—CONVERSION GUIDEEnclosed Breakers Transition GuideSpectra™ and Q-Line to FORMULA A2 and Tmax® XT• Spectra™ and Q-Line to Enclosed Circuit Breakers featuring:• Tmax® XT MCCBs,• NEMA 1 and 3R enclosures
2ENCLOSED CIRCUIT BREAKERS TRANSITION GUIDE—Transition from Spectra™ to Tmax® XTCombining ABB and GE Industrial Solutions leading-edge technologies offers you a new, comprehensive, one-line construction package.The June 2019 acquisition of GE Industrial Solutions by ABB brought together the best of two technologies. As part of the continuing development of a new, leading-edge and comprehensive one-line construction package, the Spectra RMS and RMS with microEntelliGuard® technology breakers will be retired and replaced by the Tmax XT circuit breakers in traditional GE Industrial Spectra series and ReliaGear™ neXT power panelboards, A-line lighting boards, switchboards, busway plugs and motor control centers.This brochure is designed to assist you in transitioning from EnclosedSpectra and Q-Line to Tmax XT and Formula A2.—Spectra performance rangeSE frame SF frame SG frame SK frameFrame size (A) 150 250 600 1200Poles 2, 3 2, 3 2, 3 2, 3Interrupt ratings (kA) 2 4 0 V A C 18, 65, 100, 200 65, 100, 200 65, 100, 200 65, 100, 200480 V AC 18, 25, 65, 100 35, 65, 100 35, 65, 100 50, 65, 100600 V AC 14, 18, 25 22, 25, 25 25, 65 25, 42, 65Dimensions (in.) Width 4.12 4.12 5.50 8.25Depth 3.38 3.81 3.81 5.50Height 6.31 10.12 10.09 15.50Trip units RMS X X X XmicroEntelliGuard – – X X
3ENCLOSED CIRCUIT BREAKERS TRANSITION GUIDE—Tmax XT MCCBs7 frame sizes to fit your applicationA new generation of innovative molded case circuit breakers, designed to save you both money and time.There’s a lot more to the SACE Tmax XT than meets the eye, and the benefits for your business can be significant. To start with, everything you need is self-contained within the breaker, requiring no external relays or other devices to purchase, install or wire. Second, the Tmax XT product range includes a wide array of options and accessories. An online configurator makes it easy to select and order exactly what you need and skip what you don’t. Then there’s installation. Tmax XT MCCBs can be installed in up to 40% less time than traditional circuit breakers, and you can update their electronic trip units in the field in as little as 5 minutes. And finally, Tmax XT provides plug-and-play communication that allows you to connect to the cloud and access 30% more information. All these advantages add up to help deliver substantial savings in time and money to your business.—Tmax XT performance rangeXT1 XT2 XT3 XT4 XT5 XT6 XT7Frame size (A) 125 125 225 250 600 800 1200Poles 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4Interruptrating (kA)240 V AC 50, 65, 100 65, 100, 150, 200 50, 65 65, 100, 150, 200 65, 100, 150, 200 65, 100, 200 65, 100, 200480 V AC 22, 35, 65 22, 35, 65, 100, 150, 200 25, 35 22, 35, 65, 100, 150, 200 35, 50, 65, 100, 150, 200 35, 50, 65 50, 65, 100600 V AC – 18, 22, 25, 35, 42 – 18, 22, 25, 50, 65, 100 18, 25, 35, 65, 100 20, 25, 35 25, 50, 65Dimensions (in.)Width 3.00 3.54 4.13 4.13 5.51 8.27 8.27Depth 2.75 3.25 2.75 3.25 4.07 4.07 6.57Height 5.12 5.12 5.90 6.30 8.07 10.55 10.55Trip units TMF X X X X – – –TMA – X – X X X –Ekip DIP – X – X X X XEkip Touch – X – X X – X—Tmax XT trip unit capability Features TMF TMA Ekip DIP Ekip TouchStandard protection X X X XLSIG – – X XAdjustability to 40% of rating – – X XConnectivity and communication – – – XEmbedded advanced functions – – – XOnline upgradability – – – X
4ENCLOSED CIRCUIT BREAKERS TRANSITION GUIDE—Selecting the right Tmax XT molded case circuit breakerOrder exactly what you need, skip what you don’tCorrect cross-referencingSpectra breakers come with four frame options (SE, SF, SG and SK). Tmax XT breakers have seven frames(XT1, XT2, XT3, XT4, XT5, XT6 and XT7), bringing you more options to get your most efficient cross-reference.*Rating plug into lower frame capacity = Consult lower frame*Most efficient cross = Thermal magnetic, 480 VPreliminary for reference only; subject to change.SE 150 ASF 250 ASG 600 ASK 1200 AXT1125 AXT3225 AXT4250 AXT2125 AUp to 65 kA480 V TM onlyUp to 100 kA at 480 V AC600 V electronic trip unit150 A or higherUp to 35 kA at 480 VUp to 225 A TM onlyUp to 250 A 600 VElectronic trip unitXT3225 AXT4250 AThermal magneticElectronic trip unitXT5600 AXT5600 AUp to 65 kA at 480 VUp to 35 kA at 600 V1000 A and higherAdvanced electronic trip unitXT6800 AXT71200 A
5ENCLOSED CIRCUIT BREAKERS TRANSITION GUIDE—Spectra RMS and RMS with microEntelliGuard molded case circuit breakersProduct number structureSpectra RMS catalog number constructionSpectra RMS with microEntelliGuard catalog number constructionFamilyDigitSSpectraFrame ratingDigitE150 AF250 AG600 AK1200 AInterruption ratingDigitD18 kA (65 kA2 )L65 kAH253/35 kAR100 kAS F 4 TA 2H 2A 5 00Continuous load ratingDigitA StandardH100%L100%R100%PolesDigit22 poles33 polesVoltage ratingDigit2240 V4480 V6600 VTrip unitDigitA RMS1Trip function DigitTLSI1Sensor (max. amps) Digit0 0 3 0 0 1 5 0 0 6 0 00 0 6 0 0 2 5 0 0 8 0 00 1 0 0 0 4 0 0 1 2 0 0S G 6 1C 3H 30 X XLFamilyDigitSSpectraFrameDigitG600 AK1200 AInterruption ratingDigitH35/501 kAL65 kAP100 kAT65 kA extended instantaneous (selective)5S100 kA extended instantaneous (selective)Continuous load ratingDigitCStandardH100%L100%P100%S100%T100%PolesDigit33 polesVoltage ratingDigit6600 V4480 V5Max. ampsDigit0 1150 A0 4400 A0 6600 A0 8800 A1 0 1000 A21 21200 ATrip functionDigitL 3LSI3L 4LSIGL 5LSIAL 7LSI-CP4Advanced protection functionsDigitXNoneMZSI (ST+GF) + neutral protectionKNeutral protectionNZSI (ST+GF) + RELT + neutral protectionZZS I (ST/GF )VRELT + neutral protectionTZS I (ST/GF/INST) PZSI (ST/GF/INST) + RELTRRELTSZSI (ST/GF/INST) + neutral protectionLZSI (ST+GF) + RELTWZSI (ST/GF/INST) + RELT + neutral protectionAdvanced features and meteringDigitXMetering (basic)2Metering (basic) + Modbus6Metering (adv.) + Modbus8Metering (adv.) + Modbus1 Adjustable instantaneous with tracking short time (long time established via interchangeable rating plugs)2 SGD rated 65 kA for 240 V (SG frame)3 25 kA for SE frame150 kA for SK frames2Max amps option 10 only available on 100% rated breakers3Without a control power connection, unless required by advanced protection functions or advanced features and communication4With a control power connection. The only valid trailing product digits for L7 are XX.5SC, SS, TC and TT catalog codes are optimized for selectivity (extended instantaneous) and will carry a 480 V AC max voltage rating
6ENCLOSED CIRCUIT BREAKERS TRANSITION GUIDE—Enclosed Circuit BreakersProduct number structure1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 181 & 2 VersionDigitX B4 Interrupting ratings – 480 V AC*Digits XT1 XT2 XT3 XT4 XT5 XT6 XT7N25 25 25 25 35 35 –S35 35 35 35 50 50 50H65 65 – 65 65 65 65L– 100 – 100 100 – 100V– 150 – 150 150 – –X– 200 – 200 200 – –5 Standard UL and IECDigitUUL 80%QUL 100%3 FrameDigit1 2 3 4 5 6 76 Number of polesDigit22 Poles33 Poles7, 8, 9 Frame ampsXT1–4 XT5–7Digits Amps Digits Amps0 1 0 102 5 A250 (XT5)0 1 5153 0 A300 (XT5)0 2 0 20 4 0 A400 (XT5)0 2 5 255 0 B500 (XT5)0 3 0 306 0 B600 (XT5)0 3 5356 0 0 600 (XT6)0 4 0 406 0 C600 (XT7)0 4 5458 0 0 800 (XT6)0 5 0 508 0 C800 (XT7)0 6 0 601 0 D1000 (XT7)0 7 0 701 2 E1200/1250 (XT7)0 8 0 800 9 0 901 0 0 1001 1 0 1101 2 51251 5 0 1501 7 51752 0 0 2002 2 52252 5 0 25010 Trip unitDigitA TMFB TMAC Ekip DIP LIG D MCSE Ekip DIP LS/IF Ekip DIP LSIG Ekip DIP LSIGJ Ekip DIP IK Ekip DIP M-IL Ekip DIP M-LIUM MA (MCP)N TMGP Ekip Touch LSIQ Ekip Touch LSIGR Ekip Touch Measuring LSIS Ekip Touch Measuring LSIGT Ekip Hi-Touch LSIU Ekip Hi-Touch LSIGW Ekip M Touch LRIUX Ekip G DIP LS/IY Ekip G Touch LSIGZ Ekip G Hi-Touch LSIGSee Tmax XT Technical Catalog for full list of accessoriesX B*For 240 V AC and 600 V AC ratings, refer to Tmax XT UL Technical Catalog.1IEC only.
7ENCLOSED CIRCUIT BREAKERS TRANSITION GUIDE—Transition from Q-Line to FORMULA A2Legacy Product Line: TQD & THQD Replacement Product Line: FORMULATQD & THQD 2 pole molded case circuit breakerFORMULA A2 2 pole molded case circuit breakerTQD & THQD 3 pole molded case circuit breakerFORMULA A2 3 pole molded case circuit breaker
8ENCLOSED CIRCUIT BREAKERS TRANSITION GUIDE—Affected Legacy ProductsTQD/THQD Product Number StructureType/Interrupt RatingTQD (10kA @ 240 VAC)THQD (22kA @ 240 VAC)Poles23Amperage150175200225LugsWL (Line & Load Lugs)Blank (Load Lugs)LL (No Lugs)X2 (Line Lugs Only)Voltage2 (240 VAC)3 2TQD 150 WL
9ENCLOSED CIRCUIT BREAKERS TRANSITION GUIDE—Replacement ProductsFORMULA A2 circuit breaker part number schemeFrame size2 250 A, ULNumber of poles-2 2-pole (UL and IEC)None 3-pole (UL and IEC)1) A1 1-pole UL only; A2 1-pole is not available.Trip unit functionTThermal-magnetic (UL and IEC)Type connectorsW NoneCurrent rating015 15 A (UL and IEC)020 20 A (UL and IEC)025 25 A (UL and IEC)030 30 A (UL and IEC)040 40 A (UL and IEC)050 50 A (UL and IEC)060 60 A (UL and IEC)070 70 A (UL and IEC)080 80 A (UL and IEC)090 90 A (UL and IEC)100 100 A (UL and IEC)125 125 A (UL and IEC)150 150 A (UL and IEC)160 160 A (UL and IEC)175 175 A (UL and IEC)200 200 A (UL and IEC)225 225 A (UL and IEC)250 250 A (UL and IEC)Interrupting rating classA Adequate (UL and IEC)N Normal (UL and IECA W
10ENCLOSED CIRCUIT BREAKERS TRANSITION GUIDE—Circuit Breaker EnclosuresNEMA Type 1Type 1, Indoor Surface or Flush MountingProduct Features - Suitable for use as service equipment (SE) as noted. - 60°C/75°C conductor ratings - Short circuit ratings are equal to the rating of the installed breaker. To order enclosed or accessorized circuit breakers, a configurator is available at: empower.abb.com—NEMA Type 1Certifications Product NumberFor 3P4W EnclosuresFor Enclosures with Ground Fault ProtectionMax. Ampere RatingFrame TypeNo. ofPolesULSEcULcULSE1CSA Flush SurfaceSurface,Blank End Wall2Neutral Product NumberNeutral Product Number3NeutralSensor for Ground Fault670THQL, TXQL, THQL-GF1, 2, 3 • • - - TQL70F4TQL70S4- Included - -100THQL, TXQL, THQL-GF1, 2, 3 • • - - TQL100F4TQL100S4- Included - -125 THQL 2 • • - - TQL125F TQL125S - Included - -100THQC, THHQC, TXQC1, 2, 3 • • - - TQC100F4TQC100S4- Included - -250 Formula A2 2, 3 • • - - A2ENCL250F A2ENCL250S - Included - -100SE150, THED, TED, TEB2, 3 • • - - TE100F TE100S TE100SB Included - -150SE150, THED, TED2, 3 • • • - TE150F TE150S TE150SB Included - -125 Tmax XT1 3 • • - - XT1ENCL125F XT1ENCL125S - Included - -125 Tmax XT2 3 • • - - XT2ENCL125F XT2ENCL125S - TNIA2255TNIA250XTGF 1SDA067211R1 (10A DIP)1SDA067212R1 (25A DIP)1SDA081983R1 (60A DIP)1SDA069143R1 (100A DIP)1SDA081984R1 (125A DIP)1SDA101971R1 (60A Touch)1SDA101972R1 (100A Touch)1SDA107406R1 (60A Touch V)1SDA107407R1 (100A Touch V)225 Tmax XT3 3 • • - - XT3ENCL225F XT3ENCL225S - Included - -1cUL Listed - Suitable for use as service equipment.2Enclosures with blank end walls (no Knockouts) and a feature to adjust the instantaneous setting on Spectra Circuit breakers.3Neutral for ground fault required to mount neutral sensor in enclosure.43-Pole breakers with an accessory cannot be installed in these enclosures.5For 250A rating, use copper cable only.6Neutral Sensor for Ground Fault requires connector cable KXTCECNEFP purchased separately.(Table continued on next page.)
11ENCLOSED CIRCUIT BREAKERS TRANSITION GUIDE—Circuit Breaker EnclosuresNEMA Type 1 —NEMA Type 1 (continued)Certifications Product NumberFor 3P4W EnclosuresFor Enclosures with Ground Fault ProtectionMax. Ampere RatingFrame TypeNo. ofPolesULSEcULcULSE1CSA Flush SurfaceSurface,Blank End Wall2Neutral Product NumberNeutral Product Number3NeutralSensor for Ground Fault7250 Tmax XT4 3 • • - - X T4ENCL250F XT4ENCL250S - TNIA2254TNIA250XTGF 1SDA066975R1 (40A DIP)1SDA081985R1 (60A DIP)1SDA066977R1 (100A DIP)1SDA081986R1 (150A DIP)1SDA081987R1 (225A DIP)1SDA066979R1 (250A DIP)1SDA101973R1 (Touch)1SDA10740 8R1 (Touch V)250 SF250 2, 3 • - - • SF250F SF250S SF250SB TNIA2254- -600 Tmax XT5 3 • • - - XT5ENCL600F XT5ENCL600S - TNIA400TNIA600TNIA400XTGFTNIA600XTGF1SDA101966R1 (250A DIP)1SDA105152R1 (300A DIP)1SDA105154R1 (400A DIP)1SDA105155R1 (600A DIP)1SDA101974R1 (Touch)1SDA10740 9R1 (Touch V)400 SG400 2, 3 • - - • SG400F SG400S SG400SB TNIA400 TNIA400VGTSRG201TSRG204600 SG600 2, 3 • - - • SG600F SG600S SG600SB TNIA600 TNIA600VG TSRG206800 Tmax XT6 3 • • - - XT6ENCL800F XT6ENCL800S - TNIA800 TNIA800XTGF1SDA105158R1 (800A)1200 Tmax XT7 3 • • - - XT7ENCL1200F XT7ENCL1200S - TNIA1200 TNIA1200XTGF 1SDA082134R11200 SK1200 2, 3 • - - • TK4V1200F5,6TK4V1200S5,6TK4V1200SB5,6TNIA400TNIA600TNIA800TNIA1200TNIAC1200TNIA800GTNIA1200GTSKG408TSKG410TSKG4121cUL Listed - Suitable for use as service equipment.2Enclosures with blank end walls (no Knockouts) and a feature to adjust the instantaneous setting on Spectra Circuit breakers.3Neutral for ground fault required to mount neutral sensor in enclosure.4For 250A rating, use copper cable only.5Not suitable for 100% rated 1200A SK breakers.6Suitable for parallel 500 kcmil maximum.7Neutral Sensor for Ground Fault requires connector cable KXTCECNEFP purchased separately.
12ENCLOSED CIRCUIT BREAKERS TRANSITION GUIDEType 3R, Outdoor, RaintightProduct Features - Suitable for use as service equipment (SE) as noted. - 60°C/75°C conductor ratings - Short circuit ratings are equal to the rating of the installed breaker. To order enclosed or accessorized circuit breakers, a configurator is available at: empower.abb.com—NEMA Type 3RCertificationsFor 3P4W EnclosuresFor Enclosures with Ground Fault ProtectionMax. Ampere RatingFrame TypeNo. ofPolesULSEcULcULSE1CSA Product Number9Neutral Product NumberNeutral Product Number2Neutral Sensor for Ground Fault10100 THQL, TXQL, THQL-GF 1, 2, 3 • - - • TQL70R3Included - -100 THQL, TXQL, THQL-GF 1, 2, 3 • - - • TQL100R3Included - -125 THQL 2 • - - • TQL125R Included - -100 THQC, THHQC, TXQC 1, 2, 3 • - - • TQC100R3Included - -250 Formula A2 2, 3 • • • - A2ENCL250R Included - -100 SE150, THED, TED, TEB 2, 3 • - - • TE100R Included - -125 Tmax XT1 3 • • • - XT1ENCL125R Included - -125 Tmax XT2 3 • • • - XT2ENCL125R TNIA2254TNIA250XTGF 1SDA067211R1 (10A DIP)1SDA067212R1 (25A DIP)1SDA081983R1 (60A DIP)1SDA069143R1 (100A DIP)1SDA081984R1 (125A DIP)1SDA101971R1 (60A Touch)1SDA101972R1 (100A Touch)1SDA107406R1 (60A Touch V)1SDA107407R1 (100A Touch V)150 SE150, THED, TED 2, 3 • - - • TE150R Included - -225 Tmax XT3 3 • • • - XT3ENCL225R Included - -250 Tmax XT4 3 • • • - XT4ENCL250 R TNIA2254TNIA250XTGF 1SDA066975R1 (40A DIP)1SDA081985R1 (60A DIP)1SDA066977R1 (100A DIP)1SDA081986R1 (150A DIP)1SDA081987R1 (225A DIP)1SDA066979R1 (250A DIP)1SDA101973R1 (Touch)1SDA107408R1 (Touch V)250 SF250 2, 3 • - - • TF225R TNIA2254- -1cUL Listed - Suitable for use as service equipment.2Neutral for ground fault required to mount neutral sensor in enclosure.33-Pole breakers with an accessory can not be installed in these enclosures.4For 250A rating, use copper cable only.5Suitable for parallel 250 kcmil maximum. If larger cable is required, use 600A enclosure.6Not suitable for 100% rated 1200A SK breakers.7Suitable for parallel 500 kcmil maximum.8Service rated equipment only.9100-250A devices have removable closing cap. Larger ampere devices require field cut openings. Order hubs separately. See page 7-10.10Neutral Sensor for Ground Fault requires connector cable KXTCECNEFP purchased separately.(Table continued on next page.)—Circuit Breaker EnclosuresNEMA Type 3R
13ENCLOSED CIRCUIT BREAKERS TRANSITION GUIDE—NEMA Type 3R (continued)CertificationsFor 3P4W EnclosuresFor Enclosures with Ground Fault ProtectionMax. Ampere RatingFrame TypeNo. ofPolesULSEcULcULSE1CSA Product Number9Neutral Product NumberNeutral Product Number2Neutral Sensor for Ground Fault10600 Tmax XT5 3 • • • - XT5ENCL600R TNIA400TNIA600TNIA400XTGFTNIA600XTGF1SDA101966R1 (250A DIP)1SDA105152R1 (300A DIP)1SDA105154R1 (400A DIP)1SDA105155R1 (600A DIP)1SDA101974R1 (Touch)1SDA107409R1 (Touch V)400 SG400 2, 3 • - - • SG400R TNIA400 TNIA400VGTSRG201TSRG204600 SG600 2, 3 • - - • SG600R TNIA600 TNIA600VG TSRG206800 Tmax XT6 3 • • • - XT6ENCL800R TNIA800 TNIA800XTGF1SDA107671R1 (600A)1SDA105158R1 (800A)1200 Tmax XT7 3 • • • - XT7ENCL1200R TNIA1200 TNIA1200XTGF 1SDA082134R11200 SK1200 2, 3 • - - • TK4V1200R6, 7TNIA400TNIA600TNIA800TNIA1200TNIAC1200TNIA800GTNIA1200GTSKG408TSKG410TSKG412—NEMA Type 3R with Factory Installed BreakerCertificationsFor 3P4W EnclosuresMax. Ampere RatingFrame TypeNo. ofPolesULSEcULcULSE1CSA Product Number9Neutral Product NumberNotes100 THQL, TXQL, THQL-GF 1, 2, 3 • • - - TQL70RE3Included 100A circuit breaker factory installed (2-pole)150 Formula A2 2 • • • - A2A250W150ECB Included 150A circuit breaker factory installed (2-pole)200 Formula A2 2 • • • - A2A250W200ECB Included 200A circuit breaker factory installed (2-pole)150 THQMV 2 • • • - THQMV150NRE8Included 150A circuit breaker factory installed (2-pole)200 THQMV 2 • • • - THQMV200NRE8Included 200A circuit breaker factory installed (2-pole)1cUL Listed - Suitable for use as service equipment.2Neutral for ground fault required to mount neutral sensor in enclosure.33-Pole breakers with an accessory can not be installed in these enclosures.4For 250A rating, use copper cable only.5Suitable for parallel 250 kcmil maximum. If larger cable is required, use 600A enclosure.6Not suitable for 100% rated 1200A SK breakers.7Suitable for parallel 500 kcmil maximum.8Service rated equipment only.9100-250A devices have removable closing cap. Larger ampere devices require field cut openings. Order hubs separately. See page 7-10.10Neutral Sensor for Ground Fault requires connector cable KXTCECNEFP purchased separately—Circuit Breaker EnclosuresNEMA Type 3R
14ENCLOSED CIRCUIT BREAKERS TRANSITION GUIDE—Guide for the migration process, focused on application requirementsQuestions to ask your customerWhat are your system requirements?1. What voltage do you need?2. What amperage do you need?3. What interrupting current do you need?4. How many poles do you need?5. Do you need 80% or 100% rated?What are your electrical requirements?1. What trip unit do you need?• L (overload protection) – Fixed or adjustable?• S (selective short circuit protection) – Yes (adjustable) or no?• I (short circuit protection) – Fixed or adjustable?• G (ground fault protection) – Yes or no?2. What will the application be?• General protection?• Motor protection?• Generator protection?• Molded case switch?3. Do you need communications/monitoring?• Bluetooth® connectivity?• Metering?• Monitoring?• Communication?• Cloud connectivity?Migration exampleYour customer currently uses a Spectra SF frame breaker, outlined below.What are your system requirements?1. What voltage do you need?• 480 V2. What amperage do you need?• 200 A3. What interrupting current do you need?• 65 kA4. How many poles do you need?• 3 poles5. Do you need 80% or 100% rated?• 80% rated What are your electrical requirements?1. What trip unit do you need?• L (overload protection), fixed2. What will the application be?• General protection3. Do you need communications/monitoring?• No communications/monitoringBased on the customer’s needs, ABB would suggest the following options:1. XT3 – Since the customer wants a thermal magnetic trip for a breaker rated 200 A at 480 V.2. XT4 – If the customer ends up needing an electronic trip unit or needs the ability to install the breaker into a Spectra power panelboard with the Spectra retrofit kit.System Spectra SF Tmax XT3 Tmax XT4Frame size (max.) (A) 250 225 250Interrupt rating (kA) 65 65 65Poles 3 3 3Voltage (V) 600 480 480Amperage (A) 250 200 200Trip unit Electronic trip Thermal magnetic Thermal magnetic, ETUDimensions (W X H X D) (in.)4.12 x 3.81 x 10.12 4.13 x 2.75 x 5.90 4.13 x 3.25 x 6.30
—ABB Inc. 305 Gregson DriveCary, NC 27511electrification.us.abb.comCustomer service:888-862-3290abbinsidesalessupport@us.abb.comMonday - Friday, 7am - 5:30pm, Central TimeTechnical Support: 888-437-3765Monday - Friday, 7am - 5pm, Central Time—We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB Inc. does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB Inc. © 2021 ABB Inc. All rights reserved1SXU930001G0201 12.2020