹Approx. NetWeight (Lbs)FrameSizeCatalogNumber                                              ¹ See page 10A-45 and 10A-46 for wiring diagrams.

Page 71

—General purposeCopper coilThree-phase DOE 2016 efficiencyK = 1 150°C Rise NEMA 2InputVoltageOutputVoltagekVA TapsWiringDiagram No.¹Approx. NetWeight (Lbs)FrameSizeCatalogNumber                                         K = 1 150°C Rise NEMA 2InputVoltageOutputVoltagekVA TapsWiringDiagram No.¹Approx. NetWeight (Lbs)FrameSizeCatalogNumber                               K = 1 150°C Rise NEMA 2InputVoltageOutputVoltagekVA TapsWiringDiagram No.¹Approx. NetWeight (Lbs)FrameSizeCatalogNumber                                              K = 1 115°C Rise NEMA 2InputVoltageOutputVoltagekVA TapsWiringDiagram No.¹Approx. NetWeight (Lbs)FrameSizeCatalogNumber                                         K = 1 80°C Rise NEMA 2InputVoltageOutputVoltagekVA TapsWiringDiagram No.¹Approx. NetWeight (Lbs)FrameSizeCatalogNumber                                         ¹ See page 10A-45 and 10A-46 for wiring diagrams.

Page 72

58

Page 73

Page 74

— SINGLE PHASE TRANSFORMERSelectrification.us.abb.comGIZ-1345E 9/19kVA RatingFull-load Current - in Amperes at the Line-to-Line Voltages Listed Below120V 240V 480V 600V0.5 4.16 2.08 1.04 0.831 8.33 4.16 2.08 1.662 16.66 8.33 4.16 3.333 25.00 12.50 6.25 5.005 41.66 20.83 10.41 8.337.5 62.50 31.25 15.62 12.5010 83.33 41.66 20.83 16.6615 125.00 62.50 31.25 25.0025 208.33 104.16 52.08 41.6637.5 312.50 156.25 78.12 62.5050 416.66 208.33 104.16 83.3375 625.00 312.50 156.25 125.00100 833.33 416.66 208.33 166.66167 1391.66 695.83 347.91 278.33KVA = (FLA X LINE V) ÷ 1000 UL Listed to 600Velectrification.us.abb.comGIZ-1345E 9/19kVA RatingFull-load Current - in Amperes at the Line-to-Line Voltages Listed Below208V 240V 480V 600V3 8.32 7. 21 3.60 2.886 16.65 14.43 7.21 5.779 24.98 21.65 10.82 8.6615 41.63 36.08 18.04 14.4330 83.27 72.16 36.08 28.8645 124.90 108.25 54.12 43.3075 208.17 180.42 90.21 72.16112.5 312.26 270.63 135.31 108.25150 416.35 360.84 180.42 144.33225 624.53 541.26 270.63 216.50300 832.71 721.68 360.84 288.67500 1387.86 1202.81 601.40 481.12750 2081.79 1804.21 902.10 721.681000 2775.72 2405.62 1202.81 962.25KVA = (FLA X LINE V X 1.732) ÷ 1000 UL Listed and CSA Certified to 600V— THREE PHASE TRANSFORMERS

Page 75

—Lighting contactors

Page 76

—CR460 componentsBasic contactorCombined with other appropriate components, basic contactors allow configuration into any available electrically or mechanically held model. Includes two power poles.Contact configuration Product number  assembled contactor with no additional auxiliary contacts, pilot devices, pilot lights, control circuit fuses or CPTs.Coil voltageAC, 60Hz AC, 50Hz Electrically held Mechanically held Coil digit  • • C  • • D115-120V 110V • • J - • • L  • • S277V 240V • • N - •T  •U  •Y1Control module switching device rated 277V max; use CPT for higher voltagePower polesCR460 series basic contactors accept up to 6 single- or double-pole power poles. These can be used to form up to: - 12 NO poles when 6 double-poles are used in the NO positions (1-6) or - 8 NC poles with 4 double-poles in the NC positions (1-4) + NO poles with 2 double-poles in the 2 NO positions (5-6)Type Product numberSingle pole Double pole Packaged individually and overpacked in multiple of 5.Conversion kits for mechanically held contactorsKits for converting electrically held contactors to a mechanically held version. Kits include control module, latch, latch cover and auxiliary contact(s) plus installation instructions. Conversion kits are suitable for coil voltages 277V and below. Use CPT to reduce coil voltage if line voltage is higher than 277V.Coil voltage rangeControl circuit wiringAuxiliary contacts1Control circuit voltageProduct number                                1Auxiliary contact block required for feedback loop, alternate 2 pole blocks may be required for status feedback and/or pilot lights. See fuse and transformer kits table on page 3-11 for CPT selection. See wiring diagrams on page 3-23.CR463L - basic contactor

Page 77

—CR460 componentsAuxiliary contactsEach contactor may use one single or one double auxiliary contact block on eacch side of the base. When installed on the left side the contacts are NO, when installed on the right side the contacts are NC. This allows a total of 2NO +2NC contacts maximum.Type Product numberSingle pole Double pole See additional auxiliary contacts tables on pages 3-15 and 3-19 for contact selection data.Spare coilsCoil voltage @ 60Hz Coil voltage @ 50Hz Product number       -      -     

Page 78

2CR463L1A3 4 5 6 7 8 9—CR463LModified assembled forms - electrically heldCR463L Electrically held contactorsFollow the diagram and tables below to select the options and corresponding product number digits for your modified contactor.1: NO power pole contact configuration       1For digit 1 with 10 NO contactsuse B; for 11 NO contacts, useC; for 12 NO contacts, use D.2: NC power pole contact configuration      3: Standard controlA 4: Coil voltageAC, 60Hz AC, 50Hz Digit 4  C  D  J - L  S  N - T  U  Y5: Additional auxiliary contactsAdditional(field use)auxiliarycontactsDigit 5(aux)OpentypeEnclosed with pilot device codes Enclosed with pilot device codes(Digit 7) 0. 2, 4, 5, 6, 7, 8 below (Digit 7) 1, 3 belowNo pilotdevicesor pilotlightsDigit 8=AON light across coil Digit 8=B,DOFF light thru NC contact Digit 8=C,EON light across coil and OFF light thru NCcontact Digit 8=F,GNo pilot devices or pilot lightsDigit 8=AON light across coil Digit 8=B,DOFF lightthru NC contactDigit 8=C,EON light across coil and OFF light thru NCcontact Digit 8=F,GNone A• • • • • • • • • B• • • • • • • • • C• • • • • • • • • D• • • • • • • • • E• • • • • - - - - F• • • • • - - - - G• • • - - • • - - H• • • - - • • - - J• • • - - - - - -Each side of the contactor base will accept one single- or double-pole auxiliary contact block, for a maximum of 2NO-2NC contacts. Enclosures with OFF pilot lights require 1NC contact. Specify an additional 1NO contact if a holding interlock is required and "not" selected as part of Digit 7 (1 or 3). For open forms, this is the final digit.

Page 79

2CR463L1A3 4 5 6 7 8 9—CR463LModified assembled forms - electrically held (continued)CR463L Electrically held contactorsFollow the diagram and tables below to select the options and corresponding product number digits for your modified contactor.7: Pilot devicesPilot deviceHolding interlockDigit 7Not requiredIncluded2None- -ON/OFF push button (momentary)- •ON/OFF selector switch (maintained)• -ON/OFF selector switch, spring return tocenter (momentary)- •H-O-A selector switch (maintained)• -ON/OFF/AUTO keyed selector switch(removal all positions) (maintained)• -H-O-A keyed selector switch (removal allpositions) (maintained)• -OFF/AUTO selector switch (maintained)• -ON/OFF/AUTO selector switch(maintained)• -2One holding interlock is included in pilot device digit and pricing.Heavy-duty, 30mm pilot devices. Contactor supplied in oversize enclosures with these options. Not available in Type 1 flush enclosure.8: Pilot lightsType Pilot light(s) Digit 8– None AStandardON BOFF CON and OFF FPush-to-testON DOFF EON and OFF G3ON is across coil; OFF is through NC contact, which is included in pilot light digit and pricing.Heavy-duty 30mm pilot lights with interchangeable red and green lenses. Seethe additional auxiliary contacts table above for contact limitations. OFF light includes extra auxiliary contact. Not available in Type 1 flush enclosure.6: EnclosuresEnclosure type Digit 6     9: Control circuit fuses/control power transformersContactor type Description Digit 9– None Without CPT Control circuit fuses CPT primaryvoltsCPT secondaryvoltsB C D E FL M N P R S4Contactor supplied in oversize enclosure with these options.

Page 80

2CR463M13 4 5 6 7 8 9—CR463MModified assembled forms - mechanically heldCR463M Mechanically held contactorsFollow the diagram and tables below to select the options and corresponding product number digits for your modified contactor.1: NO power pole contact configuration       1For digit 1 with 10 NO contacts use B; for 11 NO contacts, use C; for 12 NO contacts, use D.2: NC power pole contact configuration       3 & 4: Control circuitControlControl module inputDigits 3 & 4 by coil voltage (60Hz)224 VAC 115-120 VAC 200-208 VAC 230-240 VAC 277 VAC BC BJ BL BS BN CC CJ CL CS CN DC DJ DL DS DN EC EJ EL ES EN MC MJ ML MS MN NC NJ NL NS NN PC PJ PL PS PN RC RJ RL RS RN2For 50Hz coil ratings see coil table, page 3-9.If coil supply voltage is greater than 277V, use CPT.5: Additional auxiliary contactsAdditional(field use)auxiliarycontactsDigit 52-wire control (when Digit 3 = B, C, D, E) 3-wire control (when Digit 3 = M, N, P, R)Open typeEnclosed (when Digit 7 = 0, 2, 4, 5, 6, 7, 8)Open typeEnclosed (when Digit 7 = 1, 2, 3)No pilotlightsDigit 8=AON light thru NO contact Digit 8=B,DOFF light thru NC contact Digit 8=C,EON light thru NO contact and OFF light thru NC contact Digit 8=F,GNo pilot devices or pilot lightsDigit 8=AON light thru NO contact Digit 8=B,DOFF lightthru NC contactDigit 8=C,EON light thru NO contact and OFF light thru NC contact Digit 8=F,GNone A• • • • • • • • • • B• • • • • • • - • - C• • • - - • • • - - D• • • - - • • - - - E• • - • - - - - - -Each side of the contactor base will accept one single- or double-pole auxiliary contact block, for a maximum of 2NO-2NC contacts. The 2-wire control module uses 1NC contact and the 3-wire uses 1NO-1NC for feedback and control. The table above indicates the additional auxiliary contacts available for customer or field use when factory-assembled forms are supplied. For open forms, this is the final digit.

Page 81

2CR463M13 4 5 6 7 8 9—CR463MModified assembled forms - mechanically held (continued)CR463M Mechanically held contactorsFollow the diagram and tables below to select the options and corresponding product number digits for your modified contactor.7: Pilot devicesPilot deviceControl moduleDigit 72-wire 3 wireNone- -ON/OFF push button (momentary)- •ON/OFF selector switch (maintained)• •ON/OFF selector switch, spring return tocenter (momentary)- •H-O-A selector switch (maintained)• -ON/OFF/AUTO keyed selector switch(removal all positions) (maintained)• -H-O-A keyed selector switch (removal allpositions) (maintained)• -OFF/AUTO selector switch (maintained)• -ON/OFF/AUTO selector switch(maintained)• -Heavy-duty, 30mm pilot devices. Oversize enclosure required for field installed pilot devices, pilot lights and control power transformers. Not available in Type 1 flush enclosure.8: Pilot lightsType Pilot light(s)3Digit 8– None AStandardON BOFF CON and OFF FPush-to-testON DOFF EON and OFF G3Contactor supplied in oversize enclosure with these options. ON is through NO contact; OFF is through NC contact. Auxiliary contacts are included in pilot light digit.Heavy-duty 30mm pilot lights with interchangeable red and green lenses. See the additional auxiliary contacts table above for contact limitations. OFF light includes extra auxiliary contact. Not available in Type 1 flush enclosure.6: EnclosuresEnclosure type Digit 6     9: Control circuit fuses/control power transformersContactor type Description Digit 9– None Without CPT Control circuit fuses CPT primaryvoltsCPT secondaryvoltsB C D E FL M N P R S4Oversize enclosure required for field installed pilot devices, pilot lights and control power transformers.CPT secondary voltage must match control voltage. Not available in Type 1 flush enclosure.

Page 82

—Surge Protection Devices

Page 83

—ABB ME seriesWallmount SPDVoltage Configuration Product Number240/120 1-phase, 3-wire + ground TME120SxxxWMN208Y/120 3-phase, 4-wire + ground TME120YxxxWMN380Y/220 3-phase, 4-wire + ground TME220YxxxWMN240 Delta 3-phase, 3-wire + ground TME240DxxxWMN240/120 Hi-Leg Delta 3-phase, 4-wire + ground TME240HxxxWMN415Y/240 3-phase, 4-wire + ground TME240YxxxWMN4 8 0Y/277 3-phase, 4-wire + ground TME277YxxxWMN60 0Y/3 47 3-phase, 4-wire + ground TME347YxxxWMN480 Delta 3-phase, 3-wire + ground TME480DxxxWMNDesired kA xxx Code65 06580 080100 100T M E W M NProduct #Nominal Voltage (Volts RMS)System Voltage ConfigurationVoltage Protection Rating (VPR) UL 1449 4th Edition September 2014 RevisionMCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L HL-L120S 120/240 1 Ph, 3 W + G 1000 - 1000 - 700 1200 - 125%120Y 120Y/208 3 Ph, 4 W + G 1000 - 1000 - 700 1200 - 125%220Y 220Y/38 0 3 Ph, 4 W + G 1500 - 1500 - 1000 2000 - 145%240D 240 Delta 3 Ph, 4 W - - 1500 - - 1800 - 196%240H120/240 Delta HL3 Ph, 4 W + G 1000 1500 1000 1500 700 1200 2500 115%240Y 240Y/415 3 Ph, 4 W + G 1500 - 1500 - 1000 2000 - 130%277Y 277 Y/48 0 3 Ph, 4 W + G 1500 - 1500 - 1000 2000 - 115%347Y 3 47 Y/6 0 0 3 Ph, 4 W + G 1800 - 1500 - 1500 2500 - 115%480D 480 Delta 3 Ph, 4 W - - 2000 - - 4000 - 198%Maximum Surge Current CapacityExposure LevelPer Mode Per Phase065 ME 65kA 130kA080 ME 80kA 160kA100 ME 100kA 200kAProduct # ExampleTME277Y150WMN4SSuffix DescriptionNEMA EnclosureMounting Disconnect4S Painted Steel 4 Surface No4X Stainless Steel 4X Surface No

Page 84

—ABB HE seriesWallmount SPDVoltage Configuration Product Number240/120 1-phase, 3-wire + ground THE120SxxxWMN208Y/120 3-phase, 4-wire + ground THE120YxxxWMN380Y/220 3-phase, 4-wire + ground THE220YxxxWMN240 Delta 3-phase, 3-wire + ground THE240DxxxWMN240/120 Hi-Leg Delta 3-phase, 4-wire + ground THE240HxxxWMN415Y/240 3-phase, 4-wire + ground THE240YxxxWMN4 8 0Y/277 3-phase, 4-wire + ground THE277YxxxWMN60 0Y/3 47 3-phase, 4-wire + ground THE347YxxxWMN480 Delta 3-phase, 3-wire + ground THE480DxxxWMN600 Delta 3-phase, 3-wire + ground THE600DxxxWMNDesired kA xxx Code125 125150 150200 200300 300T H E W M NProduct #Nominal Voltage (Volts RMS)System Voltage ConfigurationVoltage Protection Rating (VPR) UL 1449 4th Edition September 2014 RevisionMCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L HL-L120S 120/240 1 Ph, 3 W + G 1000 - 1000 - 700 1200 - 125%120Y 120Y/208 3 Ph, 4 W + G 1000 - 1000 - 700 1200 - 125%220Y 220Y/38 0 3 Ph, 4 W + G 1500 - 1500 - 1000 2000 - 145%240D 240 Delta 3 Ph, 4 W - - 1500 - - 1800 - 196%240H120/240 Delta HL3 Ph, 4 W + G 1000 1500 1000 1500 700 1200 2500 115%240Y 24 0Y/415 3 Ph, 4 W + G 1500 - 1500 - 1000 2000 - 130%277Y 27 7 Y/4 8 0 3 Ph, 4 W + G 1500 - 1500 - 1000 2000 - 115%347Y 3 47 Y/6 0 0 3 Ph, 4 W + G 1800 - 1500 - 1500 2500 - 115%480D 480 Delta 3 Ph, 4 W - - 2000 - - 4000 - 198%Maximum Surge Current CapacityExposure LevelPer Mode Per Phase125 HE 125kA 250kA150 HE 150kA 300kA200 HE 200kA 400kA250 HE 250kA 500kA300 HE 300kA 600kAProduct # ExampleTHE277Y150WMN4SSuffix DescriptionNEMA EnclosureMounting Disconnect4S Painted Steel 4 Surface No4X Stainless Steel 4X Surface No

Page 85

—ABB ME seriesWallmount SPD with enhanced thermal protectionVoltage Configuration Product Number240/120 1-phase, 3-wire + ground TPME120SxxxWMN208Y/120 3-phase, 4-wire + ground TPME120YxxxWMN380Y/220 3-phase, 4-wire + ground TPME220YxxxWMN240 Delta 3-phase, 3-wire + ground TPME240DxxxWMN240/120 Hi-Leg Delta 3-phase, 4-wire + ground TPME240HxxxWMN415Y/240 3-phase, 4-wire + ground TPME240YxxxWMN4 8 0Y/277 3-phase, 4-wire + ground TPME277YxxxWMN60 0Y/3 47 3-phase, 4-wire + ground TPME347YxxxWMN480 Delta 3-phase, 3-wire + ground TPME480DxxxWMNDesired kA xxx Code65 06580 080100 100Product # ExampleTPME277Y15WMN4S277Y/480 V, 3 Ph, 4 W + G150kA per modeSurface mount enclosure without disconnectPainted steelT P M E W M NProduct #Nominal Voltage (Volts RMS)System Voltage ConfigurationVoltage Protection Rating (VPR) UL 1449 4th Edition September 2014 RevisionMCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L HL-L120S 120/240 1 Ph, 3 W + G 900 - 800 - 700 1200 - 125%120Y 120Y/208 3 Ph, 4 W + G 900 - 800 - 700 1200 - 125%220Y 220Y/3 80 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 - 145%240D 240 Delta 3 Ph, 4 W - - 1200 - - 1800 - 196%240H120/240 Delta HL3 Ph, 4 W + G 1000 1200 800 1200 700 2000 2200 115%240Y 24 0Y/415 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 - 130%277Y 277 Y/4 80 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 - 115%347Y 347 Y/6 0 0 3 Ph, 4 W + G 1500 - 1500 - 1500 2500 - 115%480D 480 Delta 3 Ph, 4 W - - 1800 - - 3000 - 198%Also available in 600D configurations. For details, please contact ABB Service at 800 637 1738.Maximum Surge Current CapacityExposure LevelPer Mode Per Phase06 ME 65kA 130kA08 ME 80kA 160kA10 ME 100kA 200kAPhase Rating = (L-N + L-G)Suffix DescriptionNEMA Enclosure Mounting Disconnect1 Painted Steel 1 Surface Yes1T11 Painted Steel 1 Surface Yes4 Fiberglass 4X Surface Yes4T11 Fiberglass 4X Surface Yes4S Painted Steel 4 Surface No4ST11 Painted Steel 4 Surface No4X Stainless Steel 4X Surface No4XT11 Stainless Steel 4X Surface No1UL Type 1 device

Page 86

—ABB HE seriesWallmount SPD with enhanced thermal protectionVoltage Configuration Product Number240/120 1-phase, 3-wire + ground TPHE120SxxxWMN208Y/120 3-phase, 4-wire + ground TPHE120YxxxWMN380Y/220 3-phase, 4-wire + ground TPHE220YxxxWMN240 Delta 3-phase, 3-wire + ground TPHE240DxxxWMN240/120 Hi-Leg Delta 3-phase, 4-wire + ground TPHE240HxxxWMN415Y/240 3-phase, 4-wire + ground TPHE240YxxxWMN4 8 0Y/277 3-phase, 4-wire + ground TPHE277YxxxWMN60 0Y/3 47 3-phase, 4-wire + ground TPHE347YxxxWMN480 Delta 3-phase, 3-wire + ground TPHE480DxxxWMN600 Delta 3-phase, 3-wire + ground TPHE600DxxxWMNDesired kA xxx Code150 150200 200250 250300 300T P H EW M NProduct #Nominal Voltage (Volts RMS)System Voltage ConfigurationVoltage Protection Rating (VPR) UL 1449 4th Edition September 2014 RevisionMCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L HL-L120S 120/240 1 Ph, 3 W + G 900 - 800 - 700 1200 - 125%120Y 120Y/208 3 Ph, 4 W + G 900 - 800 - 700 1200 - 125%220Y 220Y/380 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 - 145%240D 240 Delta 3 Ph, 4 W - - 1200 - - 1800 - 196%240H120/240 Delta HL3 Ph, 4 W + G 1000 1200 800 1200 700 2000 2200 115%240Y 24 0 Y/415 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 - 130%277Y 277 Y/48 0 3 Ph, 4 W + G 1500 - 1200 - 1200 2000 - 115%347Y 347Y/6 0 0 3 Ph, 4 W + G 1500 - 1500 - 1500 2500 - 115%480D 480 Delta 3 Ph, 4 W - - 1800 - - 3000 - 198%Also available in 600D configurations. For details, please contact ABB Service at 800 637 1738.Maximum Surge Current CapacityExposure LevelPer Mode Per Phase12 HE 125kA 250kA15 HE 150kA 300kA20 HE 200kA 400kA25 HE 250kA 500kA30 HE 300kA 600kAPhase Rating = (L-N + L-G)Product # ExampleTPHE277Y15WMN4S277Y/480 V, 3 Ph, 4 W + G150kA per modeSurface mount enclosure without disconnectPainted steelSuffix DescriptionNEMA Enclosure Mounting Disconnect1 Painted Steel 1 Surface Yes1T11 Painted Steel 1 Surface Yes4 Fiberglass 4X Surface Yes4T11 Fiberglass 4X Surface Yes4S Painted Steel 4 Surface N24ST11 Painted Steel 4 Surface No4X Stainless Steel 4X Surface No4XT11 Stainless Steel 4X Surface No1UL Type 1 device

Page 87

—ABB LE seriesWallmount SPDVoltage Configuration Product Number240/120 1-phase, 3-wire + ground TLE120SxxxWM208Y/120 3-phase, 4-wire + ground TLE120YxxxWM380Y/220 3-phase, 4-wire + ground TLE220YxxxWM240 Delta 3-phase, 3-wire + ground TLE240DxxxWM240/120 Hi-Leg Delta 3-phase, 4-wire + ground TLE240HxxxWM415Y/240 3-phase, 4-wire + ground TLE240YxxxWM4 8 0Y/277 3-phase, 4-wire + ground TLE277YxxxWM480 Delta 3-phase, 3-wire + ground TLE480DxxxWMDesired kA xxx Code25 02550 050T L E W MProduct #Nominal Voltage (Volts RMS)System Voltage ConfigurationVoltage Protection Rating (VPR) UL 1449 4th Edition September 2014 RevisionMCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L HL-L120S 120/240 1 Ph, 3 W + G 600 - 600 - 600 1000 - 125%120Y 120Y/208 3 Ph, 4 W + G 600 - 600 - 600 1000 - 125%220Y 220Y/38 0 3 Ph, 4 W + G 1200 - 1000 - 1200 1800 - 145%240D 240 Delta 3 Ph, 4 W - - 900 - - 1800 - 196%240H120/240 Delta HL3 Ph, 4 W + G 600 1200 600 1000 600 1000 1800 115%240Y 24 0 Y/415 3 Ph, 4 W + G 1200 - 1000 - 1200 1800 - 130%277Y 27 7 Y/4 8 0 3 Ph, 4 W + G 1200 - 1000 - 1200 1800 - 115%480D 480 Delta 3 Ph, 4 W - - 1800 - - 4000 - 198%025 25 kA per mode 50 kA per phase (TLE)050 50 kA per mode 100 kA per phase (TLE)

Page 88

—ABB ME seriesWallmount SPDVoltage Configuration Product Number240/120 1-phase, 3-wire + ground TME120SxxxWM208Y/120 3-phase, 4-wire + ground TME120YxxxWM380Y/220 3-phase, 4-wire + ground TME220YxxxWM240 Delta 3-phase, 3-wire + ground TME240DxxxWM240/120 Hi-Leg Delta 3-phase, 4-wire + ground TME240HxxxWM415Y/240 3-phase, 4-wire + ground TME240YxxxWM4 8 0Y/277 3-phase, 4-wire + ground TME277YxxxWM480 Delta 3-phase, 3-wire + ground TME480DxxxWMDesired kA xxx Code65 06580 080100 100T M E W MProduct #Nominal Voltage (Volts RMS)System Voltage ConfigurationVoltage Protection Rating (VPR) UL 1449 4th Edition September 2014 RevisionMCOV% Max. Continuous Operating VoltageL-N HL-N L-G HL-G N-G L-L HL-L120S 120/240 1 Ph, 3 W + G 600 - 600 - 600 1000 - 125%120Y 120Y/208 3 Ph, 4 W + G 600 - 600 - 600 1000 - 125%220Y 220Y/380 3 Ph, 4 W + G 1200 - 1000 - 1200 1800 - 145%240D 240 Delta 3 Ph, 4 W - - 900 - - 1800 - 196%240H120/240 Delta HL3 Ph, 4 W + G 600 1200 600 1000 600 1000 1800 115%240Y 24 0Y/415 3 Ph, 4 W + G 1200 - 1000 - 1200 1800 - 130%277Y 277 Y/4 8 0 3 Ph, 4 W + G 1200 - 1000 - 1200 1800 - 115%480D 480 Delta 3 Ph, 4 W - - 1800 - - 4000 - 198%065 65 kA per mode 130 kA per phase (TME)080 80 kA per mode 160 kA per phase (TME)100 100 kA per mode 200 kA per phase (TME)

Page 89

—Load Centers and Circuit Breakers* New Load Center offering coming soon

Page 90

PowerMark Gold load centers lower your costs by making installation faster and easier, increasing application flexibility and reducing inventory requirements. At the same time, they deliver obvious and significant advances in design, function and quality. - UL Listed (Panelboards No. 67) - Service Barriers included for factory installed main circuit breaker and main circuit breaker kits (required to meet UL67 for service entrance applications) - Suitable for Use as Service Entrance Equipment when i nstalled in accordance with National Electrical Code - 60°C/75°C Conductor Rating - Single phase, 40-225A, 2-42 circuits - Main lug models field convertible to main breaker - Main breaker 22kAIC standard - factory installed - All load centers top or bottom feed - Indoor and outdoor rated enclosures - Indoor fronts combination surface/flush - Copper bus with tin plating standard1 - Split neutrals extend the full length of the interior for ease of wiring - Entire main lug line converts easily to main breaker - Combination surface/flush front with spring- reinforced pan - Combination slotted/Robertson square-drive screws on neutral,2 ground, front and breaker lugs - Front packed in inner carton for added protection—PowerMark Gold Load CentersHighest Quality and Convenience - Field installable feed-through lugs up to 200A - Straight-through main wiring - Main breaker is clearly marked and circuit numbers are stamped on front - Isolated ground bar is available - Compact box maintains optimum wire-bending space1 Three-phase PowerMark Plus load centers have aluminum bus with copper breaker mounting stabs.2 16 circuit and above.One-piece interior removes and reinstalls easilyFull-length neutrals are easier to wire,2 reducing installation time and costMinimum 100% neutral terminationsSturdy copper bus and galvanized box increase durability and reliabilityAccepts ABB Q-Line branch circuit breakers, including ABB’s exclusive 1/2" THQPsTie bar may be removed to split neutral/ground100% rated split neutral on each side2All holes rated for 14-4 wireCombination slotted/Robertson square-drive speeds screw wiringMain breaker configuration allows top or bottom feed without modificationSafety accessories – convenient and easy to install - THQLSURGE whole house surge protector - Arc fault circuit interrupter breaker, 1- or 2-pole - Ground fault circuit interrupter breaker, 5mA and 30mA - Generator transfer panel – 30A or 60A, indoor or outdoor - ABB AC disconnects - Service Barrier KitsAccessories and Options - Door lock and handle - Equipment ground kits - Sub-feed and feed-thru lugs - Front filler plates - Handle lock and ties - Hardware kits - Main breaker retainers - Neutral kits - Universal raintight hubsPackaging features comprehensive selection and application data.Fronts are packed in inner cartons for added protection during shipment and at the job site.A complete family of meter socket load centers — ring style and ringless, wide and narrow, meter mains, farm panels and more — deliver specialized solutions for special situations.Main lug load centers offer an economical solution for subpanels and similar applications. All main lug units 125A and above convert easily to main breaker.The PowerMark Gold line includes a wide range of outdoor as well as indoor units.ABB’s residential load centers reach into commercial applications as well, with riser panels, auxiliary gutters, three-phase units with standard 22kAIC ratings, and all the accessories needed to complete the job.

Page 91

—PowerMark Gold and Plus Load CentersProduct Number GuidesProduct Number Guide for Load Centers(Product number for illustrative purposes only)Product Number Guide for Q-Line Plug-in Circuit Breakers(Product number for illustrative purposes only)204CBCU42MTABB IdentificationType M = Main breaker L = Main lug LM = Convertible PL = Main lug (Thermoplastic)Insert for PowerMark Gold CU = Copper Bus 42 = Copper Bus Full 42 circuit panelMaximum Number 1" Spaces 2, 4, 6…42Insert for 3-Phase 4-WireLoad CentersInsert for Specials G or T = Factory installed ground bar B = Bottom feed main breaker FL = Factory installed feed-through lugs D = Optional door for 6-8 circuit panel. (Doors standard on all units 12 circuits or greater) W = White Front Enclosure Type C = Combination surface/flush F = Flush S = Surface R = OutdoorBus Ampere Rating 40 = 40 Amps 20 = 200 Amps 70 = 70 Amps 22 = 225 Amps 10 = 100 Amps 12 = 125 Amps 15 = 150 AmpsABB IdentificationInterrupting Rating H = 10kAlC HH = 22kAlC X = 65kAlCGround Fault/Arc Fault Circuit Interrupter AF2 = 1- & 2-pole Combination Arc Fault Circuit Interrupter GFEP = 1- & 2-pole Ground Fault with Equipment Protection Interrupter–30 mA GFT = 1- & 2-pole Ground Fault with Self-Test Feature Interrupter - 5 mA DF = 1-pole Dual Function GFCI/AFCI Ground Fault & Combination Arc Fault Circuit Interrupter S = Short pig tailPoles (1, 2, 3)Type QL = 1" plug-in QP = 1/2" plug-in QB = 1" bolt-onAmpere RatingVoltage 1 = 120/240V 2 = 240V*Omit character for THQP breakers, which are all 120/240V.1*115QLHTGFTS

Page 92

Q-Line Plug-in Circuit Breakers SpecificationsBreaker Type Ampere RatingWire Size AWG/kcmilCu AlTHQP15-30 14-8 12-835-50 8-4 8-4THQLTHHQLTXQL15-30 14-8 12-835-60 8-3 8-370 -100 6-1/0 4 -1/0110 -125 2-2/0 2-2/01 Solid or stranded for 14-10 AWGReferences:Accessories Pages 1-26 thru 1-32Auxiliary Switches and Shunt Trips BuyLog pages 6-40 thru 6-42Q-Line Plug-in Circuit BreakersAmpere Rating          Product Number Product Number Product Number Product Number Product Number Product NumberSingle Pole1152THQP115 THQL1115 – THHQL1115 – TXQL1115202THQP120 THQL1120 – THHQL1120 – TXQL112025 THQP125 THQL1125 – THHQL1125 – TXQL112530 THQP130 THQL1130 – THHQL1130 – TXQL113035 THQP135 THQL1135 – THHQL1135 – –40 THQP140 THQL1140 – THHQL1140 – –45 THQP145 THQL1145 – THHQL1145 – –50 THQP150 THQL1150 – THHQL1150 – –Std. Pkg.    Two-Pole: Incorporates Internal Common Trip Bar15 THQP215 THQL2115 THQL220154THHQL2115 THHQL220154TXQL211520 THQP220 THQL2120 THQL220204THHQL2120 THHQL220204TXQL212025 THQP225 THQL2125 THQL220254THHQL2125 THHQL220254TXQL212530 THQP230 THQL2130 THQL220304THHQL2130 THHQL220304TXQL213035 THQP235 THQL2135 THQL220354THHQL2135 THHQL220354–40 THQP240 THQL2140 THQL220404THHQL2140 THHQL220404–45 THQP245 THQL2145 THQL220454THHQL2145 THHQL220454–50 THQP250 THQL2150 THQL220504THHQL2150 THHQL220504–60 – THQL2160 THQL220604THHQL2160 THHQL220604–70 – THQL2170 THQL220704THHQL2170 THHQL220704–80 – THQL2180 THQL220804THHQL2180 THHQL220804–90 – THQL2190 THQL220904THHQL2190 THHQL220904–100 – THQL21100 THQL221004THHQL21100 THHQL221004–110 – THQL21110 – THHQL21110 – –125 – THQL21125 – THHQL21125 – –Std. Pkg.      : Incorporates Internal Common Trip Bar15 – – THQL32015 – THHQL32015 TXQL3201520 – – THQL32020 – THHQL32020 TXQL3202025 – – THQL32025 – THHQL32025 TXQL3202530 – – THQL32030 – THHQL32030 TXQL3203035 – – THQL32035 – THHQL32035 –40 – – THQL32040 – THHQL32040 –45 – – THQL32045 – THHQL32045 –50 – – THQL32050 – THHQL32050 –60 – – THQL32060 – THHQL32060 –70 – – THQL32070 – THHQL32070 –80 – – THQL32080 – THHQL32080 –90 – – THQL32090 – THHQL32090 –100 – – THQL32100 – THHQL32100 –Std. Pkg.   1 UL Listed as HACR (heating, air conditioning and refrigeration).2 UL Listed as SWD (switching duty). Suitable for 120 volts ac fluorescent lighting loads.3 15-100 amp UL Listed as HACR (heating air conditioning and refrigeration).4 Required for three-phase and High Leg Delta Systems only.—Q-Line Plug-in Circuit BreakersUL Listed (Molded Case Circuit Breakers No. 489)Federal Government Specification Qualified (WC-375B)60°C / 75°C Conductor RatingQuick Make, Quick BreakBox Type TerminalsTHQP230 THQL1120THQL2140 THQL32015THQP130THQL32015

Page 93

Arc Fault2cULus ListedArc-Fault Circuit Interrupters No. 1699Ampere RatingProduct Number Product NumberLong Pig Tail 15 THQL1115AF2 THQL1115AF2S20 THQL1120AF2 THQL1120AF2S15 THHQL1115AF2 -20 THHQL1120AF2 -Std. Pkg.  -As of Jan. 1, 2008, 2005 NEC™ requires combination AFCI.1 Combination AFCI compliant with 2008 NEC™ and later2 For 2-Pole shared neutral applications use two 1-pole circuit breakers with a handle tie. See DET-719 for more details on our Arc Fault products.PowerMark Gold* Main Circuit Breakers Kits for use in 150A, 200A & 225A Convertible Load CentersUL Listed - Example - TLMXX20CCU - 200A Convertible Load Center - Includes mounting base - Not for use in 125A and below Convertible Load Centers (TLMXX12CCU) - Main Breaker Conversions for 125A load centers - see footnotes for individual catalog numbersDescription Ampere Rating Product Number Lug SizeMain Circuit Breaker Kits22,000 AIC100 THQMV100D1-300 (cu), 2/0-300125 THQMV125D150 THQMV150D175 THQMV175D200 THQMV200D225 THQMV225DNote: Wire bending rules affect allowed wire sizes when THQMV breakers are installed in an enclosure. For load centers, the wire range will be on the rating label. In addition, refer to the specifications for the main breaker versions of the load center you are considering to review allowed wire ranges when a TLMXX20 load center is converted to main breaker.cULusGround Fault Circuit Interrupters UL943 ed5 (5 milliamperes)Ampere Rating  Product Number Product Number Product NumberLong Pig Tail  Long Pig Tail15 THQL1115GFT THQL1115GFTS THQL2115GFT20 THQL1120GFT THQL1120GFTS THQL2120GFT25 THQL1125GFT - THQL2125GFT30 THQL1130GFT - THQL2130GFT40 – - THQL2140GFT350 – - THQL2150GFT315 THHQL1115GFT - THHQL2115GFT20 THHQL1120GFT - THHQL2120GFT25 THHQL1125GFT - THHQL2125GFT30 THHQL1130GFT - THHQL2130GFTStd. Pkg.  - -3 UL & CSADual Function GFCI/AFCI Ground Fault & Combination Arc Fault Circuit BreakercULus ListedAmpere Rating Product Number Product NumberLong Pig Tail 15 THQL1115DF THQL1115DFS20 THQL1120DF THQL1120DFS15 THHQL1115DF –20 THHQL1120DF –Std. Pkg.  –—Special Purpose Circuit Breakers60°C / 75°F Conductor RatingBox Type TerminalsQuick-Make, Quick-BreakMulti-pole Breakers Incorporate Internal Common TripArc FaultTHQL1115DF THQL1115DFSTHQL2120GFT THQL1115GFTSTHQMV100D with filler platesTHQMV200DTHQL1115AF2S

Page 94

PowerMark Gold Main Circuit Breaker KitFor use with 125A PowerMark Gold load Centers; 22kAIC RMS symmetrical.Description Product NumberMain Circuit Breaker Kit - Order appropriate THQL10kAIC or THHQL 22kAIC breakers separately. Includes service barriers for use with THQL or THHQL main.TQMH00011 Please review the footnotes listed with the individual Load Center product numbers for proper parts needed to convert to a main circuit breaker. This main breaker base is only applicable for 16 circuit and larger 125 amp load centers, 12 circuit load centers with A C24 suffix, and the TLM812RCU2.cULusGround Fault Circuit Interrupters No. 943 30 milliampere ground fault trip levelAmpere Rating Product Number Product Number15 THQL1115GFEP THQL2115GFEP20 THQL1120GFEP THQL2120GFEP30 THQL1130GFEP THQL2130GFEP15 - THHQL2115GFEP20 - THHQL2120GFEPStd. Pkg.  UL Listed. 10kAIC RMS symmetrical.Standard 1- or 2-pole automatic breaker plus one fully-rated, non-automatic pole.Ampere Rating  Product Number Product Number15 THQL21WY15 THQL31WY1520 THQL21WY20 THQL31WY2025 THQL21WY25 THQL31WY2530 THQL21WY30 THQL31WY30Std. Pkg.  UL Listed as HID. HID breakers have been designed to handle the current and voltagespikes that result when gaseous discharge lamps, including fluorescent and HID lamps,are switched on and off.Ampere Rating Product Number Product Number15 THQL1115HID2THQL2115HID20 THQL1120HID2THQL2120HID30 THQL1130HID THQL2130HID15 THHQL1115HID2THHQL2115HID20 THHQL1120HID2THHQL2120HID30 THHQL1130HID THHQL2130HIDStd. Pkg.  2 UL Listed as SWD (switching duty). Suitable for 120 volts ac fluorescent lighting loads.UL Listed. 10kAIC RMS symmetricalHigh short circuit setting suitable for circuits with inherent high-inrush load currents.Ampere RatingProduct Number15 THQL1115HM20 THQL1120HM25 THQL1125HM30 THQL1130HM40 THQL1140HM50 THQL1150HMStd. Pkg. —Special Purpose Circuit Breakers60°C / 75°F Conductor RatingBox Type TerminalsQuick-Make, Quick-BreakMulti-pole Breakers Incorporate Internal Common TripTQMH000THQL21WY30THQL2115GFEPTHQL2120HIDTHQL1140HM

Page 95

—Special Purpose Circuit Breakers60°C / 75°F Conductor RatingBox Type TerminalsQuick-Make, Quick-BreakMulti-pole Breakers Incorporate Internal Common TripUL ListedWithout overload or short circuit protection.Ampere Rating Product Number Product Number60 TQL21Y60 –100 TQL21Y100 –60 TQL22Y60 TQL32Y60100 TQL22Y100 TQL32Y100Std. Pkg.  TQ Circuit Breakers3/4" UL Classified Circuit Breakers for use in *Square D **QO Load Centers.10 kAIC RMS symmetricalAmpere Rating Product Number Product Number15 TQ1115 TQ211520 TQ1120 TQ212030 TQ1130 TQ213040 TQ1140 TQ214050 TQ1150 TQ215060 – TQ2160Std. Pkg.  1# ofPolesAmpereRatingWire RangeInterrupting RatingProduct Number1 15 (1) 14-8 Cu/12-8 Al 10k A THQL1115ST11 20 (1) 14-8 Cu/12-8 Al 10kA THQL1120ST11 30 (1) 14-8 Cu/12-8 Al 10k A THQL1130ST11 35 (1) 8-3 Cu/8-3 Al 10kA THQL1135ST11 Shunt trip requires one additional pole of space.1# ofPolesAmpereRatingWire RangeInterrupting RatingProduct Number2 15 14-8 Cu/12-8 Al 10kA THQL2115ST12 20 14-8 Cu/12-8 Al 10kA THQL2120ST12 30 14-8 Cu/12-8 Al 10kA THQL2130ST12 35 8-3 Cu/8-3 Al 10kA THQL2135ST12 40 8-3 Cu/8-3 Al 10kA THQL2140ST12 45 8-3 Cu/8-3 Al 10kA THQL2145ST12 50 8-3 Cu/8-3 Al 10kA THQL2150ST12 60 8-3 Cu/8-3 Al 10kA THQL2160ST12 70 6-1/0 Cu/4-1/0 Al 10kA THQL2170ST12 80 6-1/0 Cu/4-1/0 Al 10kA THQL2180ST12 90 6-1/0 Cu/4-1/0 Al 10kA THQL2190ST12 100 6-1/0 Cu/4-1/0 Al 10kA THQL21100ST13 20 14-8 Cu/12-8 Al 10kA THQL32020ST13 30 14-8 Cu/12-8 Al 10kA THQL32030ST13 40 8-3 Cu/8-3 Al 10kA THQL32040ST13 50 8-3 Cu/8-3 Al 10kA THQL32050ST13 60 8-3 Cu/8-3 Al 10kA THQL32060ST13 70 6-1/0 Cu/4-1/0 Al 10kA THQL32070ST13 80 6-1/0 Cu/4-1/0 Al 10kA THQL32080ST13 90 6-1/0 Cu/4-1/0 Al 10kA THQL32090ST13 100 6-1/0 Cu/4-1/0 Al 10kA THQL32100ST12 Solid or stranded for 14-10 AWG.*Square D is a registered trademark of SNA Holdings, Inc. **QO is a registered trademark of the Square D Company.Interlocking Circuit Breakers for use in PowerMark Gold Generator PanelsTwo breakers required for interlocking.Poles Ampere Rating Product Number2 30 THQL2130GEN2 60 THQL2160GENTQL21Y100TQ1120TQ2120THQL1130ST1THQL2120ST1THQL32020ST1

Page 96

—PowerMark Gold and Plus Load CentersSingle-Phase, Three-Wire, 120/240 VacMain Lugs Convertible to Main BreakerProduct Features - UL Listed (Panelboards No. 67) - 0°/75°C Conductor Rating - Suitable for Use as Service Entrance Equipment when Installed in Accordance with the National Electrical Code - 22kAIC RMS symmetrical, Except Where Noted - 6-42 circuit devices UL Listed for bottom mounted lugs by installing complete unit (box, interior and front) upside down. - For a listing of CSA Listed load centers, visit electrification.us.abb.com.TLM2020CCU TPL412RLoad Center1PHMain LugIndoor NEMA 1MainAmpereRatingSpacesSpacesSpacesSpacesTotalSpacesFrontTypeFeed TypeBoxNumberMain Wire Size(AWG/kcmil)Cu-AlGround KitProductNumber40 2 1 4 1 4 SurfaceTopBottom1A 14-4 TGK4 (order separately) TL240SCU1,870 2 1 4 1 4 SurfaceTopBottom1A 6-3 TGK4 (order separately) TL270SCU1,8125 4 2 8 3 8CombinationFlush/SurfaceTopBottom2A 1-2/0 TGL1 (order separately) TL412C1,2,8125 4 2 8 3 8CombinationFlush/SurfaceTopBottom2A 1-2/0 TGL1 installed TL412CT1,2,3,8125 4 2 8 3 8 ThermoplasticTopBottom2 1-2/0 TGL1 (order separately) TPL412C1,2,3,8125 4 2 8 3 8 ThermoplasticTopBottom2 1-2/0 TGL1 installed TPL412CT1,2,3,8125 6 3 12 4 12 FlushTopBottom3A 6-1 TGL2 (order separately) TLM612FCU4,8125 6 3 12 4 12 FlushTopBottom3A 6-1 TGL2 (order separately) TLM612FCUD4,8125 6 3 12 4 12 FlushTopBottom3A 6-1 TGL2 installed TLM612FCUDG4,8125 6 3 12 4 12 SurfaceTopBottom3A 6-1 TGL2 (order separately) TLM612SCU4,8125 6 3 12 4 12 SurfaceTopBottom3A 6-1 TGL2 (order separately) TLM612SCUD4,8125 6 3 12 4 12 SurfaceTopBottom3A 6-1 TGL2 installed TLM612SCUDG4,8125 8 4 16 8 16 FlushTopBottom3A 6-1 TGL2 (order separately) TLM812FCU4,8125 8 4 16 8 16 FlushTopBottom3A 6-1 TGL2 (order separately) TLM812FCUD4,8125 8 4 16 8 16 FlushTopBottom3A 6-1 TGL2 (order separately) TLM812FCUDG4,8125 8 4 16 8 16 SurfaceTopBottom3A 6-1 TGL2 (order separately) TLM812SCU4,8125 8 4 16 8 16 SurfaceTopBottom3A 6-1 TGL2 (order separately) TLM812SCUD4,8125 8 4 16 8 16 SurfaceTopBottom3A 6-1 TGL2 installed TLM812SCUDG4,8125 14 6 20 8 24CombinationFlush/SurfaceTopBottom18 6-2/0 Included10TLM1212CCU7,8125 14 6 20 8 24White ComboFlush/SurfaceTopBottom18 6-2/0 Included10TLM1212CCUW7,8,91 No door2 10 kAIC3 125 amp maximum branch capacity.4 For main breaker, order THQLRK2 retainer kit plus 2-pole circuit breaker. See page 1-30, 100 amp max.5 For main breaker, order TQMH000. See page 1-26. Also order 2-pole THQL, THHQL, or TXQL circuit breaker. See page 1-7.6 For main breaker, order THQMVXXXD circuit breaker from page 1-8.7 For main breaker applications, use reverse feed THQL breaker or THHQL circuit breaker (see page 1-7) and THQLRK3 breaker retainer (see page 1-30).8 No lock provision available. Use next size larger load center such as TLM1612CCU with a TDL106 accessory if locking provision is required.9 Minimum order QTY is 40 for below 24 circuits; QTY 24 for 24 circuits and above. (See DEE-590)10 Load center includes a factory installed ground bar and add-a-lug. See wiring diagram on page 1-33. A separate TGL2 can be added in the unlikey event that another ground bar is required.This table continued on next page

Page 97

—PowerMark Gold and Plus Load CentersSingle-Phase, Three-Wire, 120/240 VacMain Lugs Convertible to Main BreakerMainAmpereRatingSpacesSpacesSpacesSpacesTotalSpacesFrontTypeFeed TypeBoxNumberMain Wire Size(AWG/kcmil) Cu-AlGround KitProductNumber125 16 8 16 6 24CombinationFlush/SurfaceTopBottom4 6-2/0TGK12 or TGK24(order separately)TLM1612CCU5125 16 8 16 6 24CombinationFlush/SurfaceTopBottom4 6-2/0TGK12 and TLK20installedTLM1612CCUG5125 24 12 0 0 24CombinationFlush/SurfaceTopBottom7 6-2/0TGK24 or TGK32(order separately)TLM2412CCU5125 24 12 0 0 24White ComboFlush/SurfaceTopBottom7 6-2/0TGK24 or TGK32(order separately)TLM2412CCUW5,9125 24 12 0 0 24CombinationFlush/SurfaceTopBottom7 6-2/0TGK24 and TLK20installedTLM2412CCUG5200 16 8 32 14 32CombinationFlush/SurfaceTopBottom7 6-250TGK32(order separately)TLM1620CCU6200 16 8 32 14 32White ComboFlush/SurfaceTopBottom7 6-250TGK32(order separately)TLM1620CCUW6,9200 16 8 32 14 32CombinationFlush/SurfaceTopBottom7 6-250TGK32installedTLM1620CCUG6200 20 10 40 18 40CombinationFlush/SurfaceTopBottom8 6-250TGK32(order separately)TLM2020CCU6200 20 10 40 18 40White ComboFlush/SurfaceTopBottom8 6-250TGK32(order separately)TLM2020CCUW6,9200 20 10 40 18 40CombinationFlush/SurfaceTopBottom8 6-250TGK42installedTLM2020CCUG6200 24 12 36 18 42CombinationFlush/SurfaceTopBottom91-3/0 (Cu),2/0-3/0 (Al)TGK24 or TGK32(order separately)TLM2420C426200 32 16 20 8 42CombinationFlush/SurfaceTopBottom111-250 (Cu),2/0-250 (Al)TGK32 and TLK20(order separately)TLM3220C426200 32 16 16 6 40CombinationFlush/SurfaceTopBottom11 6-250TGK32(order separately)TLM3220CCU6200 32 16 16 6 40White ComboFlush/SurfaceTopBottom11 6-250TGK32(order separately)TLM3220CCUW6,9200 32 16 16 6 40CombinationFlush/SurfaceTopBottom11 6-250TGK32 andTNLK250 installedTLM3220CCUG6200 32 16 64 30 64CombinationFlush/SurfaceTopBottom19 6-250(2) TGK32 and (1) TLK250 installedTLM3220C64G2200 40 20 0 0 40CombinationFlush/SurfaceTopBottom13 6-250TGK42(order separately)TLM4020CCU6200 40 20 0 0 40White ComboFlush/SurfaceTopBottom13 6-250TGK42order separately)TLM4020CCUW6,9200 40 20 0 0 40CombinationFlush/SurfaceTopBottom13 6-250TGK42 andTNLK250 installedTLM4020CCUG6200 40 20 80 38 80CombinationFlush/SurfaceTopBottom20 6-250(2) TGK32 and (1) TLK250 installedTLM4020C80G2200 42 20 0 0 42CombinationFlush/SurfaceTopBottom141-300 (Cu),2/0-300 (Al)TGK42(order separately)TLM4220CCU6200 42 20 0 0 42CombinationFlush/SurfaceTopBottom141-300 (Cu),2/0-300 (Al)TGK42 andTNLK250 installedTLM4220CCUG6225 42 20 0 0 42CombinationFlush/SurfaceTopBottom141-300 (Cu),2/0-300 (Al)TGK42(order separately)TLM4222CCU6225 42 20 0 0 42CombinationFlush/SurfaceTopBottom141-300 (Cu),2/0-300 (Al)TGK42 andTNLK250 installedTLM4222CCUG61 No door2 10 kAIC3 125 amp maximum branch capacity.4 For main breaker, order THQLRK2 retainer kit plus 2-pole circuit breaker. See page 1-30, 100 amp max.5 For main breaker, order TQMH000. See page 1-26. Also order 2-pole THQL, THHQL, or TXQL circuit breaker. See page 1-7.6 For main breaker, order THQMVXXXD circuit breaker from page 1-8.7 For main breaker applications, use reverse feed THQL breaker or THHQL circuit breaker (see page 1-7) and THQLRK3 breaker retainer (see page 1-30).8 No lock provision available. Use next size larger load center such as TLM1612CCU with a TDL106 accessory if locking provision is required.9 Minimum order QTY is 40 for below 24 circuits; QTY 24 for 24 circuits and above. (See DEE-590)10 Load center includes a factory installed ground bar and add-a-lug. See wiring diagram on page 1-33. A separate TGL2 can be added in the unlikey event that another ground bar is required.Note: See page 11-4, AL Series Lighting Panelboards as replacements for 300-600A load centers.Load Center1PHMain LugIndoor NEMA 1

Page 98

—PowerMark Gold and Plus Load CentersSingle-Phase, Three-Wire, 120/240 VacMain Lugs Convertible to Main BreakerMainAmpereRatingSpacesSpacesSpacesSpacesTotalSpacesFrontTypeFeed TypeBoxNumberMain Wire Size(AWG/kcmil) Cu-AlGround KitProductNumber40 2 1 4 1 4 - Top R1A 14-4 TGK4 (order separately) TL240RCU70 2 1 4 1 4 - Top R1A 6-3 TGK4 (order separately) TL270RCU100 5 0 0 0 5 Flush Top R41 6-3 TGL1 installed TL510RT2,8125 4 2 8 3 8 - Top R1A 1-2/0 TGL1 (order separately) TL412R12125 4 2 8 3 8 - Top R1A 1-2/0 TGL1 installed TL412RT12125 4 2 8 3 8 - Top R41 1-2/0 TGL1 (order separately) TL412R22125 4 2 8 3 8ThermoplasticFrontTop R1 1-2/0 TGL1 (order separately) TPL412R2,3125 4 2 8 3 8ThermoplasticFrontTop R1 1-2/0 TGL1 installed TPL412RT2,3125 6 2 12 4 12 - Top R2A 6-1 TGL2 (order separately) TLM612RCU4125 8 4 16 8 16 - Top R2A 6 -1 TGL2 (order separately) TLM812RCU4125 8 4 16 8 16 - Top R3A 6 -1 TGL2 (order separately) TLM812RCU25125 14 6 20 8 24 - Top R3A 6-2/0 Included TLM1212RCU7,9125 24 12 0 0 24 -TopBottomR4A 6-2/0TGK24 or TGK32(order separately)TLM2412RCU5150 24 12 12 4 30 -TopBottomR6A1-3/0 (Cu),2/0-3/0 (Al)TGK24 or TGK32(order separately)TLM2415RCU6200 12 6 24 10 24 - Top R5A 6-250 TGK24 (order separately) TLM1220RCU6200 16 8 32 14 32 - Top R5A 6-250 TGK32 (order separately) TLM1620RCU6200 20 10 40 18 40 - Top R6A 6-250TGK24 or TGK42(order separately)TLM2020RCU6200 24 12 36 18 42 -TopBottomR391-250 (Cu),2/0-250 (Al)TGK24 (order separately) TLM2420R42200 32 16 16 6 40 -TopBottomR7A1-250 (Cu), 2/0-250 (Al)TGK32 (order separately) TLM3220RCU6200 40 20 0 0 40 -TopBottomR8A 6-250 TGK42 (order separately) TLM4020RCU6225 42 20 0 0 42 -TopBottomR8A1-300 (Cu),2/0-300 (Al)TGK42 (order separately) TLM4222RCU61 40-225 amp single-phase devices have removable closing caps. Larger ampere devices require field-cut openings. Order hubs separately. See page 1-29.2 10 kAIC.3 125 amp maximum branch capacity.4 For main breaker, order THQLRK2 retainer kit plus 2-pole circuit breaker. See page 1-30, 100 amp maximum due to wire bending requirements.5 For main breaker, order TQMH000. See page 1-26. Also order 2-pole THQL or THHQL circuit breaker. See page 1-7.6 For main breaker, order THQMVXXXD circuit breaker from page 1-8.7 For main breaker applications, use reverse feed THQL or THHQL circuit breaker (see page 1-7) and THQLRK3 breaker retainer (see page 1-30).8 Main and branch breakers are limited to 70 amps.9 Load center includes a factory installed ground bar and add-a-lug. See wiring diagram on page 1-33. A separate TGL2 can be added in the unlikey event that another ground bar is required.Note: See page 11-4, AL Series Lighting Panelboards as replacements for 300-600A load centers.Load Center1PHMain LugOutdoor NEMA 3R

Page 99

—PowerMark Gold and Plus Main Breaker Load CentersSingle-Phase, Three-Wire, 120/240 VacMain Breaker Factory InstalledProduct Features - UL Listed (Panelboards No. 67) - 60°C/75°C Conductor Rating - Suitable for Use as Service Entrance Equipment when Installed in Accordance with the National Electrical Code - 22kAIC RMS symmetrical, Except Where Noted - 6-42 circuit devices UL Listed for bottom mounted lugs by installing complete unit (box, interior and front) upside down. - For a listing of CSA Listed load centers, visit electrification.us.abb.com.TM2020CCU TM820RCUFLMainAmpereRatingSpacesSpacesSpacesSpacesTotalSpacesFrontTypeFeed TypeBoxNumberMain Wire Size(AWG/kcmil) Cu-AlGround KitProductNumber100 12 5 20 8 22CombinationFlush/SurfaceFrontTopBottom18 4-1/0 Included1TM1210CCU2100 24 12 0 0 24CombinationFlush/SurfaceFrontTopBottom7 1-2/0TGK24 or TGK32; andTLK20 (order separately)TM2410CCU100 20 10 0 0 20CombinationFlush/SurfaceFrontTopBottom6 4-1/0 TGK24 (order separately) TM2010CCU100 32 16 0 0 32CombinationFlush/SurfaceFrontTopBottom11 4-1/0 TGK32 (order separately) TM3210CCU125 12 5 20 8 22CombinationFlush/SurfaceFrontTopBottom18 1-2/0 Included1TM1212CCU2125 24 12 0 0 24CombinationFlush/SurfaceFrontTopBottom7 1-2/0 TGK24 (order separately) TM2412CCU125 16 8 16 6 24CombinationFlush/SurfaceFrontTopBottom4 1-2/0TGK12 or TGK24(order separately)TM1612CCU125 16 8 16 6 24CombinationFlush/SurfaceFrontTopBottom4 1-2/0 TGK24 installed TM1612CCUG150 16 8 32 14 32CombinationFlush/SurfaceFrontTopBottom71-3/0 (Cu),2/0-3/0 (Al)TGK24 or TGK32(order separately)TM1615CCU150 16 8 32 14 32CombinationFlush/SurfaceFrontTopBottom71-3/0 (Cu),2/0-3/0 (Al)TGK32 installed TM1615CCUGThis table continued on next pageLoad Center1PHMain BreakerIndoor NEMA 1

Page 100

—PowerMark Gold and Plus Main Breaker Load CentersSingle-Phase, Three-Wire, 120/240 VacMain Breaker Factory InstalledMainAmpereRatingSpacesSpacesSpacesSpacesTotalSpacesFrontTypeFeed TypeBoxNumberMain Wire Size(AWG/kcmil) Cu-AlGround KitProductNumber150 32 16 0 0 32CombinationFlush/SurfaceTopBottom111-3/0 (Cu),2/0-3/0 (Al)TGK32 (order separately) TM3215CCU150 24 12 36 18 42CombinationFlush/SurfaceTopBottom91-3/0 (Cu),2/0-3/0 (Al)TGK24 or TGK32(order separately)TM2415C42150 32 16 20 10 42CombinationFlush/SurfaceTopBottom111-3/0 (Cu),2/0-3/0 (Al)TGK32 and TLK20(order separately)TM3215C42150 40 20 80 38 80CombinationFlush/SurfaceTopBottom201-250 (Cu)2/0-250 (Al)Order separatelyif requiredTM4015C80200 16 8 32 14 32CombinationFlush/SurfaceTopBottom71-250 (Cu)2/0-250 (Al)TGK32 (order separately) TM1620CCU200 16 8 32 14 32CombinationFlush/SurfaceTopBottom81-250 (Cu)2/0-250 (Al)TGK32 installed TM1620CCUG200 20 10 40 18 40CombinationFlush/SurfaceTopBottom81-250 (Cu)2/0-250 (Al)TGK32 (order separately) TM2020CCU200 20 10 40 18 40White ComboFlush/SurfaceTopBottom81-250 (Cu)2/0-250 (Al)TGK24 or TGK42(order separately)TM2020CCUW3200 20 10 40 18 40CombinationFlush/SurfaceTopBottom81-250 (Cu)2/0-250 (Al)TGK32 installed TM2020CCUG200 20 10 40 18 40White ComboFlush/SurfaceTopBottom81-250 (Cu)2/0-250 (Al)TGK32 installed TM2020CCUGW3200 32 16 16 6 40CombinationFlush/SurfaceTopBottom111-250 (Cu)2/0-250 (Al)TGK32 (order separately) TM3220CCU200 40 20 0 0 40CombinationFlush/SurfaceTopBottom131-250 (Cu)2/0-250 (Al)TGK42 (order separately) TM4020CCU200 32 16 20 8 42CombinationFlush/SurfaceTopBottom111-250 (Cu)2/0-250 (Al)TGK32 and TLK20(order separately)TM3220C42200 42 20 0 0 42CombinationFlush/SurfaceTopBottom141-300 (Cu),2/0-300 (Al)TGK42 (order separately) TM4220CCU200 32 16 64 30 64CombinationFlush/SurfaceTopBottom191-250 (Cu)2/0-250 (Al)TGK32 (order separately) TM3220C64200 40 20 80 38 80CombinationFlush/SurfaceTopBottom201-250 (Cu)2/0-250 (Al)TGK42 (order separately) TM4020C80225 42 20 0 0 42CombinationFlush/SurfaceTopBottom141-300 (Cu),2/0-300 (Al)TGK42 (order separately) TM4222CCU1 Load center includes a factory installed ground bar and add-a-lug. See wiring diagram on page 1-33. A separate TGL2 can be added in the unlikey event that another ground bar is required.2 No lock provision available. Use next size larger load center such as TLM1612CCU with a TDL106 accessory if locking provision is required.3 Minimum order QTY is 40 for below 24 circuits; QTY 24 for 24 circuits and above. (See DEE-590)MainAmpereRatingSpacesSpacesSpacesSpacesTotalSpacesFeed TypeBoxNumberMain Wire Size(AWG/kcmil) Cu-AlGround KitProductNumber100 12 5 20 8 22 Top R3A 4-1/05TM1210RCU100 20 10 0 0 30 Top R4 4-1/0 TGK24 (order separately) TM2010RCU125 12 5 20 8 22 Top R3A 1-2/05TM1212RCU125 24 12 0 0 24 Top R4 1-2/0 TGK24 (order separately) TM2412RCU150 8 4 16 6 16 Top R5 1-250 (Cu), 2/0-250 (Al) TGK24 (order separately) TM815RCUFL150 16 8 32 14 32 Top R5 1-3/0 (Cu), 2/0-3/0 (Al)TGK24 (order separately)TGK32 (order separately)TM1615RCU150 24 12 12 4 30 Top R6 1-3/0 (Cu), 2/0-3/0 (Al)TGK24 (order separately)TGK32 (order separately)TM2415RCU150 24 12 36 18 42TopBottomR39 1-250 (Cu), 2/0-250 (Al) TGK24 (order separately) TM2415R42150 32 16 0 0 32 Top R7 1-3/0 (Cu), 2/0-3/0 (Al) TGK32 (order separately) TM3215RCU200 8 4 16 6 16 Top R5 1-250 (Cu), 2/0-250 (Al)TGK24 or TGK32 (order separately)TM820RCUFL200 20 10 40 18 40 Top R6 1-250 (Cu), 2/0-250 (Al)TGK24 (order separately)TGK42 (order separately)TM2020RCU200 24 12 36 18 42TopBottomR39 1-250 (Cu), 2/0-250 (Al) TGK24 (order separately) TM2420R42200 32 16 16 6 40 Top R7 1-250 (Cu), 2/0-250 (Al) TGK32 (order separately) TM3220RCU200 40 20 0 0 40 Top R8 1-250 (Cu), 2/0-250 (Al) TGK42 (order separately) TM4020RCU225 8 4 16 6 16 Top R5 1-250 (Cu), 2/0-250 (Al) TGK24 (order separately) TM822RCUFL225 42 20 0 0 42 Top R8 1-300 (Cu), 2/0-300 (Al) TGK42 (order separately) TM4222RCU4 100-225 amp devices have removable closing caps. Larger ampere devices require field-cut openings. Order hubs separately. See page 1-29.5 Load Center includes a factory installed ground bar and add-a-lug. See wiring diagram on page 1-33. A separate TGK12 or TGK24 can be ordered as accessories.Note: See page 11-4, AL Series Lighting Panelboards as replacements for 300-600A load centers.Load Center1PHMain BreakerIndoor NEMA 1Load Center1PHMain BreakerOutdoor NEMA 3R

Page 101

—PowerMark Plus™ Load CentersThree-Phase, Four-Wire, 208Y/120 Vac2Main Lugs Factory InstalledProduct Features - UL Listed (Panelboards No. 67) - 60°/75°C Conductor Rating - Suitable for Use as Service Entrance Equipment when Installed in Accordance with the National Electrical Code - 22kAIC RMS symmetrical Short-circuit Rating Standard - Bottom feed models available where noted with a “B” suffix. - For a listing of CSA Listed load centers, visit electrification.us.abb.com. - Copper breaker mounting stabs with aluminum bus1MainAmpereRatingSpacesSpacesSpacesTotalSpacesFrontTypeFeed TypeBoxNumberMain Wire Size(AWG/kcmil) Cu-AlGround KitProductNumber125 12 6 4 12CombinationFlush/SurfaceFrontTopBottom4 6-2/0TGK12 (order separately)TGK24 (order separately)TL12412C3150 18 8 6 18CombinationFlush/SurfaceFrontTopBottom71-3/0 (Cu),2/0-3/0 (Al)TGK24 (order separately)TGK32 (order separately)TL18415C3150 24 12 8 24CombinationFlush/SurfaceFrontTopBottom71-3/0 (Cu),2/0-3/0 (Al)TGK24 (order separately)TGK32 (order separately)TL24415C3200 18 8 6 18CombinationFlush/SurfaceFrontTopBottom81-250 (Cu),2/0-250 (Al)TGK32 (order separately) TL18420C3200 30 14 10 30CombinationFlush/SurfaceFrontTopBottom111-250 (Cu),2/0-250 (Al)TGK32 (order separately) TL30420C3200 42 20 14 42CombinationFlush/SurfaceFrontTopBottom131-250 (Cu),2/0-250 (Al)TGK42 (order separately) TL42420C225 30 14 10 30CombinationFlush/SurfaceFrontTopBottom151-300 (Cu),2/0-300 (Al)(2) TGL2 (order separately) TL30422C4225 42 20 14 42CombinationFlush/SurfaceFrontTopBottom151-300 (Cu),2/0-300 (Al)(2) TGL2 (order separately) TL42422C41 Three-phase PowerMark Plus load centers have aluminum bus with copper breaker mounting stabs, providing copper-to-copper contact at breaker stabs.2 Also UL Listed for three-phase, four-wire 240/120 Volts ac delta and three-phase, three-wire 240 Volts ac branch breakers installed.3 Alternate main breaker: 100 Amp max. THQL (10kAIC), THHQL (22kAIC) three-pole, use retainer THQLRK. See page 1-30.4 Not suitable for use as service entrance equipment.Note: See page 11-4, AL Series Lighting Panelboards as replacements for 300-600A load centers.Load Center3PHMain LugsIndoor NEMA 1TL18415C

Page 102

—PowerMark Plus™ Load CentersThree-Phase, Four-Wire, 208Y/120VacMain Circuit Breaker or Main Lugs Factory InstalledMain Breaker Factory InstalledMainAmpereRatingSpacesSpacesSpacesTotalSpacesFrontTypeFeed TypeBoxNumberMain Wire Size(AWG/kcmil) Cu-AlGround KitProductNumber100 12 6 4 12CombinationFlush/SurfaceFrontTopBottom66-1/0 (Cu),4-1/0 (Al)TGK12 or TGK24(order separately)TM12410C5100 18 8 6 18CombinationFlush/SurfaceFrontTopBottom66-1/0 (Cu),4-1/0 (Al)TGK24 or TGK32(order separately)TM18410C5125 30 14 10 30CombinationFlush/SurfaceFrontTop 111-3/0 (Cu),2/0-3/0 (Al)TGK32 (order separately) TM30412C125 30 14 10 30CombinationFlush/SurfaceFrontBottom 111-3/0 (Cu),2/0-3/0 (Al)TGK32 (order separately) TM30412CB150 24 12 8 24CombinationFlush/SurfaceFrontTop 111-3/0 (Cu),2/0-3/0 (Al)TGK32 (order separately) TM24415C150 24 12 8 24CombinationFlush/SurfaceFrontBottom 111-3/0 (Cu),2/0-3/0 (Al)TGK32 (order separately) TM24415CB150 30 14 10 30CombinationFlush/SurfaceFrontTop 111-3/0 (Cu),2/0-3/0 (Al)TGK32 (order separately) TM30415C150 30 14 10 30CombinationFlush/SurfaceFrontBottom 111-3/0 (Cu),2/0-3/0 (Al)TGK32 (order separately) TM30415CB150 42 20 14 42CombinationFlush/SurfaceFrontTop 131-3/0 (Cu),2/0-3/0 (Al)TGK42 (order separately) TM42415C150 42 20 14 42CombinationFlush/SurfaceFrontBottom 131-3/0 (Cu),2/0-3/0 (Al)TGK42 (order separately) TM42415CB200 24 12 8 24CombinationFlush/SurfaceFrontTop 111-300 (Cu),2/0-300 (Al)TGK32 (order separately) TM24420C200 24 12 8 24CombinationFlush/SurfaceFrontBottom 111-300 (Cu),2/0-300 (Al)TGK32 (order separately) TM24420CB4 Also UL Listed for three-phase, four-wire 240/120 Volts Hi leg delta and three-phase, three-wire 240 Volts ac branch breakers installed.5 100 Amp indoor devices UL listed for bottom-feed by installing complete unit upside-down.Note: See page 11-4, AL Series Lighting Panelboards as replacements for 300-600A load centers.This table continued on next pageMain Lugs Factory InstalledMainAmpereRatingSpacesSpacesSpacesTotalSpacesFeed TypeBoxNumberMain Wire Size(AWG/kcmil) Cu-AlGround KitProductNumber125 12 6 4 12 Top R3 6-2/0TGK12 or TGK24(order separately)TL12412R2150 18 8 6 18 Top R41-3/0 (Cu),2/0-3/0 (Al)TGK24 or TGK32(order separately)TL18415R2150 24 12 8 24 Top R41-3/0 (Cu),2/0-3/0 (Al)TGK24 or TGK32(order separately)TL24415R2200 18 8 6 18 Top R41-250 (Cu),2/0-250 (Al)TGK32 (order separately) TL18420R2200 30 14 10 30 Top R61-250 (Cu),2/0-250 (Al)TGK32 (order separately) TL30420R2200 42 20 14 42 Top R81-250 (Cu),2/0-250 (Al)TGK42 (order separately) TL42420R3225 42 20 14 42 Top R81-300 (Cu),2/0-300 (Al)TGK42 (order separately) TL42422R31 Also UL Listed for three-phase, four-wire 240/120 Volts ac delta and three-phase, three-wire 240 Volts ac branch breakers installed.2 Alternate main breaker 100 Amp max. THQL (10kAIC), THHQL (22kAIC) three-pole, use retainer THQLRK. See page 1-30.3 Not suitable for use as service entrance equipment.Load Center3PHMain LugsOutdoor NEMA 3RLoad Center3PHMain BreakerIndoor NEMA 1TM24420CB

Page 103

—PowerMark Plus™ Load CentersThree-Phase, Four-Wire, 208Y/120 Vac1Main Circuit Breaker Factory InstalledMainAmpereRatingSpacesSpacesSpacesTotalSpacesFrontTypeFeed TypeBoxNumberMain Wire Size(AWG/kcmil) Cu-AlGround KitProductNumber200 30 14 10 30CombinationFlush/SurfaceFrontTop 121-250 (Cu),2/0-250 (Al)TGK32 (order separately) TM30420C200 30 14 10 30CombinationFlush/SurfaceFrontBottom 121-250 (Cu),2/0-250 (Al)TGK32 (order separately) TM30420CB200 42 20 14 42CombinationFlush/SurfaceFrontTop 141-250 (Cu),2/0-250 (Al)TGK42 (order separately) TM42420C200 42 20 14 42CombinationFlush/SurfaceFrontBottom 141-250 (Cu),2/0-250 (Al)TGK42 (order separately) TM42420CB225 42 20 14 42CombinationFlush/SurfaceFrontTop 151-300 (Cu),2/0-300 (Al)(2) TGL2 (order separately) TM42422C225 42 20 14 42CombinationFlush/SurfaceFrontBottom 151-300 (Cu),2/0-300 (Al)(2) TGL2 (order separately) TM42422CB1 Also UL Listed for three-phase, four-wire 240/120 Volts Hi leg delta and three-phase, three-wire 240 Volts ac branch breakers installed.MainAmpereRatingSpacesSpacesSpacesTotalSpacesFeed TypeBoxNumberMain Wire Size(AWG/kcmil) Cu-AlGround KitProductNumber100 18 8 6 18 Top R46-1/0 (Cu),4-1/0 (Al)TGK24 or TGK32(order separately)TM18410R125 30 14 10 30 Top R71-3/0 (Cu),2/0-3/0 (Al)TGK32 (order separately) TM30412R150 24 12 8 24 Top R61-3/0 (Cu),2/0-3/0 (Al)TGK32 (order separately) TM24415R150 30 14 10 30 Top R71-3/0 (Cu),2/0-3/0 (Al)TGK32 (order separately) TM30415R200 30 14 10 30 Top R71-250 (Cu),2/0-250 (Al)TGK32 (order separately) TM30420R200 42 20 14 42 Top R81-250 (Cu),2/0-250 (Al)TGK42 (order separately) TM42420R225 42 20 14 42 Top R81-300 (Cu),2/0-300 (Al)TGK42 (order separately) TM42422RNote: See page 11-4, AL Series Lighting Panelboards as replacements for 300-600A load centers.Load Center3PHMain BreakerIndoor NEMA 1Load Center3PHMain BreakerOutdoor NEMA 3RTM42420CTM30420R

Page 104

—PowerMark Gold Load CentersSingle-Phase, Three-Wire, 120/240 VacProduct Features - Generator Panels - Suitable for use in accordance with Article 702 of the National Electrical Code, ANSI/NFPA 70 - Single-phase, 2 interlock 60A or 30A main breakers, 8 circuits max. - Safety and convenience when using a generator - 14,000 peak wattage, 11,520 continuous load, 48 amps at 240 volts. - Maintains power to such critical circuits as those for furnace, pump, refrigerator, lights. - Connected dual breaker mechanism ensures that only one source is active at a time.TL412R250GF TM830FCUGENGenerator Panels, Two Interlocked Main Breakers Factory InstalledMainAmpereRatingSpacesSpacesSpacesSpacesTotalSpacesFrontTypeFeed TypeBoxNumberMain Wire Size(AWG/kcmil) Cu-AlGround KitProductNumber30 4 2 8 4 8 Flush FrontTopBottom3A 6-1 TGK12 included TM830FCUGEN30 4 2 8 4 8 Surface FrontTopBottom3A 6-1 TGK12 included TM830SCUGEN60 4 2 8 4 8 Flush FrontTopBottom3A 6-1 TGK12 included TM860FCUGEN60 4 2 8 4 8 Surface FrontTopBottom3A 6-1 TGK12 included TM860SCUGENRiser PanelsMainAmpereRatingSpacesSpacesSpacesSpacesTotalSpacesFrontTypeFeed TypeBoxNumberMain Wire Size(AWG/kcmil) Cu-AlGround KitProductNumber125 20 10 40 20 40CombinationFlush/Surface FrontTop 9A 6-2/0 TGK12 (order separately) TLM2012CCURP125 12 6 24 10 24CombinationFlush/Surface FrontTop 4A 6-2/0 TGK12 (order separately) TLM1212CCURPTap kits required, order separately. See page 1-32.Auxiliary gutters available. See page 1-32.Spa PanelsMainAmpereRatingSpacesSpacesSpacesSpacesTotalSpacesLoad CenterTypeFeed TypeBoxNumberMain Wire Size(AWG/kcmil) Cu-AlGround KitProductNumber125 4 2 8 4 8Factory Included50A GFCITopBottom- 1-2/0 TGL1 installed TL412R250GF125 4 2 8 4 8Factory Included60A GFCITopBottom- 1-2/0 TGL1 installed TL412R260GFTwist Lock Power InletsReceptacles Amps  UL Product NumberL14-20 20 120/240 Canada, US T020NL14-30 30 120/240 Canada, US T030NCS637 50 120/240 Canada, US T050NGenerator Panels, Two Interlocked Main Breakers Factory InstalledMainAmpereRatingSpacesSpacesSpacesSpacesTotalSpacesFeed TypeBoxNumberMain Wire Size(AWG/kcmil) Cu-AlGround KitProductNumber30 4 2 8 4 8 Top R2A 6-1 TGK12 included TM830RCUGEN60 4 2 8 4 8 Top R2A 6-1 TGK12 included TM860RCUGENLoad CenterGenerator PanelsRiser PanelsSpa Panels

Page 105

Page 106

Page 107

Page 108

—ABB Inc.305 Gregson DriveCary, NC 27511electrification.us.abb.com © Copyright 2020 ABB. All rights reserved. Specifications subject to change without notice.Copyright 2021 ABB. All rights reserved.